ABB Installation Products R2T15J2-N0300 Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38…
UPC: 783786788804
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV voltage rating with maximum design voltage to ground of 9.5kV
- Supports cable insulation diameters from 0.84 to 1.38 inches
- Compatible with stranded/compressed conductors up to 1250kcmil and solid/compact conductors at 350/400kcmil
- Non-tracking silicone housing with superior weathering and memory characteristics
- Shrink-fit housing with field-removable center core for easy installation
- Four sheds for optimized creepage and strike distances
- Pull-down jacket seal feature for simplified installation
- Supports XLP and EPR cable types and shield constructions
- Optional connectors with copper stem, one-hole and two-hole spade connectors available
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 350 to 400 kcmil |
Earthing | Products Includes Their Own Grounding System |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T15J1-N0300
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.
R2IT15M1-N0260
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded, Conductor Code - 260 -Stranded or Compressed 360, Compact or Solid 4/0, includes Aluminum 2-Hole Spade connector for 1250 kcmil
R2T15J2-N0300-B3
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84-1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 350 /Compact or Solid 400. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)
R2IT15M1-N0230
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. #1 Stranded or 1/0 Solid
R2T15J4-N0380-B3
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 750/ Compact or Solid 900. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)
R2T15J2-T0270-B1
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 4/0/ Compact or Solid 250. Stainless Steel Mounting Bracket .80 inch - 1.25 inch (20-32mm)
R2T35M2-T0230-B3
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed #1/ Compact or Solid 1/0 . Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (35-50mm)
R2T15J4-N0330-B2
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500/ Compact or Solid 600. Plated Mild Steel Mounting Bracket 1.10 inch - 1.50 inch (28-38mm)Frequently Asked Questions
What is the voltage rating of this termination?
The termination is rated for 15kV outdoor applications.
What cable insulation diameters does this termination support?
The termination supports cable insulation diameters ranging from 0.84 to 1.38 inches.
What conductor sizes are compatible with this termination?
The termination supports conductors from 2 AWG up to 1250 kcmil, including stranded/compressed 350/400 kcmil or solid 400 kcmil.
Is this termination suitable for jacketed concentric neutral cables?
Yes, the Ranger2 termination is designed for both concentric neutral and jacketed concentric neutral cables.
How to Install the R2T15J2 Ranger 2 Cable Termination
This guide provides step-by-step instructions for the installation of the R2T15J2 Ranger 2 Cable Termination on concentric and jacketed concentric neutral cables for 15kV indoor/outdoor applications, including cable preparation, lug installation, and termination body placement.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Measuring tape or ruler, Utility knife or cable knife, Cleaning cloths
Supplies needed:
Silicone Rubber Termination (R2T15J2), Lubricant, Grey Silicone Rubber Tape (2 strips), Sealing Mastic (2 strips), Gloves, Vinyl tape or binding wire, Approved solvent, Aluminum oxide abrasive (grit 120 or finer, optional), Elastimold copper or aluminum lug/connector, Silicone grease
- Perform Pre-Installation Checks and Safety Procedures
De-energize all apparatus before starting installation. Inspect all kit contents for completeness, damage, and compatibility with the cable and mating products. Ensure all required tools are at hand and maintain cleanliness throughout the procedure. Read the entire installation instructions before proceeding. Safety Warning: This product should only be installed by competent personnel trained in high voltage electrical equipment safety practices. Failure to follow instructions can result in serious injury or product damage.
- Prepare the Cable
Verify the cable size fits within the kit's specified range (e.g., for R2T15J2, Dia. Over Insulation 0.84-1.38 inches). Train the cable into its final position and cut it to the required length, ensuring sufficient neutral wire length for grounding. Prepare the cable ends according to the provided dimensions, allowing for terminal lug depth and additional exposed conductor distance for aluminum lug crimping (e.g., 7.5 inches for Dimension A for R2T15J2). Wrap one band of sealing mastic around the cable jacket 1/4 inch (6mm) from the jacket end, stretching it to 50%. Cut the mastic flush without overlapping. Bend the neutral wires back over the mastic and secure them to the cable jacket 4-6 inches (100-150mm) from the cut edge using vinyl tape or binding wire. Apply a second band of mastic over the neutral wires and the first mastic band, stretching it to 50% and cutting it flush. Wrap two half-lapped layers of vinyl tape around the mastic seal, maintaining the 1/4 inch (6mm) dimension.
- Install the Lug or Connector
If using a lug that does not fit through the termination core, clean the cable insulation and slide the termination body onto the cable before installing the lug (do not remove the core yet). Position the chosen connector or lug and crimp it according to its specific directions, avoiding crimping the last 1/4 to 3/8 inch of the connector. Remove any excess oxide inhibitor and sharp crimp flashings after crimping.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent, ensuring the solvent does not touch the semi-con insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation only, avoiding the semi-con insulation shield. Do not reduce the cable insulation diameter.
- Prepare Termination for Installation
Create a track-resistant moisture seal by wrapping a band of gray silicone rubber tape around the base of the terminal lug. If the barrel diameter is smaller than the cable primary insulation, build up the tape band to equal the insulation diameter. Apply a liberal coating of silicone grease to the edge of the semi-con insulation shield to fill the step at the semi-con cut-off. For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until it is flush with the bottom.
- Install Termination Body
Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise from the loose end. Ensure the termination body, not the core, is butted against the leading edge of the mastic seal. Do not push or pull the termination assembly while removing the core material. Apply a thin film of silicone lubricant to the skirt and mastic seal area (avoiding skirt tabs). Carefully fold down the skirt over the mastic seal.
- Finalize Termination Seal and Grounding
Complete the lug area moisture seal using the remaining gray silicone rubber tape, overlapping the termination insulator by approximately 1 inch and extending over a non-crimped region of the lug/connector barrel with a half-lap configuration. Twist the concentric neutral wires together and connect them to the system ground. Confirm that the High-K step does not exceed 1.5 inches.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.