ABB Installation Products R2IT15M1-N0300 Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Tape Shield/Wire Shield/…
UPC: 075114308304
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV indoor termination
- Insulation range: 0.64" - 1.12"
- Aluminum 2-hole spade connector
- Supports #2 AWG - 1250 kcmil conductors
- Compatible with tape shield, wire shield, and unshielded cables
Specifications
Application | Cable Termination, Indoor Application, 15kV |
Cable Type | Copper Tape Shielded Wire |
Color | Gray |
Conductor Size | 350 to 400 kcmil |
Connection Type | Tape Shield/Wire Shield/Unshield |
Current Rating | 1250 kcmil |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum |
Mounting | Product Need to have Cable Holder (not included) |
Mounting Type | Indoor |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 Termination |
Size | 0.64 inch - 1.12 inch |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Indoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T28M2-N0300
Outdoor Ranger2 Cable Termination. 25/28kV, Cable Type - Tape Shield/Wire Shield/UniShield. Insulation Range - .84 inch - 1.38 inch. Aluminum 2-Hole Spade #2-1250 kcmil, Conductor 350 Stranded/Compressed or 400 Compact/Solid
R2T35M2N2250-B2
Outdoor, Ranger2 Termination, 35kV, Tape Shield/Wire Shield/UniShield Cable Type, Insulation Range - .84-1.38 inch (21-35mm). Connector Type Copper 2-Hole Spade #2-1250 kcmil. Conductor - 2/0 Stranded/Compressed or 3/0 Compact/Solid. Cable Mounting Bracket Material - Stainless Steel, Size 1.10-1.50 inch (28-38mm).
R2T35M2T0240
Outdoor Ranger2 Cable Termination. 35kV, Cable Type - Tape Shield/Wire Shield/UniShield. Insulation Range - .84 inch - 1.38 inch. Universal Aluminum Barrel for AL or CU Conductor with Copper Wire Lead #2-4/0, Conductor 1/0 Stranded/Compressed or 2/0 Compact/Solid
R2T35M4N0300-B3
Ranger2 Termination. Type - Indoor, 35kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400. Cable Mounting Bracket Material Stainless Steel - 1.45 inch to 1.95 inch (37-50mm).
R2T35M2-H0330-B1
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 1-Hole Spade connector for #2-500 kcmil, Stranded or Compressed 500/ Compact or Solid 600 . Stainless Steel Mounting Bracket .80 inch - 1.25 inch (20-35mm)
R2IT15M1-N0210
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. #1 Stranded or 1/0 Solid. #2 Solid.
R2T35J4-T0270-B3
Ranger2 Termination for 35KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 4/0 /Compact or Solid 250, Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch
R2T15J2-T0270-B2
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 4/0/ Compact or Solid 250. Plated Mild Steel Mounting Bracket 1.10 inch - 1.50 inch (28-38mm)Frequently Asked Questions
What is the voltage rating of the R2IT15 termination?
The R2IT15 cable termination has a voltage rating of 15 kV.
What cable sizes are compatible with R2IT15 terminations?
The R2IT15 terminations accommodate cables from #2 AWG through 1250 kcmil, covering insulation diameters from 0.64 in to 2.10 in.
What is the operating temperature range for the R2IT15?
The R2IT15 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the maximum altitude for R2IT15 termination installation?
The R2IT15 termination can be installed at a maximum altitude of 3300 feet (1005 m).
What is the IEEE classification for the R2IT15 indoor termination?
The R2IT15 indoor termination has an IEEE Classification of Indoor = Class 2.
What is the power system frequency range for R2IT15?
The R2IT15 termination is designed for power system frequencies ranging from 48 to 62 Hz.
What is the Lightning Impulse Withstand (BIL Dry) for R2IT15?
The Lightning Impulse Withstand (BIL Dry) for the R2IT15 termination is 110 kV Crest.
What is the maximum design voltage to ground for R2IT15?
The maximum design voltage to ground for the R2IT15 termination is 9.5 kV.
What is the maximum design voltage to ground for R2IT15?
The maximum design voltage to ground for the R2IT15 termination is 9.5 kV.
What cable sizes are compatible with R2IT15 terminations?
The R2IT15 terminations accommodate cables from #2 AWG through 1250 kcmil, covering insulation diameters from 0.64 in to 2.10 in.
How to Install the R2IT15M 15kV Shrink Fit Silicone Rubber Termination
This guide provides step-by-step instructions for the indoor installation of the 15kV Ranger 2 Shrink fit Silicone Rubber Termination on tape shield, wire shield, or UniShield® cables. This indoor kit does not restore a moisture-resistant seal; use indoor/outdoor kits if moisture resistance is required. Installation should only be performed by competent personnel trained in high voltage electrical equipment safety practices.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Solvent saturated pads, Aluminum oxide abrasive (optional)
Supplies needed:
R2IT15M Silicone Rubber Termination kit (includes termination, preformed ground braid, constant force spring, lubricant, copper foil tape, gloves), Terminal lug or connector, High-voltage cable (tape shield, wire shield, or UniShield®), Vinyl tape, Cleaning solvent
- Prepare the Cable
DANGER: All apparatus must be de-energized during installation. Verify the cable size fits within the termination selection chart. Train and cut the cable to the required length. Prepare the cable according to the specified dimensions for jacket removal, semi-con, and insulation. For tape shield cables, secure the tape shield edge with a single wrap of the supplied copper foil tape. Allow for additional exposed conductor distance to account for growth during crimping of aluminum lugs or connectors.
- Install the Ground Braid
Carefully wrap one band of vinyl tape 1/4 inch (6mm) from the cable jacket end; this serves as a marker. Position the preformed ground braid with the short tail over the cable shield and the solder block centered over the vinyl tape marker. Secure the ground braid to the cable jacket using vinyl tape. Apply a second vinyl tape band directly over the original marker and ground braid solder block, maintaining the 1/4 inch (6mm) dimension. Wrap the ground braid around the cable shield for one complete wrap, trim any excess to prevent overlap, and secure it in place with the constant force spring. Wrap the spring in the same direction as the ground braid and cinch it after the final winding. Secure the constant force spring with two wraps of vinyl tape.
- Install the Terminal Lug or Connector
Before crimping, check to ensure the termination assembly will fit over the selected lug. If the lug will not fit through the termination core, clean the insulation and slide the termination body onto the cable before installing the lug (do not remove the core at this time). Position the terminal lug or connector and crimp it according to the manufacturer's directions, ensuring not to crimp the last 3/8 inch to 1/2 inch of the connector. After crimping, remove any excess oxide inhibitor and all sharp crimp flashings or edges.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with solvent-saturated pads. Do not allow the solvent to touch the semi-conductive insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation, avoiding the semi-conductive shield. Be careful not to reduce the cable insulation diameter below that allowed by the kit.
- Install the Termination Body
Cover the edge of the semi-conductive insulation shield with a liberal coating of silicone grease; this fills the step at the semi-con cut-off. Slide the termination body onto the cable, aligning its edge with the forward edge of the vinyl tape marker. Carefully begin to remove the core by pulling counter-clockwise. Recheck the termination's position and continue removing the core. Do not push or pull on the termination assembly while removing the core. Finally, connect the ground braid to the system ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.