ABB Installation Products R2IT15M1-N0210 Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12…
UPC: 783786022076
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Terminates 15kV indoor cables with insulation diameters from 0.64 to 1.12 inches
- Supports Tape Shield, Wire Shield, and Unshielded cable configurations
- Includes aluminum 2-hole spade connector for #2 to 1250 kcmil conductors
- Compatible with #1 stranded or 1/0 solid, and #2 solid conductors
- Field-proven solution for indoor medium-voltage applications
Specifications
Application | Cable Termination, Indoor Application, 15kV |
Cable Type | Copper Tape Shielded Wire |
Color | Gray |
Conductor Size | #2 SOL AWG , #2 COMPT AWG |
Earthing | Products Includes Their Own Grounding System |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Indoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

PCT1-0210-4-PB1(1)
15kV, Single Piece Terminator (Class 1), includes Universal Aluminum Rod Contact as standard, Power Cable Termination, Conductor Size - #2 Compact/Solid, Use for Insulation Diameter Range from .640 to 1.070 inches. Positioning Bracket
R2T35J4-T0270-B3
Ranger2 Termination for 35KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 4/0 /Compact or Solid 250, Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch
R2T15J2-T0270-B2
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 4/0/ Compact or Solid 250. Plated Mild Steel Mounting Bracket 1.10 inch - 1.50 inch (28-38mm)
R2IT15M1N0220
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded, Conductor Code - 220 -Stranded or Compressed #2, Compact or Solid #1, includes Aluminum 2-Hole Spade connector for 1250 kcmil
R2T35M4N0410
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1000
R2T35M4N0350
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 650 /Compact or Solid 750
R2T35M4N0330
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500 /Compact or Solid 600
R2T15J2-N0330
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64-1.12 for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole SpadeFrequently Asked Questions
What is the voltage rating of the R2IT15 termination?
The R2IT15 cable termination has a voltage rating of 15 kV.
What is the IEEE classification for the R2IT15 termination?
The R2IT15 termination has an IEEE Classification of Indoor = Class 2.
What power system frequency does the R2IT15 support?
The R2IT15 termination supports a power system frequency range of 48 to 62 Hz.
What is the creepage distance for the R2IT15 termination?
The creepage distance for the R2IT15 termination is 8.4 in (213 mm).
What is the minimum strike distance for the R2IT15?
The minimum strike distance for the R2IT15 termination is 8.4 in (213 mm).
What is the maximum altitude for R2IT15 installation?
The R2IT15 termination can be installed at a maximum altitude of 3300 feet (1005 m).
What is the operating temperature range for R2IT15?
The R2IT15 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What AWG cable sizes are compatible with R2IT15 terminations?
The R2IT15 terminations are compatible with cable sizes from #2 AWG through 1250 kcmil.
What cable insulation diameters does the R2IT15 support?
The R2IT15 termination covers cable insulation diameters from 0.64 in (16 mm) to 2.10 in (53 mm).
What is the Lightning Impulse Withstand Voltage (BIL)?
The Lightning Impulse Withstand Voltage (BIL Dry 110 Withstand) for the R2IT15 is 110 kV Crest.
How to Install the 15kV Ranger 2 Shrink Fit Silicone Rubber Termination for Tape Shielded Cables
This guide provides step-by-step instructions for the safe and proper installation of the 15kV Ranger 2 Shrink Fit Silicone Rubber Termination on tape shielded cables, including cable preparation, ground braid installation, lug connection, and termination placement. Ensure all apparatus are de-energized before starting.
Estimated time: 1h 30m
Tools needed:
Cable preparation tools (e.g., utility knife, wire strippers), Crimping tool, Solvent pads, Aluminum oxide abrasive (grit 120 or finer)
Supplies needed:
R2IT15M Silicone Rubber Termination Kit (includes termination, preformed ground braid, constant force spring, lubricant, copper foil tape, gloves), Terminal lug or connector, Vinyl electrical tape, Cable cleaning solvent, Semi-conductive rubber tape (Scotcht No. 13, if needed)
- Prepare Cable for Termination
DANGER: All apparatus must be de-energized during installation. Verify the cable size fits the termination kit's insulation range. Train the cable into position and cut to the required length. Prepare the cable jacket, semi-con, and insulation to the specified dimensions: 9-1/4” (235mm) jacket removal, 1-1/2” (38mm) depth for terminal lug plus growth allowance, 3/4” (19mm) tape shield, and 3/4” (19mm) insulation. Secure the tape shield edge with a single wrap of the supplied copper foil tape to prevent unrolling.
- Install and Secure Ground Braid
Wrap one band of vinyl tape around the cable jacket 1/4” (6mm) from the jacket end; this serves as a marker. Position the preformed ground braid with its short tail over the tape shield and the solder block centered over the vinyl tape marker. Secure the ground braid to the cable jacket using vinyl tape. Apply a second vinyl tape band directly over the original marker and ground braid solder block, maintaining the 1/4” (6mm) dimension. Wrap the ground braid around the cable tape shield one complete wrap, trim any excess to prevent overlap, and secure it in place with the constant force spring, wrapping in the same direction. Cinch the spring after the final winding and secure it with two wraps of vinyl tape. If the cable has a cloth or paper semi-conductive shield, overwrap it with one half-lapped layer of highly stretched semi-conductive rubber tape.
- Crimp Terminal Lug or Connector
Before crimping, check that the termination assembly fits over the selected lug. If it does not, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core at this time). Position the connector or lug and crimp it according to the manufacturer’s directions, ensuring not to crimp the last 3/8” to 1/2” of the connector. After crimping, remove any excess oxide inhibitor and all sharp crimp flashings or edges.
- Clean Cable Insulation and Lug
Wipe the cable insulation thoroughly with solvent-saturated pads. IMPORTANT: Do not allow the solvent to touch the semi-conductive insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation only, being careful not to reduce the cable insulation diameter below the kit's allowance. Do not use abrasive on the semi-conductive insulation shield.
- Position and Install Termination Body
Liberally coat the edge of the semi-conductive insulation shield with silicone grease; this fills the step at the semi-con cut-off. Slide the termination body onto the cable, aligning its edge with the forward edge of the vinyl tape marker. Carefully begin to remove the core by pulling counter-clockwise. Recheck the termination position and continue to remove the core completely. Do not push or pull on the termination assembly while removing the core.
- Connect Ground Braid
Connect the installed ground braid securely to the system ground. This is a critical step for safety and proper operation of the termination.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.