ABB Installation Products R2T28J2-N0280 Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed…
UPC: 783786527069
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Outdoor-rated 28kV termination
- Compatible with Concentric Neutral/Jacketed Concentric Neutral cable
- Insulation Range: 0.84 inch - 1.38 inch
- Aluminum 2-Hole Spade Connector (#2 - 1250 kcmil)
- Conductor Code 280: Stranded/Compressed 250 kcmil, Solid 300 kcmil
Specifications
Application | Cable Termination, Outdoor Application, 28kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 250 to 300 kcmil |
Earthing | Products Includes Their Own Grounding System |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 28 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T28M2-N0280-B2
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 280 -Stranded or Compressed 250 kcmil or Compact or Solid 300 kcmil. Cable Mounting Bracket - 1.10 to 1.50 inch (28-38mm).
R2T15M4N2330-B3
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Copper 2-Hole Spade #2-1250 kcmil, Conductor Code - 330 -Stranded or Compressed 500 Compact or Solid 600. Cable Mounting Bracket - B3 - Stainless Steel - Size 1.45 inch - 1.95 inch.
R2T15M4-N2380-B3
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - Tape Shield/Wire Shield/Unshield Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 750 /Compact or Solid 900. - Cable Mounting Bracket - Stainless Steel, 1.45 inch - 1.95 inch (37-50mm)
R2T15M4-N0380-B3
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. Includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 750 /Compact or Solid 900 - Cable Mounting Bracket - Stainless Steel, 1.45 inch - 1.95 inch (37-50mm)
R2T15M4-N2350-B3
15 kv, Cable Terminator Ranger2, Outdoor, Cable Type - Tape Shield/Wire Shield/UniShield, Insulation Range 4 - 1.30 inch to 2.10 inch (33 mm to 53 mm), Connector Type N2 - Copper 2-Hole Spade #2-1250 kcmil, Conductor Code 350 - Compressed 600 or Compact 700, Cable Mounting Bracket B3 - Material Stainless Steel - Size - 1.45 inch to 1.95 inch (37mm - 50mm)
R2T15M4-N0380
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. Includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 750 /Compact or Solid 900
R2T15M2N2330
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .84 inch - 1.38 inch, Connector Type - Copper 2-Hole Spade #2-1250 kcmil, Conductor Code - 330 -Stranded or Compressed 500 Compact or Solid 600.
R2T15M2N2310
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .84 inch - 1.38 inch, Connector Type - Copper 2-Hole Spade #2-1250 kcmil, Conductor Code - 310 -Stranded or Compressed 400 Compact or Solid 500.Frequently Asked Questions
What is the voltage rating of the R2T28 termination?
The R2T28 termination has a voltage rating of 25/28 kV.
What is the maximum altitude for installation?
The maximum altitude range for installation of the R2T28 termination is 3300 feet (1005 m).
What is the creepage distance for the R2T28?
The creepage distance for the R2T28 termination is 22.8 inches (579 mm).
What is the minimum strike distance?
The minimum strike distance for the R2T28 termination is 14.5 inches (368 mm).
What is the power system frequency range?
The power system frequency range for the R2T28 termination is 48 to 62 Hz.
What is the ambient temperature range for operation?
The R2T28 termination can operate in an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the maximum design voltage to ground?
The maximum design voltage to ground for the R2T28 termination is 16 kV.
What cable sizes does the R2T28 termination accommodate?
It accommodates insulation diameters from 0.84 inches (21.3 mm) to 2.10 inches (53 mm), covering #2 AWG through 1250 kcmil cables.
What is the minimum strike distance?
The minimum strike distance for the R2T28 termination is 14.5 inches (368 mm).
What is the creepage distance for the R2T28?
The creepage distance for the R2T28 termination is 22.8 inches (579 mm).
How to Install the R2T28J2 28kV Ranger 2 Cable Termination
This guide provides step-by-step instructions for preparing the cable, installing the lug, cleaning the insulation, and installing the silicone rubber termination for 28kV Ranger 2 cable terminations on concentric and jacketed concentric neutral cables.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Approved solvent, Aluminum oxide abrasive (optional, grit 120 or finer), Vinyl tape or binding wire
Supplies needed:
Silicone Rubber Termination, Lubricant, Grey Silicone Rubber Tape, Sealing Mastic, Gloves, Connector or Lug, Silicone grease
- Perform Safety Checks and Initial Preparation
DANGER: Ensure all apparatus is de-energized before installation. This product must be installed by competent personnel trained in high voltage electrical equipment safety practices. Check the kit contents for completeness and damage. Verify all components fit the cable and mating products. Read the entire instructions and have all required tools ready, maintaining cleanliness throughout the procedure.
- Prepare the Cable for Termination
Confirm the cable size fits within the kit range. Train the cable into position and cut to the required length, allowing sufficient neutral wire length for grounding. Prepare the cable using the specified dimensions, accounting for terminal lug depth and conductor growth during crimping. Wrap one band of sealing mastic around the cable jacket 1/4 inch (6mm) from the jacket end, using 50% stretch, and cut flush without overlapping. Bend the neutral wires back over the mastic and secure them to the cable jacket 4-6 inches (100-150mm) from the cut edge using vinyl tape or binding wire. Apply a second mastic band over the neutral wires and the first mastic, using 50% stretch, and cut flush. Wrap two half-lapped layers of vinyl tape around the mastic seal, carefully maintaining the 1/4 inch (6mm) dimension.
- Install the Lug or Connector
If using a lug that does not fit through the termination core, clean the cable insulation and slide the termination onto the cable before installing the lug (do not remove the core at this time). Position the connector or lug and crimp it according to directions, ensuring not to crimp the last 1/4 to 3/8 inch of the connector. After crimping, remove any excess oxide inhibitor and sharp crimp flashings.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent, taking care not to allow the solvent to touch the semi-con insulation shield. If abrasive cleaning is necessary, use it only on the insulation, not the semi-con shield. Use only aluminum oxide abrasive, grit 120 or finer, and be careful not to reduce the cable insulation diameter below the kit's allowed range.
- Install the Termination Body
Create a track-resistant moisture seal by wrapping a band of gray silicone rubber tape around the base of the terminal lug. Adjust the number of tape layers based on whether the barrel diameter is equal to or smaller than the cable primary insulation. Liberally coat the edge of the semi-con insulation shield with silicone grease to fill the step at the semi-con cut-off. For terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is butted up to the leading edge of the mastic seal, and avoid pushing or pulling the termination assembly during core removal.
- Finalize Sealing and Grounding
Apply a thin film of silicone lubricant to the skirt and mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber tape, overlapping the termination insulator by approximately 1 inch and extending the tape wrapping over a non-crimped region of the lug or connector barrel with a half-lap configuration. Twist the concentric neutral wires together and connect them to the system ground. Finally, confirm that the High-K step does not exceed 1.5 inches.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.