ABB - Installation Products R2T15J4-N0410 - Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. 1000 kcmil Stranded.

ABB Installation Products R2T15J4-N0410 Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10…

UPC: 783786785926


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB Ranger2 Termination (SKU: R2T15J4-N0410) is engineered for 15KV outdoor applications, providing reliable cable termination for both Concentric Neutral (CN) and Jacketed Concentric Neutral (JCN) cables. This termination system is designed to accommodate cable insulation diameters ranging from 1.30 to 2.10 inches, ensuring a secure fit for a variety of cable constructions. The included Aluminum 2-Hole Spade connector is versatile, supporting conductor sizes from #2 AWG up to 1250 kcmil, with specific compatibility for 1000 kcmil stranded conductors. This product is part of ABB's Installation Products catalog, known for its electrical infrastructure solutions. The Ranger2 termination ensures proper electrical connection and environmental sealing for medium-voltage outdoor power distribution systems. Its robust design addresses the critical need for dependable connections in exposed electrical environments. The UNSPSC code for this product is 26121648, categorizing it under electrical connectors and accessories.
  • 15KV outdoor termination for Concentric Neutral (CN) and Jacketed Concentric Neutral (JCN) cables.
  • Accommodates cable insulation diameters from 1.30 to 2.10 inches.
  • Includes Aluminum 2-Hole Spade connector compatible with #2 to 1250 kcmil conductors.
  • Specifically designed for 1000 kcmil stranded conductors.
  • Manufacturer: ABB - Installation Products.

Specifications

Application
Cable Termination, Outdoor Application, 15kV
Cable Type
Concentric Neutral Wire
Color
Gray
Conductor Size
1000 kcmil
Connection Type
2-Hole Spade connector
Current Rating
1000 kcmil
Earthing
Products Includes Their Own Grounding System
Material
Aluminum
Mounting
Product Need to have Cable Holder (not included)
Number Of Terminals
(1) Single Phase
Series
Ranger2
Size
1.30 - 2.10 (cable insulation diameter)
Special Features
Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction
Standard
IEEE 48
Type
Cable Termination - Outdoor - Ranger2
Voltage Rating
15 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - LC Shield Tape Shield/Wire Over Tape Shield, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1000, Cable Mounting Bracket - Stainless Steel, 1.45 inch - 1.95 inch (37-50mm)

R2T28L4-N0410-B3

Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - LC Shield Tape Shield/Wire Over Tape Shield, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1000, Cable Mounting Bracket - Stainless Steel, 1.45 inch - 1.95 inch (37-50mm)
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable. Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 350 /Compact or Solid 400.

R2T15J2-N0300

Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable. Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 350 /Compact or Solid 400.
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded, Conductor Code - 260 -Stranded or Compressed 360, Compact or Solid 4/0, includes Aluminum 2-Hole Spade connector for 1250 kcmil

R2IT15M1-N0260

Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded, Conductor Code - 260 -Stranded or Compressed 360, Compact or Solid 4/0, includes Aluminum 2-Hole Spade connector for 1250 kcmil
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84-1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 350 /Compact or Solid 400. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)

R2T15J2-N0300-B3

Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84-1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 350 /Compact or Solid 400. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. #1 Stranded or 1/0 Solid

R2IT15M1-N0230

Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. #1 Stranded or 1/0 Solid
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 750/ Compact or Solid 900. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)

R2T15J4-N0380-B3

Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 750/ Compact or Solid 900. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 4/0/ Compact or Solid 250. Stainless Steel Mounting Bracket .80 inch - 1.25 inch (20-32mm)

R2T15J2-T0270-B1

Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 4/0/ Compact or Solid 250. Stainless Steel Mounting Bracket .80 inch - 1.25 inch (20-32mm)
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed #1/ Compact or Solid 1/0 . Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (35-50mm)

R2T35M2-T0230-B3

Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed #1/ Compact or Solid 1/0 . Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (35-50mm)

Frequently Asked Questions

What is the maximum design voltage to ground?

The maximum design voltage to ground for the R2T15 is 9.5 kV.

What is the IEEE classification for this product?

The R2T15 termination has an IEEE Classification of Outdoor = Class 1A.

What is the power system frequency range?

The power system frequency range for this termination is 48 to 62 Hz.

What is the maximum altitude for installation?

The maximum altitude range for installation is 3300 feet (1005 m).

What is the operating ambient temperature range?

The R2T15 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).

What AWG cable sizes are compatible with R2T15?

The R2T15 termination accommodates cable sizes from #2 AWG through 1250 kcmil.

What cable insulation diameters does the R2T15 cover?

The R2T15 termination covers cable insulation diameters from 0.64 inches (16 mm) to 2.10 inches (53 mm).

What is the voltage rating of the R2T15 termination?

The R2T15 cable termination has a voltage rating of 15 kV.

What is the IEEE classification for this product?

The R2T15 termination has an IEEE Classification of Outdoor = Class 1A.

What cable insulation diameters does the R2T15 cover?

The R2T15 termination covers cable insulation diameters from 0.64 inches (16 mm) to 2.10 inches (53 mm).

How to Install the Ranger 2 Cable Termination (R2T15/28J)

This guide provides step-by-step instructions for preparing the cable, installing the lug or connector, cleaning the cable insulation, and installing the Ranger 2 Cable Termination for 15kV and 28kV indoor/outdoor applications.

Estimated time: 1h 30m

Tools needed:

Wire strippers, Cutting tool, Crimping tool, Vinyl tape, Binding wire (optional), Approved solvent, Aluminum oxide abrasive (grit 120 or finer, optional)

Supplies needed:

Silicone Rubber Termination, Lubricant, Grey Silicone Rubber Tape, Sealing Mastic, Gloves, Connector (optional), Cable Support Bracket (optional), Silicone grease

  1. Ensure Safety and Prepare Workspace

    De-energize all apparatus during installation or removal of parts to prevent serious or fatal injury. Verify kit contents are complete and undamaged. Check all components for proper fit with cable and/or mating products. Read the entire installation instructions before starting, and gather all required tools, maintaining cleanliness throughout the procedure.

  2. Prepare the Cable

    Check that the cable size fits within the kit range as shown in the Termination Selection Chart. Train the cable into position and cut it to the length required for installation, allowing sufficient neutral wire length for the grounding connection. Prepare the cable using the dimensions shown, ensuring to allow for the depth of the terminal lug and additional exposed conductor distance for growth during crimping of aluminum lugs or connectors.

  3. Apply First Mastic and Secure Neutral Wires

    Using 50% stretch, carefully wrap one band of sealing mastic around the cable jacket 1/4 inch (6mm) from the jacket end. Position the mastic carefully as it also serves as a marker for positioning the terminator; cut the mastic flush without overlapping. Bend the neutral wires back over and press them into the sealing mastic, then secure them to the cable jacket 4-6 inches (100-150mm) from the cut edge using vinyl tape or binding wire.

  4. Apply Second Mastic and Tape Seal

    Using 50% stretch, apply a second mastic band over the neutral wires and the previously applied mastic; cut it flush without overlapping. Wrap two half-lapped layers of vinyl tape around the mastic seal, carefully maintaining the 1/4 inch (6mm) dimension from the jacket end.

  5. Install Lug or Connector

    If using lugs that will not fit through the termination core, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core at this time). Position the connector/lug and crimp it according to directions, ensuring not to crimp the last 1/4 inch to 3/8 inch of the connector. Remove any excess oxide inhibitor and sharp crimp flashings after crimping.

  6. Clean Cable Insulation and Lug Barrel

    Wipe the cable insulation with an approved solvent, ensuring not to allow the solvent to touch the semi-con insulation shield. If an abrasive must be used, apply it only on the insulation (not the semi-con insulation shield), use only aluminum oxide abrasive (grit 120 or finer), and be careful not to reduce the cable insulation diameter below that allowed by the kit.

  7. Create Lug Moisture Seal with Silicone Tape

    Wrap a band of gray silicone rubber tape (contained in the kit) around the base of the terminal lug to create a track-resistant moisture seal between the termination insulator and the lug/connector. If the barrel diameter is equal to or greater than the cable primary insulation, the tape band should not exceed 2 layers. If the barrel diameter is smaller, use the tape strip to form the tape band equal to the insulation diameter.

  8. Apply Silicone Grease

    Cover the edge of the semi-con insulation shield with a liberal coating of silicone grease. On this product, the silicone grease does not serve as a lubricant; it must be used to fill the step at the semi-con cut-off.

  9. Prepare and Slide Termination Body

    On lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom of the termination. Slide the termination body onto the cable, aligning the terminator with the forward edge of the mastic seal.

  10. Remove Termination Core

    Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Make sure the termination body, not the core, is butted up to the leading edge of the mastic seal. Do not push or pull on the termination assembly while removing the core material.

  11. Lubricate and Fold Down Skirt

    Apply a thin film of silicone lubricant to the skirt and mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal.

  12. Complete Lug Area Moisture Seal

    With the termination installed, complete the lug area moisture seal using the remaining gray silicone rubber tape. Overlap the termination insulator by approximately 1 inch and extend the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration.

  13. Connect Neutral Wires to Ground

    Twist the concentric neutral wires together and connect them to the system ground.

  14. Confirm High-K Step

    Confirm that the High-K step does not exceed 1.5 inches.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.