ABB - Installation Products R2T28M2-N0260 - Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 inches for Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 3/0 /Compact or Solid 4/0

ABB Installation Products R2T28M2-N0260 Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84…

UPC: 783786065271


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB Ranger2 Termination (SKU: R2T28M2-N0260) is a high-performance outdoor termination system engineered for reliable 25/28KV power distribution applications in utility and industrial sectors. This termination is specifically designed to handle a cable insulation diameter range of 0.84 to 1.38 inches, ensuring compatibility with a wide variety of cable constructions including tape shield, wire shield, and unshielded cables. The kit includes a durable aluminum 2-hole spade connector, rated for conductor sizes from #2 AWG up to 1250 kcmil, providing flexibility for large-scale installations. This connector is engineered to accommodate stranded or compressed 3/0 AWG conductors, as well as solid 4/0 AWG conductors, making it suitable for both compact and solid cable configurations. The Ranger2 termination system ensures secure and efficient connection points for critical outdoor electrical infrastructure, maintaining electrical insulation integrity in exposed environments. Its robust design prioritizes long-term reliability and performance, meeting the stringent demands of outdoor power distribution networks. The termination is part of ABB's Ranger2 series, known for its advanced engineering and high-quality components in medium-voltage applications. UNSPSC Code: 26121648.
  • Designed for 25/28KV outdoor applications
  • Accommodates cable insulation diameter from 0.84 to 1.38 inches
  • Compatible with tape shield, wire shield, and unshielded cables
  • Includes aluminum 2-hole spade connector
  • Connector supports conductor sizes #2 - 1250 kcmil (stranded/compressed 3/0 AWG, solid 4/0 AWG)

Specifications

Application
Cable Termination, Outdoor Application, 28kV
Cable Type
Copper Tape Shielded Wire
Color
Gray
Conductor Size
360 kcmil , 4/0 AWG
Earthing
Products Includes Their Own Grounding System
Mounting
Product Need to have Cable Holder (not included)
Number Of Terminals
(1) Single Phase
Special Features
Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction
Standard
IEEE 48
Type
Cable Termination - Outdoor - Ranger2
Voltage Rating
28 kV
Package Dimensions (L x W x H)
3.62 IN x 15.5 IN x 4.75 IN
Package Dimensions (L x W x H)
9.1948 cm x 39.37 cm x 12.065 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neutral/Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 3/0 /Compact or Solid 4/0

R2T28J4-T0260

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neutral/Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 3/0 /Compact or Solid 4/0
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Includes Copper 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1/0 /Compact or Solid 2/0

R2T28J2-N2240

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Includes Copper 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1/0 /Compact or Solid 2/0
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Universal Aluminum Barrel for AL or CU Condutor with Copper Wire Lead #2-4/0, Conductor Code - 240 -Stranded or Compressed 1/0 Compact or Solid 2/0. Cable Mounting Bracket - B3 - Stainless Steel - Size 1.45 inch - 1.95 inch.

R2T28J2-T0240-B3

Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Universal Aluminum Barrel for AL or CU Condutor with Copper Wire Lead #2-4/0, Conductor Code - 240 -Stranded or Compressed 1/0 Compact or Solid 2/0. Cable Mounting Bracket - B3 - Stainless Steel - Size 1.45 inch - 1.95 inch.
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Universal Aluminum Barrel for AL or CU Condutor with Copper Wire Lead #2-4/0, Conductor Code - 270 -Stranded or Compressed 4/0 Compact or Solid 250. Cable Mounting Bracket - B3 - Stainless Steel - Size 1.45 inch - 1.95 inch.

R2T28J2-T0270-B3

Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Universal Aluminum Barrel for AL or CU Condutor with Copper Wire Lead #2-4/0, Conductor Code - 270 -Stranded or Compressed 4/0 Compact or Solid 250. Cable Mounting Bracket - B3 - Stainless Steel - Size 1.45 inch - 1.95 inch.
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Conductor 400 Stranded/Compressed or 500 Compact/Solid

R2T28J4-N0310

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Conductor 400 Stranded/Compressed or 500 Compact/Solid
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed #2 /Compact or Solid #1

R2T28J2-N0220

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed #2 /Compact or Solid #1
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - LC Shield Tape Shield/Wire Over Tape Shield, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1000

R2T28L4-N0410

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - LC Shield Tape Shield/Wire Over Tape Shield, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1000
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1000.

R2T28J4-N0410

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1000.

Frequently Asked Questions

What cable sizes are compatible with R2T28 terminations?

R2T28 terminations accommodate cables with insulation diameters from 0.84 in to 2.10 in, covering #2 AWG through 1250 kcmil.

What is the creepage distance for R2T28?

The creepage distance for the R2T28 termination is 22.8 inches (579 mm).

What is the minimum strike distance for R2T28?

The minimum strike distance for the R2T28 termination is 14.5 inches (368 mm).

What is the IEEE classification for the R2T28 outdoor termination?

The R2T28 outdoor termination has an IEEE Classification of Class 1A.

Where can I find installation instructions for R2T28?

Installation instructions are available as IS-1134 for R2T28J, IS-1135 for R2T28M, and IS-1136 for R2T28L.

What are the mounting options for the R2T28 termination?

The R2T28 termination can be mounted free hanging or with an optional bracket.

How many sheds does the R2T28 outdoor model have?

The R2T28 outdoor model features six sheds.

What is the maximum altitude for R2T28 operation?

The R2T28 termination can operate at a maximum altitude of 3300 feet (1005 m).

What power system frequency does R2T28 support?

The R2T28 termination supports a power system frequency range of 48 to 62 Hz.

What is the operating ambient temperature range for R2T28?

The R2T28 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).

How to Install the R2T28M2 Shrink-fit Silicone Rubber Termination

This guide provides detailed instructions for installing the 28kV Ranger 2 Shrink-fit Silicone Rubber Termination (R2T28M2) on tape shield cables, covering cable preparation, ground braid installation, lug connection, and termination placement.

Tools needed:

Wire strippers, Measuring tape, Crimping tool, Abrasive (aluminum oxide, grit 120 or finer, if needed)

Supplies needed:

R2T28M2 Termination Kit (includes termination, lubricant, gray silicone rubber tape, constant force spring, preformed ground braid, sealing mastic, copper foil tape, gloves), Vinyl electrical tape, Approved solvent, Compatible terminal lug or connector

  1. Preparation and Safety Check

    De-energize all apparatus in the work area before beginning installation. Inspect the kit contents for completeness and damage, and verify all components fit the cable and mating products. Gather all required tools and maintain cleanliness throughout the procedure. Ensure installation is performed only by competent personnel trained in good safety practices involving high voltage electrical equipment.

  2. Prepare the Cable

    Confirm the cable size is within the termination's insulation range as shown in the Termination Selection Chart. Train the cable into its final position and cut it to the required length for installation. Prepare the cable using the dimensions provided in Table 1 for jacket removal length, allowing for the depth of the terminal lug and additional exposed conductor distance for growth during crimping of aluminum lugs or connectors. To prevent the tape shield from unrolling, hold down its edge with a single wrap of the supplied copper foil tape.

  3. Install the Ground Braid

    Carefully wrap one band of sealing mastic around the cable jacket, 1/4 inch (6mm) from the jacket end, using 50% stretch. Position the mastic carefully as it also serves as a marker for the termination. Cut the mastic flush without overlap. Position the preformed ground braid with its short tail over the tape shield and the solder block centered over the mastic strip. Secure the ground braid to the cable jacket using vinyl tape and press the solder block firmly into the mastic. Apply a second mastic band (50% stretch) over the solder block and the previously applied mastic, maintaining the 1/4 inch (6mm) dimension, and cut flush. Wrap two half-lapped layers of vinyl tape around the mastic seal, carefully maintaining the 1/4 inch (6mm) dimension. Wrap the ground braid around the cable tape shield one complete wrap, trim any excess to prevent overlap, and secure it in place with the constant force spring. Wrap the spring in the same direction as the ground braid, cinch (tighten) the spring after wrapping the final winding, and secure it with two wraps of vinyl tape.

  4. Install the Terminal Lug or Connector

    Check to ensure the termination assembly fits over the selected lug. If the lug will not fit through the termination core, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core at this time). Position the connector or lug and crimp it according to the manufacturer’s directions. Do not crimp the last 3/8 inch to 1/2 inch of the connector. Remove any excess oxide inhibitor and all sharp crimp flashings and edges following crimping.

  5. Clean Cable Insulation and Lug Barrel

    Wipe the cable insulation with an approved solvent. Do not allow solvent to touch the semi-conductive insulation shield. If an abrasive must be used, apply it only to the insulation, not the semi-conductive insulation shield. Use only aluminum oxide abrasive, grit 120 or finer, and be careful not to reduce the cable insulation diameter below that allowed by the kit.

  6. Install the Termination Body

    Create a track-resistant moisture seal between the termination insulator and the lug/connector using the gray silicone rubber electrical tape from the kit. Wrap a band of silicone tape around the base of the terminal lug; if the barrel diameter is equal to or greater than the cable primary insulation, the tape band should not exceed 2 layers. If the barrel diameter is smaller, use the tape strip to form the tape band equal to the insulation diameter. Cover the edge of the semi-conductive insulation shield with a liberal coating of silicone grease to fill the step at the semi-con cut-off. On lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Make sure the termination body, not the core, is butted up to the leading edge of the mastic seal. Continue to remove the core, but do not push or pull on the termination assembly while removing it.

  7. Complete Termination Sealing and Grounding

    Apply a thin film of silicone lubricant to the skirt and mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal. With the termination installed, complete the lug area moisture seal using the remaining gray silicone rubber electrical tape. Overlap the termination insulator by approximately 1 inch and extend the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration. Connect the ground braid to the system ground. Finally, confirm that the High-K step does not exceed 1.5 inches.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.