ABB - Installation Products R2T28J2-T0230 - Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For AL or CU Conductor w/copper wire lead #2 to 4/0. #1 Stranded to 1/0 Solid

ABB Installation Products R2T28J2-T0230 Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84…

UPC: 783786846290


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB Ranger2 Termination (SKU: R2T28J2-T0230) is a field-proven outdoor termination kit engineered for 25/28 kV medium-voltage cable systems. Designed for concentric neutral and jacketed concentric neutral cables, this termination supports insulation diameters from 0.84 to 1.38 inches (#2 AWG to 4/0 AWG), accommodating a broad range of conductor configurations. The universal aluminum barrel ensures compatibility with both aluminum (AL) and copper (CU) conductors, while the integrated copper wire lead provides reliable connectivity for stranded conductors up to 1/0 AWG and solid conductors up to 1/0 AWG. Key electrical performance metrics include a maximum design voltage to ground of 16 kV, a coronal extinction voltage of ≤3 pC at 22 kV, and a lightning impulse withstand rating of 150 kV crest. The termination delivers consistent dielectric integrity with a 10-second wet withstand of 60 kV (60Hz), 1-minute dry withstand of 65 kV (60Hz), and a 5-hour dry withstand of 55 kV (60Hz). For DC applications, it supports a 15-minute dry withstand of 105 kV. Constructed with a non-tracking silicone housing, the Ranger2 termination offers superior weathering resistance and long-term service life. The shrink-fit housing simplifies installation with common procedures and cable preparation dimensions, while the field-removable center core enhances flexibility. The six-shed design provides optimized creepage and strike distances (minimum 14.5 inches / 368 mm) for outdoor environments, ensuring reliable performance in power distribution networks, substations, and industrial facilities. Optional insulating silicone sleeves are available for applications requiring additional creepage or wildlife protection. The termination kit is part of the Ranger2 series, known for its robust construction and adherence to industry standards for medium-voltage cable accessories. Installation is streamlined with pre-engineered components, reducing labor time while maintaining high dielectric integrity. Ideal for utilities, contractors, and industrial operators, this termination delivers a durable, field-proven solution for medium-voltage cable terminations in outdoor applications.
  • Supports 25/28 kV medium-voltage cable systems with concentric neutral or jacketed concentric neutral cables
  • Universal aluminum barrel accommodates AL and CU conductors (#2 to 4/0 AWG)
  • Shrink-fit housing with field-removable center core for simplified installation
  • Six-shed design with minimum 14.5-inch strike distance and optimized creepage
  • Lightning impulse withstand rating of 150 kV crest; 10-second wet withstand of 60 kV (60Hz)

Specifications

Application
Cable Termination, Outdoor Application, 28kV
Cable Type
Concentric Neutral Wire
Color
Gray
Conductor Size
#1 STR AWG , #1 COMPR AWG , 1/0 SOL AWG , 1/0 COMPT AWG
Earthing
Products Includes Their Own Grounding System
Mounting
Product Need to have Cable Holder (not included)
Number Of Terminals
(1) Single Phase
Special Features
Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction
Standard
IEEE 48
Type
Cable Termination - Outdoor - Ranger2
Voltage Rating
28 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 230 -Stranded or Compressed #1 Compact or Solid 1/0.

R2T28J2-N0230

Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 230 -Stranded or Compressed #1 Compact or Solid 1/0.
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neutral/Jacketed Concentric Neutral Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 1000 . - Cable Mounting Bracket - Stainless Steel, 1.80 inch - 2.40 inch (45-61mm).

R2T28J4-N2410-B4

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neutral/Jacketed Concentric Neutral Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 1000 . - Cable Mounting Bracket - Stainless Steel, 1.80 inch - 2.40 inch (45-61mm).
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For AL or CU Conductor w/copper wire lead #2 to 4/0. 1/0 Stranded to 2/0 Solid

R2T28J2-T0240

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For AL or CU Conductor w/copper wire lead #2 to 4/0. 1/0 Stranded to 2/0 Solid
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum Barrel for AL Condutor only with Copper Wire Lead #2-4/0, Conductor Code - 230 -Stranded or Compressed #1 Compact or Solid 1/0. Cable Mounting Bracket - B2 - Stainless Steel - Size 1.10 inch - 1.50 inch.

R2T28J2-T1230-B2

Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum Barrel for AL Condutor only with Copper Wire Lead #2-4/0, Conductor Code - 230 -Stranded or Compressed #1 Compact or Solid 1/0. Cable Mounting Bracket - B2 - Stainless Steel - Size 1.10 inch - 1.50 inch.
28 kv, Ranger2, Outdoor Cable Termination, Concentric Neutral/Jacketed Concentric Neutral, Insulation Range .84-1.38 inch (21-35mm), Connector Type - Aluminum 1-Hole Spade #2-500 kcmil, Conductor Code 220 - Stranded or Compressed #2, Compact or Solid #1. Stainless Steel Cable Mounting Bracket .80-1.25 inch (20-32mm).

R2T28J2H0220-B1

28 kv, Ranger2, Outdoor Cable Termination, Concentric Neutral/Jacketed Concentric Neutral, Insulation Range .84-1.38 inch (21-35mm), Connector Type - Aluminum 1-Hole Spade #2-500 kcmil, Conductor Code 220 - Stranded or Compressed #2, Compact or Solid #1. Stainless Steel Cable Mounting Bracket .80-1.25 inch (20-32mm).
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neutral/Jacketed Concentric Neutral Cable, Aluminum 2-Hole Spade #2-1250kcmil, Stranded or Compressed 1000 . - Cable Mounting Bracket - Stainless Steel, 1.80 inch - 2.40 inch (45-61mm). L

R2T28J4-N0410-B4L

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neutral/Jacketed Concentric Neutral Cable, Aluminum 2-Hole Spade #2-1250kcmil, Stranded or Compressed 1000 . - Cable Mounting Bracket - Stainless Steel, 1.80 inch - 2.40 inch (45-61mm). L
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500 /Compact or Solid 600, Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch

R2T28J4-N0330-B3

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500 /Compact or Solid 600, Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed #2 /Compact or Solid #1

R2T28J2-T0220

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed #2 /Compact or Solid #1

Frequently Asked Questions

What is the maximum design voltage to ground for R2T28?

The maximum design voltage to ground for the R2T28 termination is 16 kV.

What is the creepage distance of the R2T28 termination?

The creepage distance for the R2T28 termination is 22.8 inches (579 mm).

What is the minimum strike distance of the R2T28 termination?

The minimum strike distance for the R2T28 termination is 14.5 inches (368 mm).

What cable types are compatible with the R2T28 termination?

The R2T28 units accommodate popular XLP and EPR cable types and shield constructions.

What is the maximum altitude for R2T28 installation?

The R2T28 termination can be installed at a maximum altitude of 3300 feet (1005 m).

What power system frequency does the R2T28 support?

The R2T28 termination supports a power system frequency range of 48 to 62 Hz.

What is the operating temperature range for the R2T28?

The R2T28 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).

What is the voltage rating for the R2T28 termination?

The R2T28 termination has a voltage rating of 25/28 kV.

What cable sizes does the R2T28 termination accommodate?

The R2T28 termination accommodates cables from #2 AWG through 1250 kcmil, covering insulation diameters from 0.84 inches to 2.10 inches.

What is the maximum design voltage to ground for R2T28?

The maximum design voltage to ground for the R2T28 termination is 16 kV.

How to Install the 28kV Ranger 2 Cable Termination (R2T28J2)

This guide provides step-by-step instructions for preparing the cable, installing the lug or connector, cleaning the cable insulation, and installing the R2T28J2 28kV Ranger 2 cable termination for indoor/outdoor applications. Ensure all apparatus is de-energized before starting.

Estimated time: 1h 30m

Tools needed:

Wire strippers, Crimping tool, Approved solvent, Aluminum oxide abrasive (grit 120 or finer, if needed)

Supplies needed:

Silicone Rubber Termination, Lubricant (Silicone lubricant), Grey Silicone Rubber Tape, Sealing Mastic, Gloves, Vinyl tape or binding wire, Elastimold copper or aluminum lugs (or other compatible lugs), Silicone grease

  1. Verify Kit and Cable Compatibility

    Check the contents of the package to ensure they are complete and undamaged. Confirm that all components, including the cable, fit within the kit's specified range (e.g., for R2T28J2, Dia. Over Insulation 0.84-1.38 inches (20-35mm), Dia. Over Jacket 1.72 inches (45mm) MAX).

  2. De-energize Apparatus and Prepare Work Area

    Ensure all apparatus is de-energized during installation. Gather all required tools and maintain cleanliness throughout the procedure. This product should only be installed by competent personnel trained in good safety practices involving high voltage electrical equipment.

  3. Train and Cut Cable

    Train the cable into its final position and cut it to the required length, ensuring sufficient neutral wire length for the grounding connection.

  4. Prepare Cable Insulation and Jacket

    Prepare the cable according to the dimensions provided in the instructions, allowing for the depth of the terminal lug and additional exposed conductor distance for aluminum lugs (e.g., 2 inches (50mm) for #2-350, 1/4 inch (6mm) for 400-650, 1/2 inch (13mm) for 750-1000, 3/4 inch (19mm) for 1000+). For R2T28J2, Dimension A is 10.5 inches (270mm).

  5. Apply First Mastic Band

    Using 50% stretch, carefully wrap one band of sealing mastic around the cable jacket 1/4 inch (6mm) from the jacket end. Position the mastic precisely as it serves as a marker for positioning the terminator. Cut the mastic flush without overlap.

  6. Secure Neutral Wires

    Bend the neutral wires back over the mastic and press them firmly into the sealing mastic. Secure the neutral wires to the cable jacket 4-6 inches (100-150mm) from the cut edge using vinyl tape or binding wire.

  7. Apply Second Mastic Band

    Using 50% stretch, apply a second mastic band over the neutral wires and the previously applied mastic. Cut this band flush without overlap.

  8. Seal Mastic with Vinyl Tape

    Wrap two half-lapped layers of vinyl tape around the mastic seal, carefully maintaining the 1/4 inch (6mm) dimension from the jacket end.

  9. Prepare for Lug Installation (If Needed)

    If the chosen lug or connector will not fit through the termination core, clean the cable insulation and slide the termination body onto the cable before installing the lug. Do not remove the core at this time.

  10. Install and Crimp Lug or Connector

    Position the connector or lug and crimp it according to the manufacturer's directions. Do not crimp the last 1/4 inch to 3/8 inch of the connector. After crimping, remove any excess oxide inhibitor and sharp crimp flashings.

  11. Clean Cable Insulation

    Wipe the cable insulation with an approved solvent. Exercise caution to prevent the solvent from touching the semi-con insulation shield.

  12. Abrasive Cleaning (If Necessary)

    If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation only. Do not use abrasive on the semi-con insulation shield, and ensure the cable insulation diameter is not reduced below the kit's allowed range.

  13. Apply First Silicone Tape Band

    Wrap a band of gray silicone rubber tape (from the kit) around the base of the terminal lug to create a track-resistant moisture seal. If the barrel diameter is smaller than the cable primary insulation, build up the tape band to equal the insulation diameter; otherwise, do not exceed two layers.

  14. Apply Silicone Grease to Semi-Con Edge

    Apply a liberal coating of silicone grease to the edge of the semi-con insulation shield. This grease is crucial for filling the step at the semi-con cut-off and does not serve as a lubricant for the termination body.

  15. Prepare Termination Core

    For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom of the termination.

  16. Slide and Position Termination Body

    Slide the termination body onto the cable, aligning the terminator with the forward edge of the mastic seal (under the vinyl tape).

  17. Remove Termination Core

    Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, remains butted up to the leading edge of the mastic seal. Do not push or pull on the termination assembly while removing the core material.

  18. Lubricate and Fold Down Skirt

    Apply a thin film of silicone lubricant to the skirt and mastic seal area, taking care to avoid the skirt tabs. Carefully fold down the skirt over the mastic seal.

  19. Complete Lug Area Moisture Seal

    Using the remaining gray silicone rubber tape, complete the lug area moisture seal. Overlap the termination insulator by approximately 1 inch and extend the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration.

  20. Connect Neutral Wires to Ground

    Twist the concentric neutral wires together and securely connect them to the system ground.

  21. Verify High-K Step

    Confirm that the High-K step does not exceed 1.5 inches.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.