ABB Installation Products R2T15J2N0270-B1 Ranger 2 Terminator, Outdoor, 15kV, Concentric Neutral/Jacketed Concentric Neutral Cable…
UPC: 075114402248
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV Voltage Rating for medium-voltage applications
- Aluminum 2-Hole Spade Connector for #2 - 1250 kcmil cable
- Accommodates 0.84 - 1.38 inch (21-35mm) insulation range
- Designed for Concentric Neutral/Jacketed Concentric Neutral cable
- Includes Stainless Steel Cable Mounting Bracket (0.80 - 1.25 inch)
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 4.0 STR/COMPR AWG , 250 SOL/COMPT kcmil |
Earthing | Products Includes Their Own Grounding System |
Mounting | Stainless Steel Cable Mounting Bracket |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction. Stainless Steel Cable Mounting Bracket |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

PCT10270-3
15kV, Single Piece Terminator (Class 1), Two Hole Spade Lug. Power Cable Termination, Conductor Size - 4/0 Stranded/Compressed, Use for Insulation Diameter Range from .640 to 1.070 inches.
R2T35M2-H0250
Outdoor Ranger2 Cable Termination. 35kV, Cable Type - Tape Shield/Wire Shield/UniShield. Insulation Range - .84 inch - 1.38 inch. Aluminum 1-Hole Spade #2-500 kcmil, Conductor 2/0 Stranded/Compressed AWG or 3/0 Compact/Solid AWG
R2T35M4-N0380
Outdoor Ranger2 Cable Termination. 35kV, Cable Type - Tape Shield/Wire Shield/UniShield. Insulation Range - 1.30 inch - 2.10 inch. Aluminum 2-Hole Spade #2-1250 kcmil, Conductor 750 kcmil Stranded/Compressed or 900 kcmil Compact/Solid
R2T28J4N2330-B3
Ranger2 Termination for 25/28 kV Outdoor Application, Cable Insulation Diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Copper 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500 kcmil or Compact Solid 600 kcmil. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)
R2T15M4-N2400-B3
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Cable Type - Tape Shield/Wire Shield/Unshield Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 900 /Compact or Solid 1000. - Cable Mounting Bracket - Stainless Steel, 1.45 inch - 1.95 inch (37-50mm)
R2T15J4-N0380-B4
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Wire Size Stranded or Compressed 750 kcmil / Compact or Solid 900 kcmil. Stainless Steel Mounting Bracket 1.80 inch - 2.40 inch (45-61mm)
R2T15J2-N2360-B3
Ranger2 Termination, Outdoor, 15kv, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch (21mm-35mm), Connector Type - N2 - Copper 2-Hole Spade #2-1250 kcmil, 650 Stranded/Compressed or 750 Compact/Solid, B3 - Cable Mounting Bracket - Stainless Steel - 1.45 inch - 1.95 inch (37-50mm)
R2T15J4-N2440
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Tinned Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 1250 kcmil.Frequently Asked Questions
What is the ambient temperature range for operation?
The R2T15 operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the maximum design voltage to ground?
The maximum design voltage to ground for the R2T15 termination is 9.5 kV.
What is the voltage rating of the R2T15 termination?
The R2T15 outdoor cable termination has a voltage rating of 15 kV.
What cable insulation diameters does this termination support?
The R2T termination supports insulation diameters from 0.64 inches (16 mm) to 2.10 inches (53 mm).
What cable insulation diameters does this termination support?
The R2T termination supports insulation diameters from 0.64 inches (16 mm) to 2.10 inches (53 mm).
What is the voltage rating of the R2T15 termination?
The R2T15 outdoor cable termination has a voltage rating of 15 kV.
What is the maximum design voltage to ground?
The maximum design voltage to ground for the R2T15 termination is 9.5 kV.
What is the ambient temperature range for operation?
The R2T15 operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
Where can I find installation instructions for R2T15?
Installation instructions are IS-1134 for R2T15J, IS-1135 for R2T15M, and IS-1136 for R2T15L.
What items are included in a standard R2T15 kit?
A kit includes a Ranger2 Housing, silicone lubricant, plastic glove, butyl auto tape, and silicon tape roll. Connectors and support brackets are optional.
How to Install the R2T15/28J Ranger 2 Cable Termination
This guide provides step-by-step instructions for the safe and proper installation of 15kV & 28kV Ranger 2 Cable Terminations for indoor/outdoor applications on concentric and jacketed concentric neutral cables. All apparatus must be de-energized during installation. This product should be installed only by competent personnel trained in high voltage electrical equipment safety.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Approved solvent, Aluminum oxide abrasive (grit 120 or finer, optional)
Supplies needed:
Silicone Rubber Termination, Lubricant, Grey Silicone Rubber Tape, Sealing Mastic, Gloves, Elastimold copper or aluminum lugs, Cable Support Bracket (optional), High voltage insulated cap(s) or connector(s), Vinyl tape or binding wire
- Prepare the Cable
Verify the cable size fits within the kit range. Train the cable into position and cut to the required length, allowing sufficient neutral wire length for grounding. Prepare the cable jacket, semi-con, and insulation to specified dimensions, accounting for terminal lug depth and conductor growth during crimping.
- Apply Mastic and Secure Neutral Wires
Using 50% stretch, carefully wrap one band of sealing mastic around the cable jacket 1/4” (6mm) from the jacket end; cut flush without overlap. Bend neutral wires back over and press into the mastic, securing them to the cable jacket 4-6” (100-150mm) from the cut edge using vinyl tape or binding wire. Apply a second mastic band over the neutral wires and previous mastic, cutting flush. Wrap two half-lapped layers of vinyl tape over the mastic seal.
- Install the Lug or Connector
If using non-Elastimold lugs that won't fit through the termination core, clean the insulation and slide the termination onto the cable before installing the lug. Position the connector/lug and crimp according to directions, leaving the last 1/4” to 3/8” uncrimped. Remove excess oxide inhibitor and sharp crimp flashings.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent, ensuring it does not touch the semi-con insulation shield. If necessary, use aluminum oxide abrasive (grit 120 or finer) on the insulation only, being careful not to reduce the cable insulation diameter. Do not use abrasive on the semi-con insulation shield.
- Create Lug Base Moisture Seal
Wrap a band of grey silicone rubber tape around the base of the terminal lug to create a track-resistant moisture seal. If the barrel diameter is equal to or greater than the cable primary insulation, the tape band should not exceed 2 layers. If smaller, use the tape strip to form the tape band equal to the insulation diameter.
- Apply Silicone Grease and Prepare Termination Core
Apply a liberal coating of silicone grease to the edge of the semi-con insulation shield to fill the step at the cut-off. For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom.
- Install Termination Body
Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is butted up to the leading edge of the mastic seal. Do not push or pull the termination assembly while removing the core material.
- Lubricate and Fold Down Skirt
Apply a thin film of silicone lubricant to the skirt and mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal.
- Complete Lug Area Moisture Seal
Using the remaining grey silicone rubber tape, complete the lug area moisture seal. Overlap the termination insulator by approximately 1” and extend the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration.
- Ground Neutral Wires and Confirm High-K Step
Twist the concentric neutral wires together and connect them to the system ground. Confirm that the High-K step does not exceed 1.5”.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.