ABB Installation Products R2T35J4-N0240-B3 Ranger2 Termination. Type - Outdoor, 35kV, Cable Type - Concentric Neutral/Jacketed…
UPC: 075114136259
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35 kV outdoor cable termination with shrink-fit technology
- Accommodates insulation diameters from 1.30" to 2.10" (#2 AWG to 1250 kcmil)
- Non-tracking silicone housing with 8 sheds for enhanced creepage and strike distances
- Includes B3 stainless steel cable mounting bracket (1.45"-1.95" OD)
- Rated for 22 kV max design voltage to ground, 200 kV BIL crest, 80 kV 10-sec wet withstand
Specifications
Application | Cable Termination, Outdoor Application, 35kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 1/0 STR AWG , 1/0 COMPR AWG , 2/0 SOL AWG , 2/0 COMPT AWG |
Connection Type | 2-Hole Spade connector |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum, Stainless Steel |
Mounting | Product Need to have Cable Holder (not included) |
Mounting Type | Cable Mounting with Bracket |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 1.30-2.10 inches (insulation diameter), 1.45-1.95 inches (cable bracket) |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T35J2-T0240
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead, Stranded or Compressed 1/0 /Compact or Solid 2/0
R2T35J4-N0290
Ranger2 Termination for 35KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 300 /Compact or Solid 350
R2T28M2-N2310
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .84 inch - 1.38 inch, Connector Type - Copper 2-Hole Spade #2-1250 kcmil, Conductor Code - 310 -Stranded or Compressed 400 Compact or Solid 500.
R2T28J4-N0410-B4
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 410 -Stranded or Compressed 1000 Compact or Solid N/A. Cable Mounting Bracket - B4 - Stainless Steel - Size 1.80 inch - 2.40inch.
R2T28M4N0300
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.
R2T15J1-T0240-B1
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Universal Aluminum Barrel for AL or CU Condutor with Copper Wire Lead #2-4/0, Conductor Code - 240 -Stranded or Compressed 1/0 Compact or Solid 2/0. Cable Mounting Bracket - B1 - Stainless Steel - Size .80 inch - 1.25 inch.
R2T15M2-N2300
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .84 inch - 1.38 inch, Connector Type - Copper 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.
R2T15M2-N0330
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.84 - 1.38 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. Includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500 /Compact or Solid 600Frequently Asked Questions
What is the creepage distance of the R2T35?
The creepage distance for the R2T35 termination is 30.0 inches (762 mm).
What cable sizes does the R2T35 termination support?
It supports insulation diameter cables from 0.84 in (21.3 mm) to 2.10 in (53 mm), covering #2 AWG through 1250 kcmil.
What cable types are compatible with the R2T35 termination?
The R2T35 termination accommodates popular XLP and EPR cable types and various shield constructions.
What is the voltage rating of the R2T35 termination?
The R2T35 termination has a voltage rating of 35 kV.
What is the maximum design voltage to ground for R2T35?
The maximum design voltage to ground for the R2T35 termination is 22 kV.
What is the operating ambient temperature range?
The R2T35 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the compatible power system frequency range?
The R2T35 termination is compatible with a power system frequency range of 48 to 62 Hz.
What are the mounting options for the R2T35 termination?
The R2T35 termination can be mounted free hanging or with an optional bracket.
Where can I find installation instructions for the R2T35?
Installation instructions are available as IS-1143 for R2T35J, IS-1144 for R2T35M, and IS-1145 for R2T35L.
How many sheds does the 35 kV outdoor model have?
The 35 kV outdoor model of the R2T35 termination has eight sheds.
How to Install the R2T35J 35kV Ranger 2 Cable Terminator
This guide provides step-by-step instructions for the safe and proper installation of the 35kV Ranger 2 Cable Terminator (R2T35J series) on concentric and jacketed concentric neutral cables for indoor/outdoor applications. Ensure all apparatus is de-energized and follow all safety protocols before beginning this high-voltage installation.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Approved solvent, Aluminum oxide abrasive (120 grit or finer, optional)
Supplies needed:
Silicone Rubber Termination Halves (2), Lubricant, Grey Silicone Rubber Tape (2 strips), Sealing Mastic (2 strips), Gloves, Terminal lug or connector, Vinyl tape or binding wire
- Prepare the Cable for Termination
DANGER: Ensure all apparatus is de-energized. Verify the cable size fits within the kit range. Train the cable into position and cut to the required length, allowing sufficient neutral wire length for grounding. Prepare the cable using the specified dimensions (13-1/2" or 13-3/4" jacket, 2" or 2-1/4" semi-con, plus barrel depth + 'X' for conductor). Allow additional exposed conductor distance to account for growth during crimping of aluminum lugs or connectors. Carefully wrap one band of sealing mastic around the cable jacket 1/4" (6mm) from the jacket end, using 50% stretch, and cut flush. Bend neutral wires back, press into the mastic, and secure to the cable jacket 4-6" (100-150mm) from the cut edge with vinyl tape or binding wire. Apply a second mastic band over the neutral wires and previous mastic, cut flush. Wrap two half-lapped layers of vinyl tape around the mastic seal, carefully maintaining the 1/4" (6mm) dimension.
- Install the Lug or Connector and Clean Cable Insulation
If using a lug that will not fit through the termination core, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core at this time). Position the terminal lug or connector and crimp it according to its directions, ensuring not to crimp the last 1/4" to 3/8" of the connector. Remove any excess oxide inhibitor and sharp crimp flashings following crimping. Wipe the cable insulation with an approved solvent, ensuring it does not touch the semi-con insulation shield. If an abrasive must be used, apply only aluminum oxide abrasive (grit 120 or finer) on the insulation only, being careful not to reduce the cable insulation diameter below that allowed by the kit.
- Install Termination Halves and Complete Sealing
Wrap a band of gray silicone rubber tape around the base of the terminal lug to create a track-resistant moisture seal, adjusting layers if barrel diameter differs from primary insulation. Cover the edge of the semi-con insulation shield with a liberal coating of silicone grease to fill the step at the semi-con cut off. For the lower termination with a fold-down skirt, pull the loose end of the removable core through the top until the core is flush with the bottom of the termination. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is butted up to the leading edge of the mastic seal. Using the second housing, carefully pull its core down within 1 coil of the bottom. Slide the terminator over the cable and carefully pull the core counterclockwise, overlapping the first terminator 1-1/2" (40mm). Apply a thin film of silicone lubricant to the skirt and mastic seal area (do not lubricate skirt tabs), then carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber tape, overlapping the termination insulator by approximately 1" and extending over a non-crimped region of the lug/connector barrel with a half-lap configuration. Twist concentric neutral wires together and connect them to the system ground. Finally, confirm that the High-K step does not exceed 1.5".
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.