ABB Installation Products K676CHSL-BUS 25kV, 900 Amp, Deadbreak, Compact 4-Way (H) Insulated BUS Bar with Test Point and…
UPC: 075114379137
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25kV rated voltage for medium-voltage applications
- 900 Amp current capacity for high-power distribution
- Deadbreak design allows safe connection/disconnection under load
- Compact 4-way configuration for space-efficient installations
- Integrated test point for convenient diagnostic testing
- Spiking aid simplifies connection process
- Conductive jacket and insert for enhanced electrical performance
- Painted pin for corrosion resistance
- Includes lubricant, warning tag, and instruction sheet
Specifications
Amperage Rating | 900 A |
Application | 25kV, 900 Amps |
Color | Black |
Insulation | True |
Material | Housing - EPDM-Rubber |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | 4-Way Insulated Bus Bar with Test Point and Spiking Aid |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655L3-LM0360
15/25kV 600 Series Deadbreak 3-Way L-Kit, Cable Insulation Diameter 1.280 inch to 1.430 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.
K656CHSLJK
25kV 600 Amps Jacket for K656CHSL. H-Splice Conductive Jacket. 16.2 kV L-G Deadbreak. Semi-Conductive EPDM Rubber.
K656CY-L0320
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size kcmil, Compressed Stranded 450 or Compacted Solid 500/550.
K676ISL-BUS
25kV, 900 Amp, Deadbreak, Separable Cable Joint, 1-Way Insulated Bus Bar with Test Point, With Spiking Aid.
161LRJS-D5260
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector, .890 inch - 1.220 Inch Cable Insulation Diameter, 3/0 Stranded or 4/0 Solid AWG Wire Size, Bi-Metal Compression Lug
K656I-H0260-S
15-25kV 600 Series Deadbreak Separable Straight Joint Package (2-Way) with Test Point. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 3/0 or Solid 4/0. Cold-Shrinkable Jacket Seal Included.
K151SP-C0260
200 Amp, 15/25kV, Deadbreak Elbow, Straight Plug, Bails are required but not included, order separately. Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 3/0 or Solid 4/0.
K655ETP-F0220-DRGSG3
25kV, 600 Amp Deadbreak, Test and Ground Connector Kit. Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG, Compressed / Stranded 3/0, or Compacted / Solid 4/0. With Insulated Cap and Cold-Shrinkable Seal with Copper Braid and Constant Force Spring.How to Install the K676CHSL-BUS Disconnectable Splice
This guide provides step-by-step instructions for installing the K676CHSL-BUS 28kV disconnectable splice with a sacrificial cap. It covers cable preparation, component assembly, grounding, and final cap installation. DANGER: All apparatus must be de-energized during installation or removal of parts to prevent serious injury or death.
Estimated time: 2h
Tools needed:
Cable stripping tools, Crimp tool, Torque wrench with 15/16 inch socket, Hex wrench, Hotstick, Voltage sensing device for capacitive test points, Assembly tool (e.g., 600YADT-2 or 600RRT-2), Wire brush
Supplies needed:
K676CHSL-BUS Splice Kit (including splice, sacrificial cap, lubricant, receptacle housings, nylon rod, cable adapters, retaining rings, spade contacts, bolts, washers, Belleville washers), Crimp connectors, No. 14 AWG copper wire or equivalent, Approved safety solvent, Electrical tape, Conductive copper strip (if required for cable type)
- De-energize and Prepare Cable Ends
DANGER: Ensure all apparatus is de-energized before beginning any work. Cut the cable end square and wipe the outer jacket clean 38 inches from the cut end. Inspect all parts for damage, rating, and compatibility with mating parts.
- Install Grounding Device and Receptacle Housing
If an ECS grounding device is being used, slide its tube onto the cable a distance of 38 inches from the cut end. Subsequently, slide the receptacle housing onto the cable a distance of 30 inches from the cut end.
- Perform Cable Preparation
Refer to the special cable preparation supplement (Part A for Jacketed Concentric Neutral Cable or Part B for Flat Metallic Tape Shielded Cable with Semi-con Shield) included with these instructions and follow the procedure for your specific cable type. This involves precise jacket removal, insulation shield removal, beveling the insulation, and thoroughly cleaning the insulation to remove all semi-conducting residue.
- Prepare Conductor and Retaining Ring
Remove the protruding cable insulation by cutting it even with the end of the cable adapter, taking care not to cut or nick the cable adapter or conductor. The length of exposed conductor should be 4 3/4 to 5 inches. Assemble aluminum retaining rings over the conductor, snug them firmly against the cable adapter, and hand tighten the socket head screw using the provided hex wrench. Confirm the exposed conductor measures 4 3/8 to 4 3/4 inches.
- Install and Crimp Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately insert it fully into the crimp connector containing inhibitor. As a final check prior to crimping, position all components on all cables as shown in the instructions, ensuring the bolt holes in the crimp connectors align properly with the bolt holes of the mating part. Crimp the connectors following the instructions packaged with them, rotating each crimp 90 or 180 degrees. After crimping, measure the distance from the end of the connector to the holding collar; if it is over 7 inches, recheck all previous work.
- Repeat for Additional Cables
Repeat Steps 4 and 5 for all remaining cables that are to be joined by the splice.
- Assemble and Torque Bolts
Assemble the washers and bolt in the following order: flat washer against the spade contact, Belleville washer (concave side down), and hex-head bolt. Hand tighten all the bolts. Using a torque wrench with a 15/16 inch socket, tighten all bolts to 50 to 60 ft. lbs. The splice and cables are now in their final positions; do not attempt to move or reposition any part of the assembly after the bolts are tightened.
- Lubricate and Position Receptacle Housing
Apply the supplied lubricant or an ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the area of the splice section, and the inside mating surface of the receptacle housing. Slide the receptacle housing over the cable adapter and up to its final position, then insert the supplied nylon venting rod.
- Use Assembly Tool
Utilize the appropriate assembly tool (e.g., 600YADT-2 or 600RRT-2) as per its specific instruction sheet (IS-1307 or IS-1333) to fully seat the components.
- Complete Remaining Cables and Final Checks
Repeat Steps 8 and 9 for any remaining cables. Check all cable adapters to make sure they are located properly and remove all vinyl tape markers.
- Ground the Assembly
Complete the installation of any ECS grounding device following its specific instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings, making a small loop and twisting tightly, taking care not to damage the eye. Attach this wire directly to the system's ground; do not use one of the concentric neutral wires for this connection.
- Install Sacrificial Cap
Remove the protective shipping cap. Clean the male interface and lubricate both the interface and the inside of the new sacrificial cap with the supplied lubricant. Install the new sacrificial cap by rotating it clockwise 9 to 10 turns until it stops turning; additional torque is not required. Ensure the gap between the cap and the shoulder of the splice is 1/8 inch or less. Attach a 14 AWG wire through the grounding eye and tighten by twisting, then attach it directly to system's ground, keeping the wire snug.
- Perform Voltage Test (Optional)
WARNING: The voltage test point is a capacitance device; it is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly in line. Use a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, to determine if the cable is energized. Treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with supplied lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.