ABB - Installation Products R2T15J2-N0300-B3 - Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84-1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 350 /Compact or Solid 400. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)

ABB Installation Products R2T15J2-N0300-B3 Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84-1.38…

UPC: 783786803941


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB Ranger2 Termination, SKU R2T15J2-N0300-B3, is engineered for reliable 15KV outdoor applications. This termination system is specifically designed for Concentric Neutral and Jacketed Concentric Neutral cables, accommodating cable insulation diameters ranging from 0.84 to 1.38 inches. The included aluminum 2-hole spade is compatible with cable sizes from #2 to 1250 kcmil, supporting stranded or compressed 350 kcmil and compact or solid 400 kcmil conductors. The robust stainless steel mounting bracket ensures secure installation, with an adjustable range of 1.45 to 1.95 inches (37-50mm). This product is part of ABB's Installation Products catalog, offering a direct and functional solution for critical power distribution infrastructure. Its design prioritizes secure cable termination and reliable performance in outdoor electrical systems. Key specifications include: Cable Insulation Diameter: 0.84 - 1.38 inches. Conductor Compatibility: #2 - 1250 kcmil (Stranded/Compressed 350 kcmil, Compact/Solid 400 kcmil). Mounting Bracket Size: 1.45 - 1.95 inches (37-50mm). Application: 15KV Outdoor, Concentric Neutral and Jacketed Concentric Neutral Cable.
  • Designed for 15KV outdoor applications
  • Accommodates cable insulation diameters from 0.84 to 1.38 inches
  • Compatible with Concentric Neutral and Jacketed Concentric Neutral cables
  • Aluminum 2-hole spade for #2 - 1250 kcmil conductors
  • Includes stainless steel mounting bracket (1.45 - 1.95 inch adjustment)

Specifications

Application
Cable Termination, Outdoor Application, 15kV
Cable Type
Concentric Neutral Wire
Color
Gray
Conductor Size
350 to 400 kcmil
Earthing
Products Includes Their Own Grounding System
Mounting
Product Need to have Cable Holder (not included)
Number Of Terminals
(1) Single Phase
Special Features
Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction
Standard
IEEE 48
Type
Cable Termination - Outdoor - Ranger2
Voltage Rating
15 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.

R2T15J1-N0300

Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. #1 Stranded or 1/0 Solid

R2IT15M1-N0230

Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. #1 Stranded or 1/0 Solid
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 750/ Compact or Solid 900. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)

R2T15J4-N0380-B3

Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 750/ Compact or Solid 900. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 4/0/ Compact or Solid 250. Stainless Steel Mounting Bracket .80 inch - 1.25 inch (20-32mm)

R2T15J2-T0270-B1

Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 4/0/ Compact or Solid 250. Stainless Steel Mounting Bracket .80 inch - 1.25 inch (20-32mm)
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed #1/ Compact or Solid 1/0 . Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (35-50mm)

R2T35M2-T0230-B3

Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed #1/ Compact or Solid 1/0 . Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (35-50mm)
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500/ Compact or Solid 600. Plated Mild Steel Mounting Bracket 1.10 inch - 1.50 inch (28-38mm)

R2T15J4-N0330-B2

Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500/ Compact or Solid 600. Plated Mild Steel Mounting Bracket 1.10 inch - 1.50 inch (28-38mm)
Ranger2 Termination for 35KV outdoor application, cable insulation diameter 1.30 - 2.10 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 through 1250 kcmil. Conductor Code 330 - 500 kcmil Stranded/Compressed or 600 kcmil Compact/Solid.

R2T35J4-N0330

Ranger2 Termination for 35KV outdoor application, cable insulation diameter 1.30 - 2.10 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 through 1250 kcmil. Conductor Code 330 - 500 kcmil Stranded/Compressed or 600 kcmil Compact/Solid.
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84-1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 400 /Compact or Solid 500. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)

R2T15J2-N0310-B3

Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84-1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 400 /Compact or Solid 500. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)

Frequently Asked Questions

What is the IEEE classification for the R2T15 outdoor termination?

The IEEE Classification for the R2T15 outdoor termination is Class 1A.

What are the available sizes for the R2T15 termination?

The R2T15 termination is available in sizes 1, 2, and 4.

What is the Lightning Impulse Withstand (BIL) for R2T15?

The Lightning Impulse (BIL Dry 110 Withstand) for the R2T15 termination is 110 kV Crest.

What is the maximum design voltage to ground for R2T15?

The maximum design voltage to ground for the R2T15 termination is 9.5 kV.

What is the power system frequency range for R2T15?

The R2T15 termination is designed for power system frequencies ranging from 48 to 62 Hz.

What is the maximum altitude for R2T15 installation?

The R2T15 termination can be installed at altitudes up to 3300 feet (1005 m) maximum.

What is the operating temperature range for the R2T15?

The ambient temperature range for the R2T15 termination is -22 to +149 °F (-30 to +65 °C).

What is the voltage rating of the R2T15 termination?

The R2T15 cable termination has a voltage rating of 15 kV.

What are the available sizes for the R2T15 termination?

The R2T15 termination is available in sizes 1, 2, and 4.

What is the operating temperature range for the R2T15?

The ambient temperature range for the R2T15 termination is -22 to +149 °F (-30 to +65 °C).

How to Install Ranger 2 Cable Termination (R2T15/28J Series)

This guide provides step-by-step instructions for the installation of 15kV and 28kV Ranger 2 Cable Terminations for both indoor and outdoor applications, suitable for concentric and jacketed concentric neutral cables. Ensure all apparatus are de-energized before beginning.

Estimated time: 1h

Tools needed:

Wire strippers, Crimping tool, Approved solvent, Aluminum oxide abrasive (grit 120 or finer, if needed), Gloves

Supplies needed:

Silicone Rubber Termination, Lubricant, Grey Silicone Rubber Tape, Sealing Mastic, Terminal lug or connector, Cable Support Bracket (optional), Vinyl tape, Binding wire, Silicone grease

  1. Perform Pre-Installation Checks and Safety Measures

    Ensure all apparatus are de-energized during installation or removal of parts. Check package contents for completeness and damage. Verify all components fit the cable and mating products. Read the entire instructions and have all required tools and supplies ready, maintaining cleanliness throughout the procedure. Do not touch or move energized products.

  2. Prepare the Cable for Termination

    Confirm the cable size fits within the kit range as shown in the Termination Selection Chart. Train the cable into position and cut to the required length, allowing sufficient neutral wire length for grounding. Prepare the cable using the dimensions shown in Table 1 and Figure 1, allowing for terminal lug depth and additional exposed conductor distance for aluminum lugs.

  3. Apply First Mastic Band and Secure Neutral Wires

    Using 50% stretch, carefully wrap one band of sealing mastic around the cable jacket 1/4 inch (6mm) from the jacket end. Position it carefully as it also serves as a marker for positioning the terminator, and cut flush without overlapping. Bend neutral wires back over the mastic and press them into it, then secure them to the cable jacket 4-6 inches (100-150mm) from the cut edge using vinyl tape or binding wire.

  4. Apply Second Mastic Band and Vinyl Tape Seal

    Using 50% stretch, apply a second mastic band over the neutral wires and the previously applied mastic, cutting it flush without overlapping. Wrap two half-lapped layers of vinyl tape around this mastic seal, carefully maintaining the 1/4 inch (6mm) dimension from the jacket end.

  5. Install the Terminal Lug or Connector

    If using a lug that will not fit through the termination core, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core at this time). Position the connector/lug and crimp it according to its directions, avoiding crimping the last 1/4 to 3/8 inch. Remove any excess oxide inhibitor and sharp crimp flashings following crimping.

  6. Clean Cable Insulation and Lug Barrel

    Wipe the cable insulation with an approved solvent, ensuring the solvent does not touch the semi-con insulation shield. If abrasive must be used, apply it only on the insulation (not the semi-con shield), using aluminum oxide abrasive (grit 120 or finer), and be careful not to reduce the cable insulation diameter below that allowed by the kit.

  7. Create Initial Moisture Seal with Silicone Tape

    Wrap a band of gray silicone rubber tape (contained in kit) around the base of the terminal lug to create a track-resistant moisture seal between the termination insulator and the lug/connector. If the barrel diameter is equal to or greater than the cable primary insulation, the tape band should not exceed 2 layers. If smaller, use the tape strip to form the tape band equal to the insulation diameter.

  8. Apply Silicone Grease and Position Termination Body

    Cover the edge of the semi-con insulation shield with a liberal coating of silicone grease; this grease must be used to fill the step at the semi-con cut-off. On lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal.

  9. Remove Termination Core

    Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Make sure the termination body, not the core, remains butted up to the leading edge of the mastic seal. Do not push or pull on the termination assembly while removing the core material.

  10. Lubricate and Fold Down Skirt

    Apply a thin film of silicone lubricant to the skirt and mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal.

  11. Complete Lug Area Moisture Seal and Ground Neutral Wires

    With the termination installed, complete the lug area moisture seal using the remaining gray silicone rubber tape. Overlap the termination insulator by approximately 1 inch and extend the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration. Twist the concentric neutral wires together and connect them to the system ground.

  12. Confirm High-K Step Dimension

    Confirm that the High-K step does not exceed 1.5 inches.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.