ABB Installation Products R2IT15M2-H0250 Ranger2 Termination for 15KV indoor application, cable insulation diameter .84 - 1.38…
UPC: 783786958597
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15KV indoor application rating
- Accommodates cable insulation diameter from 0.84 to 1.38 inches
- Compatible with tape shield, wire shield, and unshielded cables
- Includes Aluminum 1-Hole Spade connector for 500 kcmil conductors
- ABB Ranger2 termination system
Specifications
Application | Cable Termination, Indoor Application, 15kV |
Cable Type | Copper Tape Shielded Wire |
Color | Gray |
Conductor Size | 2/0 STR AWG , 2/0 COMPR AWG , 3/0 SOL AWG , 3/0 COMPT AWG |
Earthing | Products Includes Their Own Grounding System |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Indoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T15J1-T0250-B1
Outdoor, Ranger2 Termination, 15kV, Concentric Neutral/Jacketed Concentric Neutral Cable Type, Insulation Range - .64-1.12 inch (16-28mm). Connector Type Universal Aluminum Barrel for AL or CU Conductor with Copper Wire Lead #2-4/0. Conductor - 2/0 Stranded/Compressed or 3/0 Compact/Solid. Cable Mounting Bracket Material - Stainless Steel, Size .80-1.25 inch (20-32mm).
R2IT15M2N0280
Ranger2 Termination for 15KV indoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Aluminum 2-Hole Spade #2-1250kcmil, Stranded or Compressed 250 / Compact or Solid 300.
R2IT15M2-N0300
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.
R2IT15M2-N0290
Ranger2 Termination for 15KV indoor application, cable insulation diameter .84 - 1.38 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. 300 kcmil stranded or 350 kcmil Solid
R2IT15M2-N0310
Ranger2 Termination for 15KV indoor application, cable insulation diameter .84 - 1.38 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. 400 kcmil Stranded or 500 kcmil Solid
R2IT15M1N2300
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, Copper 2-Hole Spade #2-1250kcmil, Stranded or Compressed 350/ Compact or Solid 400.
R2IT15M1-N0240
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 240 -Stranded or Compressed 1/0 Compact or Solid 2/0.
R2IT15J1-N0270
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 1-Hole Spade #2-1250 kcmil, Conductor Code - 270 -Stranded or Compressed 4/0 Compact or Solid 250.Frequently Asked Questions
What is the voltage rating of the R2IT15 termination?
The R2IT15 indoor cable termination has a voltage rating of 15 kV.
What cable sizes are compatible with R2IT15 terminations?
R2IT15 terminations cover cable insulation diameters from 0.64 in (16 mm) to 2.10 in (53 mm), accommodating #2 AWG through 1250 kcmil cables.
What is the maximum design voltage to ground?
The maximum design voltage to ground for the R2IT15 termination is 9.5 kV.
What is the maximum altitude for R2IT15 installation?
The R2IT15 termination can be installed at a maximum altitude of 3300 feet (1005 m).
What is the operating temperature range for R2IT15?
The R2IT15 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What power system frequencies does R2IT15 support?
The R2IT15 termination supports power system frequencies ranging from 48 to 62 Hz.
What cable sizes are compatible with R2IT15 terminations?
R2IT15 terminations cover cable insulation diameters from 0.64 in (16 mm) to 2.10 in (53 mm), accommodating #2 AWG through 1250 kcmil cables.
What is the voltage rating of the R2IT15 termination?
The R2IT15 indoor cable termination has a voltage rating of 15 kV.
What is the maximum design voltage to ground?
The maximum design voltage to ground for the R2IT15 termination is 9.5 kV.
What is the operating temperature range for R2IT15?
The R2IT15 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
How to Install the 15kV Ranger 2 Shrink-Fit Silicone Rubber Termination (Tape Shielded Cable)
This guide provides step-by-step instructions for the safe and proper installation of the 15kV Ranger 2 Shrink-Fit Silicone Rubber Termination (R2IT15M series) for indoor applications on tape shielded cables. Note: This indoor kit does not restore a moisture-resistant seal to the cable termination; use indoor/outdoor kits if moisture resistance is required. It covers cable preparation, ground braid installation, lug connection, cleaning, and termination placement.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Solvent saturated pads, Abrasive (aluminum oxide, grit 120 or finer, optional), Safety gloves
Supplies needed:
15kV Ranger 2 Shrink-Fit Silicone Rubber Termination kit (R2IT15M series), Preformed Ground Braid, Constant Force Spring, Silicone Lubricant, Copper Foil Tape, Vinyl Tape, Terminal Lug or Connector (appropriate for cable), Cleaning solvent
- Ensure Safety and Prepare Cable
WARNING: All apparatus must be de-energized during installation. This product should only be installed by competent personnel trained in high voltage electrical equipment safety practices. Inspect all parts for damage and compatibility. Check cable size against the Termination Selection Chart. Train the cable into position and cut to the required length. Prepare the cable by removing the jacket 9-1/4" (235mm) and allowing for 1-1/2" (38mm) depth of the terminal lug plus any growth allowance for aluminum lugs (1/4" to 3/4" depending on conductor size). To prevent the tape shield from unrolling, secure its edge with a single wrap of the supplied copper foil tape.
- Install Ground Braid
Wrap one band of vinyl tape around the cable jacket 1/4" (6mm) from the jacket end; this serves as a marker. Position the preformed ground braid with its short tail over the tape shield and the solder block centered over the vinyl tape marker. Secure the ground braid to the cable jacket using vinyl tape. Apply a second vinyl tape band directly over the original marker and ground braid solder block, maintaining the 1/4" (6mm) dimension. Wrap the ground braid around the cable tape shield for one complete wrap, trim any excess to prevent overlap, and secure it in place with the constant force spring, wrapping the spring in the same direction as the ground braid. Cinch the spring after the final winding and secure it with two wraps of vinyl tape. If the cable has a cloth or paper semi-conductive insulation shield, overwrap it with one half-lapped layer of highly stretched semi-conductive rubber tape (e.g., Scotcht No. 13).
- Install Terminal Lug or Connector
Verify that the termination assembly will fit over your selected lug. If it does not, clean the cable insulation and slide the termination body onto the cable before installing the lug (do not remove the core at this time). Position the connector or lug and crimp it according to the manufacturer's directions, ensuring not to crimp the last 3/8" to 1/2" of the connector. After crimping, remove any excess oxide inhibitor and all sharp crimp flashings or edges.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with solvent-saturated pads, taking care not to allow the solvent to touch the semi-conductive insulation shield. If abrasive cleaning is necessary, use it only on the insulation, not on the semi-conductive insulation shield. Use only aluminum oxide abrasive, grit 120 or finer, and be careful not to reduce the cable insulation diameter below the kit's specifications.
- Install and Ground the Termination
Apply a liberal coating of silicone grease to cover the edge of the semi-conductive insulation shield; this silicone fills the step at the semi-con cut-off. Slide the termination body onto the cable, aligning its edge with the forward edge of the vinyl tape marker. Carefully begin to remove the core by pulling counter-clockwise. Recheck the termination's position and continue to remove the core, ensuring not to push or pull on the termination assembly during this process. Finally, connect the ground braid to the system ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.