ABB Installation Products R2T15M4-N0380 Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10…
UPC: 783786772971
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15KV outdoor termination for cable insulation diameters 1.30-2.10 inches
- Supports stranded/compressed conductors from #2 AWG to 1250 kcmil and solid conductors up to 900 kcmil
- Non-tracking silicone housing with superior weathering and memory characteristics
- Shrink-fit housing with field-removable center core for easy installation
- Four sheds for enhanced creepage and strike distances in outdoor environments
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Copper Tape Shielded Wire |
Color | Gray |
Conductor Size | 750 to 900 kcmil |
Connection Type | 2-Hole Spade connector |
Current Rating | 1250 A |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 1.30-2.10 inches (insulation diameter) |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T15M4-N2380-B3
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - Tape Shield/Wire Shield/Unshield Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 750 /Compact or Solid 900. - Cable Mounting Bracket - Stainless Steel, 1.45 inch - 1.95 inch (37-50mm)
R2T15M2N2330
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .84 inch - 1.38 inch, Connector Type - Copper 2-Hole Spade #2-1250 kcmil, Conductor Code - 330 -Stranded or Compressed 500 Compact or Solid 600.
R2T15M2N2310
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .84 inch - 1.38 inch, Connector Type - Copper 2-Hole Spade #2-1250 kcmil, Conductor Code - 310 -Stranded or Compressed 400 Compact or Solid 500.
R2T15M2-T0250
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 inches for Tape Shield, Wire Shield, and Unshielded Cable, includes Universal Aluminum Barrel For AL or CU Conductor w/copper wire lead
R2T15M4-N0350
15 kv, Cable Terminator Ranger2, Outdoor, Cable Type - Tape Shield/Wire Shield/UniShield, Insulation Range 4 - 1.30 inch to 2.10 inch (33 mm to 53 mm), Connector Type N0 - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code 350 - Compressed 650/Compact 750
R2T15J1-T0270
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For AL or CU Conductor w/copper wire lead #2 to 4/0. 4/0 Stranded or 250 kcmil Solid
R2T15J1-N0330
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 500 /Compact or Solid 600.
R2T35J2-N0250
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 2/0 /Compact or Solid 3/0Frequently Asked Questions
What cable insulation diameters does this termination support?
This ABB Ranger2 termination supports cable insulation diameters ranging from 1.30 to 2.10 inches.
What types of cables are compatible with this termination?
This termination is compatible with Tape Shield, Wire Shield, and UniShield cable types.
What conductor sizes does the included spade connector accommodate?
The aluminum 2-hole spade connector accommodates #2-1250 kcmil stranded or compressed conductors, and 900 kcmil solid conductors.
What is the voltage rating for this Ranger2 termination?
The Ranger2 termination is rated for 15KV outdoor applications.
Is this termination suitable for indoor use?
No, this ABB Ranger2 termination is specifically designed for 15KV outdoor applications.
How to Install the R2T15M4 Shrink Fit Silicone Rubber Termination
This guide provides step-by-step instructions for the safe and proper installation of the R2T15M4 15kV Shrink Fit Silicone Rubber Termination on tape shielded cables, including cable preparation, grounding, and termination sealing.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Utility knife, Measuring tape/ruler, Cleaning cloths/pads, Gloves
Supplies needed:
R2T15M4 Shrink Fit Silicone Rubber Termination Kit, Lubricant (Silicone Grease), Gray Silicone Rubber Electrical Tape, Preformed Ground Braid, Sealing Mastic, Copper Foil Tape, Vinyl Tape, Terminal lug/connector, Approved solvent, Aluminum oxide abrasive (grit 120 or finer)
- Safety and Initial Checks
DANGER: Ensure all apparatus is de-energized before starting. This product must be installed by competent personnel trained in high voltage safety. Inspect all kit contents for completeness, damage, rating, and compatibility with mating parts. Read these instructions fully before proceeding.
- Prepare the Cable
Verify the cable size fits within the termination's insulation range. Train the cable into position and cut to the required length. Prepare the cable by removing the jacket to a length of 7.5 inches (190mm) plus 2 inches (50mm) for terminal lug depth and additional growth allowance (1/4 to 3/4 inch for aluminum lugs). Secure the tape shield edge with a single wrap of the supplied copper foil tape.
- Install the Ground Braid
Wrap one band of mastic around the cable jacket 1/4 inch (6mm) from the jacket end, using 50% stretch, and cut flush. Position the preformed ground braid with the short tail over the tape shield and the solder block centered over the mastic strip; secure with vinyl tape and press the solder block into the mastic. Apply a second mastic band over the solder block. Wrap two half-lapped layers of vinyl tape around the mastic seal. Wrap the ground braid around the cable tape shield one complete wrap, trim excess, and secure with the constant force spring, cinching it tightly and securing with two wraps of vinyl tape.
- Install the Terminal Lug or Connector
Check that the termination assembly fits over the selected lug. If not, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core yet). Position the connector or lug and crimp according to the manufacturer's directions, ensuring not to crimp the last 3/8 to 1/2 inch of the connector. Remove any excess oxide inhibitor and all sharp crimp flashings and edges.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent, ensuring the solvent does not touch the semi-conductive insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation only, and be careful not to reduce the cable insulation diameter below the kit's allowed range.
- Prepare the Termination for Installation
Create a track-resistant moisture seal between the termination insulator and the lug/connector using the gray silicone rubber electrical tape. Wrap a band around the base of the terminal lug, using up to two layers if the barrel diameter is equal to or greater than the cable primary insulation, or building up the tape to the insulation diameter if the barrel is smaller. Liberally coat the edge of the semi-conductive insulation shield with silicone grease to fill the step. Pull the loose end of the removable core through the top of the termination until it is flush with the bottom.
- Install the Termination Body
Slide the termination body onto the cable. Align the termination with the forward edge of the mastic seal. Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure that the termination body, not the core, is butted up to the leading edge of the mastic seal. Continue to remove the core completely, taking care not to push or pull on the termination assembly during this process.
- Complete Termination Sealing
Apply a thin film of silicone lubricant to the skirt and mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber electrical tape, overlapping the termination insulator by approximately 1 inch and extending the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration.
- Final Grounding and Verification
Connect the installed ground braid securely to the system ground. Confirm that the High-K step of the termination does not exceed 1.5 inches (38mm) to ensure proper electrical performance and safety.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.