ABB K675RTP is a 15/25kV, 900 Amp deadbreak reducing tap plug designed for safe, live-line tapping of high-voltage circuits. This 200 Amp interface allows connection to Elastimold K150T connectors, K151SR straight receptacles, and 156LR elbows. Rated for 8.3kV phase-to-ground and 14.4kV phase-to-phase at 15kV class, it withstands 95kV BIL impulse and 34kV AC for one minute. The 25kA symmetrical momentary rating ensures fault protection. Includes bail tabs and lubricant tube (82-08) for installation. Requires a 600SW spanner wrench. Meets ANSI/IEEE Standard 386.
  • 900 Amp continuous current rating
  • 200 Amp deadbreak interface for Elastimold K150T connectors, K151SR receptacles, and 156LR elbows
  • Rated for 15/25kV voltage class with 95kV BIL impulse withstand
  • Includes bail tabs and lubricant tube (82-08) for installation
  • Requires 600SW spanner wrench for assembly

Specifications

Application
15/25 kV, 900 Amps
Color
Red
Connection Type
Dead Break
Current Rating
900 A
Material
Copper
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Reducing Tap Plug
Voltage Rating
15/25 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
900 Amp, 25kV, Deadbreak, Reducing Tap Well.

K675RTW

900 Amp, 25kV, Deadbreak, Reducing Tap Well.
900 Amp, 2 point Junction, Copper, with rubber junction, stainless steel U-Straps and back plate

K675-J2-5

900 Amp, 2 point Junction, Copper, with rubber junction, stainless steel U-Straps and back plate
600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.

K655BLR-H0270

600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
15/25kV,900A DB, 2-Point Junction

K675-J2

15/25kV,900A DB, 2-Point Junction
900 Amp, 4 point junction, Copper, with rubber junction, stainless steel mounting plate, back plate and adjustable mounting bracket

K675-J4-U

900 Amp, 4 point junction, Copper, with rubber junction, stainless steel mounting plate, back plate and adjustable mounting bracket
600 Amp, Extended Connector Plug, DeadBreak, 15/25KV. Widest Diameter 3 inches. Center Body Length 5.5 inch.

K650ECP

600 Amp, Extended Connector Plug, DeadBreak, 15/25KV. Widest Diameter 3 inches. Center Body Length 5.5 inch.
600 Amp, 2 Way Vault Stretcher Kit, 15/25KV, G0260 - Cable Insulation Diameter 0.760 inch to 0.950 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 3/0 or Compacted/Solid 4/0. J0270 - Cable Insulation Diameter 0.980 inch to 1.180 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 4/0 or Compacted/Solid 250. SG3 - Cold Shrinkable Seal with Copper Braid and Constant Force Spring. (K655VS-L2-G0260-J0270-SG3).

K655VSL2-DP0592392

600 Amp, 2 Way Vault Stretcher Kit, 15/25KV, G0260 - Cable Insulation Diameter 0.760 inch to 0.950 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 3/0 or Compacted/Solid 4/0. J0270 - Cable Insulation Diameter 0.980 inch to 1.180 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 4/0 or Compacted/Solid 250. SG3 - Cold Shrinkable Seal with Copper Braid and Constant Force Spring. (K655VS-L2-G0260-J0270-SG3).
600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 900 /Solid 1000 /mmSquared 500.

K655BLR-N0400

600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 900 /Solid 1000 /mmSquared 500.

Frequently Asked Questions

What standard does the K675RTP meet?

The K675RTP meets ANSI/IEEE Standard 386, Latest Revision.

What is the K675RTP Reducing Tap Plug used for?

The K675RTP permits a 200A deadbreak tap-off from a 900A connector in 15/25kV applications.

What connectors are compatible with the K675RTP tap?

The K675RTP 200A tap accepts Elastimold K150T connectors, K151SR straight receptacles, and 156LR elbows.

What tool is required for K675RTP assembly?

A 600SW spanner wrench is required for the assembly of the K675RTP Reducing Tap Plug.

What are the operating voltage limits for 15kV class?

For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV, and the maximum phase-to-phase is 14.4kV.

What is the continuous current rating for the K675RTP?

The K675RTP has a continuous current rating of 900 Amps for both 15kV and 28kV voltage classes.

What is the impulse withstand rating for 15kV class?

For the 15kV voltage class, the impulse withstand (BIL) is 95kV (1.2 x 50 microsecond wave).

What are the operating voltage limits for 28kV class?

For the 28kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV, and the maximum phase-to-phase is 28kV.

What is the impulse withstand rating for 28kV class?

For the 28kV voltage class, the impulse withstand (BIL) is 140kV (1.2 x 50 microsecond wave).

What are the key features of the K675RTP?

Key features include a fully rated 15/25kV, 900 Amp Deadbreak Reducing Tap Plug, a 200 Amp Deadbreak Interface, and Bail Tabs.

How to Install 15/25/35kV 600/900 AMP Deadbreak Plug and Well Products

This guide provides step-by-step instructions for the safe installation and initial setup of 15/25/35kV 600/900 AMP Deadbreak Plug and Well products. It covers preparation, connection, torque tightening, and voltage testing procedures for these high-voltage power distribution accessories.

Estimated time: 1h

Tools needed:

Torque wrench, ELASTIMOLD 600SW spanner wrench, Hotstick, Suitable capacitive voltage sensing device

Supplies needed:

Deadbreak Plug or Well product, Lubricant (supplied with product), Elbow or Bushing Extension (mating part), HV insulated cap(s) or connector(s) (if replacing shipping covers), Silicone lubricant (for test point cap)

  1. Prepare for Installation and Inspect Parts

    DANGER: Ensure all apparatus is de-energized before beginning installation. Inspect all parts for damage, verify their rating, and confirm compatibility with mating parts. If the product came with protective shipping covers, remove them and replace with appropriate HV insulated caps or connectors before energizing. Check the package contents for completeness and ensure all components fit properly with the cable and/or mating products. Gather all required tools and maintain cleanliness throughout the procedure.

  2. Prepare Plug/Well and Mating Part

    Remove any protective caps from the plug or well product. If the 600amp mating interface is not equipped with a stud, hand tighten the stud (typically supplied with the elbow or bushing extension) into the 600amp interface on the plug or well. Lubricate both the elbow (or bushing extension) and its mating part thoroughly with the lubricant supplied. DO NOT SUBSTITUTE with other lubricants, as they may be harmful to the products. Ensure all surfaces of the elbow and mating parts remain clean.

  3. Connect Plug/Well to Elbow/Bushing Extension

    Carefully push the plug or well into the elbow or bushing extension. Ensure the components align correctly and engage the threads as you push them together.

  4. Torque Tighten the Connection

    Use a torque wrench to tighten the connection. If installing an Insulating Plug, apply 50 to 60 foot-pounds of torque. If installing a Connector Plug, Tap Plug, or Tap Well, use a torque wrench with an ELASTIMOLD 600SW spanner wrench and tighten to an indicated torque of 40 to 48 foot-pounds. The indicated torque is not the actual torque applied in this specific case.

  5. Install Voltage Detection Cap (if applicable)

    If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap onto the elbow and push down firmly until it snaps securely into place.

  6. Perform Voltage Test

    To test for voltage, first remove the test point cap using a hotstick. PEEL OFF THE CAP AT AN ANGLE rather than pulling directly in line with the test point assembly. WARNING: The voltage test point is a capacitance device and is NOT directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device specifically designed for separable connectors with capacitive test points, following its manufacturer’s directions, to determine if the cable is energized. Contamination, moisture, or incorrect equipment can cause a false 'no voltage' indication. To prevent serious or fatal injury, treat the elbow as energized until the 'no voltage' indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.