ABB Installation Products R2T28M2-N2310 Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Tape Shield/Wire Shield/…
UPC: 075114164665
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Outdoor-rated 28kV termination
- Accommodates cable insulation from 0.84" to 1.38"
- Compatible with tape shield, wire shield, and unshielded cables
- Features a copper 2-hole spade connector
- Supports #2 AWG to 1250 kcmil conductors (stranded/compressed 400 kcmil, solid 500 kcmil)
Specifications
Application | Cable Termination, Outdoor Application, 28kV |
Cable Type | Copper Tape Shielded Wire |
Color | Gray |
Conductor Size | 400 to 500 kcmil |
Connection Type | 2-Hole Spade |
Earthing | Products Includes Their Own Grounding System |
Material | Copper |
Mounting | Product Need to have Cable Holder (not included) |
Mounting Type | Outdoor |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 0.84 inch - 1.38 inch |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 28kV |
Voltage Rating | 28 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2IT15J2-N2310-B2
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Copper 2-Hole Spade #2-1250 kcmil, Conductor Code - 310 -Stranded or Compressed 400 Compact or Solid 500. Cable Mounting Bracket - B2 - Stainless Steel - Size 1.10 inch - 1.50 inch.
R2T28J4-N0410-B4
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 410 -Stranded or Compressed 1000 Compact or Solid N/A. Cable Mounting Bracket - B4 - Stainless Steel - Size 1.80 inch - 2.40inch.
R2T28M4N0300
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.
R2T15J1-T0240-B1
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Universal Aluminum Barrel for AL or CU Condutor with Copper Wire Lead #2-4/0, Conductor Code - 240 -Stranded or Compressed 1/0 Compact or Solid 2/0. Cable Mounting Bracket - B1 - Stainless Steel - Size .80 inch - 1.25 inch.
R2T15M2-N2300
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .84 inch - 1.38 inch, Connector Type - Copper 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.
R2T15M2-N0330
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.84 - 1.38 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. Includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500 /Compact or Solid 600
R2T15M2-N0330-B2
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.84 - 1.38 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. Includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500 /Compact or Solid 600, Stainless Steel Mounting Bracket 1.10 inch - 1.50 inch
R2T15M2-N0280
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.84 - 1.38 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. Includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 250 /Compact or Solid 300Frequently Asked Questions
What cable sizes are compatible with the R2T28 termination?
The R2T28 termination covers insulation diameters from 0.84 inches (21.3 mm) to 2.10 inches (53 mm), accommodating #2 AWG through 1250 kcmil cables.
What is the voltage rating of the R2T28 termination?
The R2T28 termination has a voltage rating of 25/28 kV.
What is the maximum design voltage to ground for R2T28?
The maximum design voltage to ground for the R2T28 termination is 16 kV.
How many sheds does the R2T28 outdoor model have?
The R2T28 outdoor model features six sheds.
What is the creepage distance for the R2T28 termination?
The creepage distance for the R2T28 termination is 22.8 inches (579 mm).
What is the operating temperature range for the R2T28?
The R2T28 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What power system frequency does the R2T28 support?
The R2T28 termination supports a power system frequency range of 48 to 62 Hz.
What is the maximum altitude for R2T28 installation?
The R2T28 termination can be installed at a maximum altitude of 3300 feet (1005 m).
Where can I find installation instructions for the R2T28?
Installation instructions are available under IS-1134 for R2T28J, IS-1135 for R2T28M, and IS-1136 for R2T28L.
What is the operating temperature range for the R2T28?
The R2T28 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
How to Install the R2T28M2 Silicone Rubber Termination
This guide provides step-by-step instructions for installing the R2T28M2 Ranger 2 Shrink-fit Silicone Rubber Termination on 28kV cables, including cable preparation, ground braid installation, lug connection, and termination placement.
Estimated time: 1h 30m
Tools needed:
Crimping tool, Cable knife, Wire strippers
Supplies needed:
R2T28M2 Termination Kit, Terminal lug or connector, Vinyl tape, Approved solvent, Aluminum oxide abrasive (optional)
- Prepare Cable and Ensure Safety
DANGER: All apparatus must be de-energized during installation. Confirm the cable size fits the termination kit. Train the cable into position and cut to the required length. Prepare the cable by removing the jacket, semi-con, and insulation to the specified dimensions, allowing for terminal lug depth and conductor growth. Consult the specific cable type section (Tape Shield, Wire Shield, or UniShield®) for detailed preparation instructions, including managing shield wires or tape and using copper foil tape if applicable.
- Install Ground Braid
Apply one band of mastic around the cable jacket 1/4” (6mm) from the jacket end, stretching 50%. Position the preformed ground braid with the short tail over the shield (tape shield, drain wires, or unishield wires) and the solder block centered over the mastic. Secure the ground braid to the cable jacket with vinyl tape and press the solder block into the mastic. Apply a second mastic band over the solder block, maintaining the 1/4” (6mm) dimension. Wrap two half-lapped layers of vinyl tape over the mastic seal. Wrap the ground braid around the cable shield one complete wrap, trim excess, and secure with the constant force spring, wrapping in the same direction and cinching after the final winding. Secure the spring with two wraps of vinyl tape.
- Install Terminal Lug or Connector
Ensure the termination assembly fits over the selected lug. If not, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core yet). Position the connector/lug and crimp according to the manufacturer’s directions. For aluminum lugs, do not crimp the last 3/8” to 1/2” of the connector. Remove any excess oxide inhibitor and all sharp crimp flashings and edges after crimping.
- Clean Cable Insulation and Install Termination Body
Wipe the cable insulation with an approved solvent, ensuring solvent does not touch the semi-con insulation shield. If abrasive is necessary, use only aluminum oxide (grit 120 or finer) on insulation only, being careful not to reduce the cable insulation diameter. Create a track-resistant moisture seal by wrapping 1-2 layers of gray silicone rubber electrical tape around the base of the terminal lug. Cover the edge of the semi-con insulation shield with a liberal coating of silicone grease to fill the step. Pull the loose end of the removable core through the top of the termination until it is flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully remove the core by unwinding counter-clockwise, ensuring the termination body, not the core, is butted against the mastic seal. Do not push or pull on the termination assembly while removing the core.
- Complete Moisture Seal and Ground Connection
Apply a thin film of silicone lubricant to the skirt and mastic seal area, but not the skirt tabs. Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber electrical tape, overlapping the termination insulator by approximately 1” and extending over a non-crimped region of the lug/connector barrel with a half-lap configuration. Connect the ground braid to the system ground. Finally, confirm that the High-K step does not exceed 1.5”.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.