
ABB Installation Products K656SR-K5320 600 Amp Straight Receptacle with Cable Adapter, Lug and Retaining Ring, with capacitive…
UPC: 783786439348
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp DeadBreak straight receptacle for 15/25kV systems
- Capacitive testpoint for safe voltage verification without shutdown
- Bi-metal compression lugs compatible with 450 kcmil stranded or 500/550 kcmil solid conductors
- Cable insulation diameter range: 1.090" to 1.310"
- Includes retaining ring for secure cable connection
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amps |
Color | Black |
Conductor Range | 450 kcmil , 500 to 550 kcmil |
Connection | Compression |
Connection Type | Deadbreak |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions, Fully Submersible |
Insulation | True |
Length | 16.98 in |
Length | 431.292 mm |
Material | Bi-Metal Compression Lug |
Material | Housing - EPDM-Rubber |
Series | K656SR |
Size | Cable Insulation Diameter 1.090 inch to 1.310 inch |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Receptacle with Test Point |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656LR-H0320-SG3
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 450 or Compact/Solid 500. Cold Shrinkable Seal with Copper Braid and Constant Force Spring.
162LR-B-2240
200 Amp, 15kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635 inch to 0.905 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
162LR-B-2260
200 Amp, 15kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635 inch to 0.905 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
K655SR-L-0330
600 Amp, Straight Receptacle with Cable Adapter, Lug and Retaining Ring, DeadBreak, 15/25 KV, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 500 or Compacted Solid 600 or mmSquared Compact 250/300.
K656SR-H2270
600 Amp Straight Receptacle with Cable Adapter, Lug and Retaining Ring, with capacitive testpoint, DeadBreak, 15/25KV, Cable Insulation Diameter 0.850 inch to 1.050 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 4/0 or kcmil Solid Compact 250 or mmSquared 126.67.
K656SR-F0220
600 Amp Straight Receptacle with Cable Adapter, Lug and Retaining Ring, with capacitive testpoint, DeadBreak, 15/25KV, Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size AWG Compressed Stranded #2 or Solid Compact #1 or mmSquared 33.62. Aluminum Compression Lug.
K656SR-H5270
600 Amp Straight Receptacle with Cable Adapter, Lug and Retaining Ring, with capacitive testpoint, DeadBreak, 15/25KV, Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 or kcmil Solid Compact 250 or mmSquared 126.67.
K655SR-J0330
600 Amp, Straight Receptacle with Cable Adapter, Lug and Retaining Ring, DeadBreak, 15/25 KV, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 500 or Compacted Solid 600 or mmSquared Compact 250/300.Frequently Asked Questions
Does this receptacle include a retaining ring?
Yes, the K656SR-K5320 includes a retaining ring to secure the cable connection.
What voltage rating does the K656SR-K5320 support?
The device supports medium-voltage systems rated at 15/25kV.
What is the cable insulation diameter range for this receptacle?
The receptacle supports cable insulation diameters between 1.090 inch and 1.310 inch.
What conductor sizes are compatible with this receptacle?
The bi-metal compression lug accommodates compressed stranded conductors up to 450 kcmil or compacted solid conductors from 500 to 550 kcmil.
Is the lug material bi-metal?
Yes, the compression lug is bi-metal, ensuring compatibility with both copper and aluminum conductors.
What is the purpose of the capacitive testpoint?
The capacitive testpoint allows safe voltage verification without requiring system shutdown, enhancing maintenance safety.
How to Install K656SR and M656SR Straight Receptacles
This guide provides step-by-step instructions for the safe and proper installation of K656SR and M656SR straight receptacles, connecting them to standard ANSI-386 600 amp 15kV, 25kV, or 35kV bushings.
Estimated time: 1h 30m
Tools needed:
5/8-11 tap, Hex wrench, Torque wrench with 15/16 socket, Wire strippers
Supplies needed:
Receptacle housing, Bushing adapter, Cable adapter, Aluminum holding collar, Hex head bolt, Hose clamp (35kV only), Crimp connector, Belleville washer, Flat washer, Lubricant (supplied), Brass bolt, Bushing converter contact, Loctite, Tape marker, No. 14 AWG copper wire (or equivalent), Suitable connector (for neutral wires)
- De-energize Apparatus and Review Safety
Ensure all apparatus is de-energized during installation or removal of parts. Do not touch or move energized products in the work area. Failure to follow these instructions will result in damage to the product and serious or fatal injury. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. All apparatus must be installed and operated in accordance with individual user, local and national work rules and electrical standards.
- Prepare Apparatus Bushing
If a stud is present in the apparatus bushing, remove it and re-tap the hole using a 5/8-11 tap. Clean and lubricate the apparatus bushing and bushing converter interface. Assemble the bushing converter onto the apparatus bushing. Apply 3-4 drops of Loctite to the threads of the brass bolt. Assemble the contact adapter to the apparatus bushing, with the bolt hole facing out, using the 5/8” brass bolt. Torque to 60 ft.-lbs.
- Prepare Cable End
Train the cable end and straighten it into its final position. Cut the cable squarely to ensure maximum available length for crimp growth.
- Manage Concentric Neutral Wires (If Applicable)
Unwrap the concentric neutral wires (if applicable) a distance of 30” (76cm). Do not cut them. Bend and fold them back out of the way.
- Clean Outer Jacket
Wipe the outer jacket clean for a distance of 38” (96.5cm) or up to the concentric neutral wires.
- Slide Receptacle Housing
Slide the receptacle housing onto the cable a distance of 30” (76cm).
- Prepare Cable Insulation
Remove the semi-con shield and install a tape marker to the dimensions shown (10-1/4” (26.04cm) from the end of the cable insulation, with the semi-con shield extending 11-1/4” (28.58cm) from the end). Do not cut or nick the cable insulation.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor Length
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor should be 4 3/4” – 5” (12.06cm–12.7cm). If the length is not within this range, redo the assembly.
- Position and Secure Holding Collar
Position the holding collar over the conductor and flush against the cable adapter. Using the supplied hex wrench, tighten the setscrew.
- Prepare and Insert Conductor into Crimp Connector
Remove the protective cap from the crimp connector. If using aluminum cable wire, brush the conductor and immediately insert it into the crimp connector, which contains inhibitor. Ensure the conductor is fully inserted into the crimp barrel. Measure the distance from the end of the connector to the holding collar. If the distance is over 7” (17.8cm), do not proceed and redo all previous work.
- Confirm Component Alignment
Confirm that the components (Receptacle Housing, Cable Adapter, Crimp Connector, Contact Adapter) are oriented in the correct order. Crucially, confirm that the bolt hole in the crimp connector is aligned with the bolt hole in the contact adapter.
- Crimp Connectors
Crimp the connectors following the instructions packaged with the connectors. Rotate each crimp 90 degrees. After crimping, measure the distance from the end of the connector to the holding collar. If the distance is over 7” (17.8cm), do not proceed and redo all previous work.
- Assemble Washers and Bolt
Assemble the washers and bolt in the following order: Flat washer against the spade contact, Belleville washer (concave side down), hex-head bolt. Hand tighten. Using a torque wrench with a 15/16 socket, tighten to 50-60 ft.-lbs. Do not attempt to move or reposition any part of the assembly after the bolts are tightened.
- Lubricate Adapters
Apply the supplied lubricant or ELASTIMOLD approved lubricant generously to the outside of the cable adapter and the area of the bushing adapter as shown in the diagram. Do not substitute lubricants, as other lubricants may be harmful to this product or its mating product.
- Seat Receptacle Housing and Ground
Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the supplied nylon venting rod. Slide the receptacle housing onto the bushing converter until fully seated. Remove the venting rod. Connect a short piece of No. 14 AWG copper wire or equivalent to the grounding eye of the receptacle housing, making a small loop and twisting tightly without damaging the eye. Gather the concentric neutral wires. Using a suitable connector, connect the neutral wires and the grounding wire.
- Secure Hose Clamp (35kV Only)
For 35kV installations only, position the hose clamp between the locator bumps on the receptacle housing. Tighten the clamp until an audible click is heard.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.