ABB Installation Products R2T35M4-N0380 Outdoor Ranger2 Cable Termination. 35kV, Cable Type - Tape Shield/Wire Shield/UniShield.…
UPC: 075114407236
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35 kV voltage rating for medium-voltage applications.
- Accommodates tape shield, wire shield, and UniShield cable types.
- Insulation diameter range from 0.84" to 2.10" for versatile compatibility.
- Non-tracking silicone housing with superior memory and weathering.
- Aluminum 2-hole spade connector for #2-1250 kcmil conductors.
Specifications
Application | Cable Termination, Outdoor Application, 35kV |
Color | Gray |
Conductor Size | 750 STR/COMPR kcmil , 900 COMPT/SOL kcmil |
Connection Type | 2-Hole Spade |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum |
Mounting | Product Need to have Cable Holder (not included) |
Series | Ranger2 |
Size | Insulation Range: 1.30 inch - 2.10 inch |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T15J4-N0380-B4
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Wire Size Stranded or Compressed 750 kcmil / Compact or Solid 900 kcmil. Stainless Steel Mounting Bracket 1.80 inch - 2.40 inch (45-61mm)
R2T28J4N2330-B3
Ranger2 Termination for 25/28 kV Outdoor Application, Cable Insulation Diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Copper 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500 kcmil or Compact Solid 600 kcmil. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)
R2T15M4-N2400-B3
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - Tape Shield/Wire Shield/Unshield Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 900 /Compact or Solid 1000. - Cable Mounting Bracket - Stainless Steel, 1.45 inch - 1.95 inch (37-50mm)
R2T15J2-N2360-B3
Ranger2 Termination, Outdoor, 15kv, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch (21mm-35mm), Connector Type - N2 - Copper 2-Hole Spade #2-1250 kcmil, 650 Stranded/Compressed or 750 Compact/Solid, B3 - Cable Mounting Bracket - Stainless Steel - 1.45 inch - 1.95 inch (37-50mm)
R2T15J4-N2440
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Tinned Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 1250 kcmil.
R2T35M2H0240
Outdoor Ranger2 Cable Termination. 35kV, Cable Type - Tape Shield/Wire Shield/UniShield. Insulation Range - .84 inch - 1.38 inch. Aluminum 1-Hole Spade #2-500 kcmil, Conductor 1/0 Stranded/Compressed AWG or 2/0 Compact/Solid AWG
R2T28M2-H0300
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .84 inch - 1.38 inch, Connector Type - Tinned Aluminum 1-Hole Spade #2-500 kcmil, Conductor Code - 300 -Stranded or Compressed 350 kcmil, Compact or Solid 400 kcmil.
69TCT212141PBBN
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 1 (Bore Diameter 1.55 inch, Insulation Range 1.65 to 1.9 inch), Connection Type - 2-Hole NEMA, Connector Type - Aluminum, Conductor Size Code 41P - 1.101 to 1.152 inch, Metallic Screen Kit - 1/0 Bonding Cable 6 foot with Two Split Bolts, Armor Kit - Heat Shrink, No Bracket RequiredFrequently Asked Questions
What is the maximum operating altitude for the R2T35?
The maximum operating altitude for the R2T35 is 3300 feet (1005 m).
What power system frequencies does the R2T35 support?
The R2T35 supports power system frequencies ranging from 48 to 62 Hz.
What is the ambient temperature range for the R2T35?
The R2T35 operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the maximum design voltage to ground for the R2T35?
The maximum design voltage to ground for the R2T35 is 22 kV.
What is the voltage rating of the R2T35 outdoor termination?
The R2T35 outdoor termination has a voltage rating of 35 kV.
What cable types are compatible with the R2T35 termination?
The R2T35 termination accommodates popular XLP and EPR cable types and shield constructions.
What cable gauges are compatible with the R2T35 termination?
The R2T35 termination accommodates cable gauges from #2 AWG through 1250 kcmil.
What cable insulation diameters does the R2T35 termination cover?
The R2T35 termination covers insulation diameters from 0.84 in (21.3 mm) to 2.10 in (53 mm).
What power system frequencies does the R2T35 support?
The R2T35 supports power system frequencies ranging from 48 to 62 Hz.
What cable gauges are compatible with the R2T35 termination?
The R2T35 termination accommodates cable gauges from #2 AWG through 1250 kcmil.
How to Install the R2T35M4-N0380 35kV Shrink Fit Silicone Rubber Termination
This guide provides step-by-step instructions for the safe and proper installation of the 35kV Ranger 2 Shrink fit Silicone Rubber Termination (R2T35M4-N0380) on tape shield, wire shield, or UniShield® cables for indoor/outdoor applications.
Estimated time: 2h
Tools needed:
Crimping tool, Wire strippers, Measuring tape, Approved solvent, Aluminum oxide abrasive (grit 120 or finer), Safety gloves
Supplies needed:
Silicone Rubber Termination Halves, Silicone Lubricant, Gray Silicone Rubber Tape, Constant Force Spring, Preformed Ground Braid, Sealing Mastic, Copper Foil Tape, Vinyl tape, Terminal lug, Connector (optional)
- Safety First: De-energize Apparatus
Before starting any work, ensure all apparatus in the work area are completely de-energized. Do not touch or move energized products. Failure to follow this instruction will result in serious or fatal injury. This product should only be installed by competent personnel trained in high voltage electrical equipment safety practices.
- Inspect Kit Contents and Cable Compatibility
Inspect all parts in the kit for completeness, damage, and compatibility with your cable and mating products. Ensure the cable size fits within the insulation range specified in the Termination Selection Chart. Read the entire installation instructions before starting and maintain cleanliness throughout the procedure.
- Prepare the Cable
Train the cable into its final position and cut it to the required length. Prepare the cable by removing the jacket, semi-conductor, and insulation according to the specified dimensions (e.g., 13-1/2” (340mm) jacket removal length, 2” (50mm) for terminal lug depth plus growth allowance, and 1” (25mm) tape shield insulation). Secure the edge of the tape shield with a single wrap of the supplied copper foil tape to prevent unrolling.
- Install the Ground Braid
Wrap one band of mastic (50% stretch) around the cable jacket 1/4” (6mm) from the jacket end. Position the preformed ground braid with the short tail over the tape shield and the solder block centered over the mastic. Secure the ground braid to the cable jacket with vinyl tape and press the solder block into the mastic. Apply a second mastic band over the solder block, maintaining the 1/4” (6mm) dimension, and then wrap two half-lapped layers of vinyl tape over the mastic seal. Finally, wrap the ground braid around the cable tape shield once, trim excess, and secure it with the constant force spring, cinching it tightly and securing with two wraps of vinyl tape.
- Install the Lug or Connector
Verify that the termination assembly can fit over the selected lug. If not, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core yet). Position the connector/lug and crimp it according to the manufacturer's instructions, leaving the last 3/8” to 1/2” uncrimped. Remove any excess oxide inhibitor and all sharp crimp flashings or edges following crimping.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent, taking care not to let the solvent touch the semi-conductive insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation, avoiding the semi-conductive shield. Be careful not to reduce the cable insulation diameter below that allowed by the kit.
- Install the Termination Body
Create a track-resistant moisture seal by wrapping gray silicone rubber electrical tape around the base of the terminal lug (1-2 layers, or build up to insulation diameter if the barrel is smaller). Liberally coat the edge of the semi-conductive insulation shield with silicone grease. For the lower termination, pull the loose end of the removable core through the top until it's flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise, ensuring the termination body remains butted against the mastic seal without pushing or pulling the assembly.
- Complete Termination Installation and Sealing
Using the second housing, carefully pull the core down to within one coil of the bottom. Slide the termination over the cable and carefully pull the core counter-clockwise, overlapping the first termination by 1-1/2” (40mm). Apply a thin film of silicone lubricant to the skirt and mastic seal area (avoiding skirt tabs), then carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal with the remaining gray silicone rubber electrical tape, overlapping the termination insulator by approximately 1” and extending over a non-crimped region of the lug/connector barrel with a half-lap configuration.
- Final Ground Connection and Verification
Connect the ground braid to the system ground. Finally, confirm that the High-K step does not exceed 1.5” and overlaps the cable semi-conductor.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.