ABB Installation Products K656CY-L0320 15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable…
UPC: 075114408356
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15-25kV voltage rating for medium voltage applications.
- 3-way separable wye joint configuration.
- Integrated test point for safe testing.
- Accommodates cable insulation diameters from 1.180" to 1.465".
- Includes aluminum compression lug for 450 kcmil (stranded) or 500/550 kcmil (solid) conductors.
Specifications
Amperage Rating | 600 A |
Application | Compact Design is suitable for small vaults and manholes |
Color | Black |
Conductor Range | 450 kcmil , 500 to 550 kcmil |
Connection | Compression |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 37.27 in |
Length | 946.658 mm |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Poles | 3-Way |
Series | 600 |
Size | Cable Insulation Diameter 1.180 inch to 1.465 inch |
Special Features | Fully Shielded, Fully Submersible, 100 Percent Peroxide Cured EPDM Molded Rubber |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Separable Wye Joint |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15-25 kV |
Width | 8.12 in |
Width | 206.248 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 26.3600 L |
Package Weight (Metric) | 11.9570 kg |

K655LRTP-L0320-DRG
600 Amp Elbow Connector, Stick Op Connector Kit, 25KV, Dead Break, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 450 /Solid 500/550.
K676ISL-BUS
25kV, 900 Amp, Deadbreak, Separable Cable Joint, 1-Way Insulated Bus Bar with Test Point, With Spiking Aid.
161LRJS-D5260
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector, .890 inch - 1.220 Inch Cable Insulation Diameter, 3/0 Stranded or 4/0 Solid AWG Wire Size, Bi-Metal Compression Lug
K656I-H0260-S
15-25kV 600 Series Deadbreak Separable Straight Joint Package (2-Way) with Test Point. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 3/0 or Solid 4/0. Cold-Shrinkable Jacket Seal Included.
K151SP-C0260
200 Amp, 15/25kV, Deadbreak Elbow, Straight Plug, Bails are required but not included, order separately. Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 3/0 or Solid 4/0.
K655ETP-F0220-DRGSG3
25kV, 600 Amp Deadbreak, Test and Ground Connector Kit. Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG, Compressed / Stranded 3/0, or Compacted / Solid 4/0. With Insulated Cap and Cold-Shrinkable Seal with Copper Braid and Constant Force Spring.
K656DLR-LAC04
15/25kV, Direct Test Elbow, DeadBreak, 600 Amp, Cable Insulation Diameter 1.180-1.465 inches, Tin Plated Aluminum Shear Bolt Connector for Aluminum or Copper Conductor Sizes 750 to 1250 kcmil Stranded / Compressed / Compact.Frequently Asked Questions
How do I order the K656CY-HP wye joint housing?
To order the basic wye joint housing only, specify the ordering number K656CY-HP.
What items are included in the K656CY-HP kit?
Each kit contains a 3-Way Bus Bar, two units of Lubricant 82-08, one Installation Instruction, and three Straight receptacles.
Does the K656CY joint include a test point?
Yes, the K656CY separable wye joint includes an integral capacitive test point.
What is the continuous current rating for the 25kV class?
The continuous current rating for the 25kV voltage class is 600 Amps.
What are the operating voltage limits for the 25kV class?
For the 25kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV, and the maximum phase-to-phase is 28kV.
What is the continuous current rating for the 15kV class?
The continuous current rating for the 15kV voltage class is 600 Amps.
What are the operating voltage limits for the 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV, and the maximum phase-to-phase is 14.4kV.
Can the K656CY joint be used for direct burial?
Yes, the K656CY separable wye joint can be used in direct-buried applications.
What is the primary use of the K656CY joint?
The K656CY cable joint is used to join cables in a disconnectable 3-way joint. It is suitable for small vaults and manholes due to its compact size.
How do I order the K656CY-HP wye joint housing?
To order the basic wye joint housing only, specify the ordering number K656CY-HP.
How to Install K656/K676 Series Deadbreak Receptacles
This guide provides detailed instructions for the safe installation and wiring of K656/K676 series deadbreak receptacles for 600 ampere, 15kV and 25kV solid dielectric cables. These instructions cover the installation of one leg of the connector.
Estimated time: 1h 30m
Tools needed:
Cable cutting tool, Wire strippers, Rag, Approved safety solvent, Hex wrench, Wire brush (for aluminum cable), Torque wrench with 15/16” socket, 650ATY assembly tool (or 600RRT assembly tool)
Supplies needed:
Receptacle housings, Cable adapters, I, Wye or H Center sections, Aluminum holding collars, Lubricant (supplied or ELASTIMOLD approved), Hex-head bolts, Crimp connectors, Belleville washers, Flat washers, Nylon venting rod, Tape (for marker), No. 14 AWG copper wire (or equivalent), ECS grounding device (if used), Appropriate HV insulated cap(s) or connector(s)
- Ensure Safety and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Inspect all parts for damage, proper rating, and compatibility with mating parts. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit. Check contents of package to ensure they are complete and undamaged.
- Clean and Cut Cable End
Wipe the outer jacket clean for a distance of 38 inches (96.5 cm) from the end. Cut the cable end squarely to ensure maximum available length for crimp growth, with respect to the interface.
- Install ECS Grounding Device Tube (if applicable)
If an ECS grounding device is being used, slide the tube onto the cable a distance of 38 inches (96.5 cm) from the end.
- Slide Receptacle Housing onto Cable
Slide the receptacle housing onto the cable a distance of 30 inches (76.2 cm) from the end.
- Prepare Jacketed Concentric Neutral Cable
Refer to the special cable preparation supplement for your specific cable type (e.g., Jacketed Concentric Neutral Cable or Flat Metallic Tape Shielded Cable). For Jacketed Concentric Neutral Cable: Measure 13-3/4 inches (34.9 cm) from the cable end and remove the cable jacket with a straight, smooth cut, taking care not to damage neutral wires. Bend neutral wires back and out of the way. Measure 10-1/4 inches (26 cm) from the cable end and remove the semi-con from the insulation with a straight, smooth, 'squared' cut, taking care not to cut or nick the insulation. At 1 inch (2.54 cm) from the end of the semi-con shield, wrap two turns of tape to serve as a marker. Bevel the end of the insulation at a 45-degree angle, approximately 1/4 inch (0.64 cm) back. Thoroughly clean the insulation with an approved safety solvent, wiping from the cable end toward the outer jacket. Apply supplied lubricant sparingly along the cable and inside the cable adapter. Slide the adapter, small end first, over the cable with a twisting motion until the end of the adapter is flush with the tape marker.
- Remove Protruding Insulation and Verify Conductor Length
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor should be 4-3/4 inches to 5 inches (12.07 cm - 12.7 cm). If not, redo the assembly.
- Assemble Aluminum Retaining Ring
Assemble the aluminum retaining ring over the conductor and snug it firmly against the cable adapter. Using the provided hex wrench, tighten the socket head screw hand tight. Confirm the exposed conductor measures 4-3/8 inches to 4-3/4 inches (11.11 cm - 12.07 cm). If not, redo the assembly.
- Prepare and Insert Crimp Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately insert it into the crimp connector, which contains inhibitor. Ensure the conductor is fully inserted into the crimp barrel. Measure the distance from the end of the connector to the holding collar. If the distance is over 7 inches (17.78 cm), do not proceed; recheck all previous work.
- Confirm Component Alignment
Prior to crimping the connector, confirm that all components (receptacle housing, cable adapter, crimp connector) are positioned correctly. Ensure the bolt holes in the crimp connectors are positioned properly to align with the bolt holes of the mating part.
- Crimp Connectors
Crimp the connectors following the instructions packaged with the connectors. Rotate each crimp 90 or 180 degrees. After crimping, measure the distance from the end of the connector to the holding collar. If the distance is over 7 inches (17.78 cm), do not proceed; redo all previous work.
- Assemble Washers and Bolt
Assemble the washers and bolt in the following order: flat washer against the spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten. The splice and cables are now in their final positions; do not attempt to move or reposition any part of the assembly after the bolts are tightened.
- Torque Tighten Bolts
Using a torque wrench with a 15/16 inch socket, tighten all bolts to 50 to 60 ft. lbs. (67.8 - 81.3 Nm).
- Lubricate Cable Adapter and Receptacle Mating Surface
Apply the supplied lubricant or ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the area of the splice section, and the inside mating surface of the receptacle housing.
- Slide Receptacle Housing and Insert Venting Rod
Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the nylon venting rod (supplied).
- Fully Seat Receptacle Housing with Assembly Tool
Attach the 650ATY assembly tool as shown in the product documentation, ensuring the 'U' shaped yoke is over the splice section and the 'C' shaped yoke is over the receptacle housing. With the assembly tool in place, slowly raise the handle to slide the receptacle housing over the splice section. Remove the venting rod. WARNING: DO NOT place hand on threaded rod or guide shaft with the assembly tool in place if using the 600RRT tool.
- Perform Final Checks and Grounding
Check all cable adapters to make sure they are located properly and remove all vinyl tape markers. Complete the installation of any ECS grounding device according to its specific instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings, making a small loop and twisting tightly, taking care not to damage the eye. Connect this wire to ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.