ABB Installation Products K656SR-F0220 600 Amp Straight Receptacle with Cable Adapter, Lug and Retaining Ring, with capacitive…
UPC: 783786439935
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating with 25kA momentary withstand
- Fully shielded, submersible molded rubber housing for harsh environments
- Deadbreak design enables safe connection/disconnection in de-energized state
- Capacitive test point for non-corrosive voltage verification
- Supports cable insulation diameters from 0.640" to 0.820" (#2 AWG conductor)
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amps |
Color | Black |
Conductor Range | #2 STR/COMPR AWG , #1 SOL/COMPT AWG |
Connection | Compression |
Environmental Conditions | All Weather Conditions, Fully Submersible |
Insulation | True |
Length | 16.98 in |
Length | 431.292 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Receptacle with Test Point |
Voltage Rating | 15 to 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR1-B5220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Bi-Metal Conductor size 2 AWG Stranded/Compressed, 1 AWG Solid/Compact. no Sealing Kit
K656SR-H5270
600 Amp Straight Receptacle with Cable Adapter, Lug and Retaining Ring, with capacitive testpoint, DeadBreak, 15/25KV, Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 or kcmil Solid Compact 250 or mmSquared 126.67.
K655SR-J0330
600 Amp, Straight Receptacle with Cable Adapter, Lug and Retaining Ring, DeadBreak, 15/25 KV, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 500 or Compacted Solid 600 or mmSquared Compact 250/300.
K656SR-L0330
600 Amp, 15/25kV, 600 Series Straight Receptacle with cable adapter, lug and retaining ring. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 500 or Compacted Solid 600 or mmSquared Compact 250/300.
K656DLR-L0380
15/25kV, Direct Test Elbow, DeadBreak, 600 Amp, Cable Insulation 1.180-1.465 inches, Aluminum Compression Lug, Conductor Size 750 Stranded/Compressed or 900 Solid/Compact.
K656SR-L0330-S
25kv Straight Receptacle 600 Amp With Sealing Kit, Capacitive Test Points. Cable Insulation Diameter 1.180-1.465 Inches, Aluminum Lug, Conductor Size 500 kcmil Stranded/Compressed or 600 kcmil Solid/Compact.
K656SR-L0320-SG3
25kV, 200 Amp, Straight Receptacle, Deadbreak, Elbow with Cable Adapter, Lug and Retaining Ring, With IEEE Std 386 Capacitive Test Point, and Sealing Kit - SG3 - Cold Shrinkable Seal with Copper Braid and Constant Force Spring. Cable Insulation Diameter 1.180-1.465, Aluminum Lug, Conductor Size 450 kcmil Stranded/Compressed or 500/550 kcmil Compact/Solid.
K656DLR-N0400-SG3
600 Amp, 15/25kV, 600 Series Deadbreak Direct Test Elbow with Test Point, (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size kcmil Compressed Stranded 900 or Compacted Solid 1000 or mmSquared Compact 500. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.Frequently Asked Questions
What items are included in each K656SR kit?
Each kit contains a straight receptacle housing, silicon lubricant, straight receptacle adapter, installation instruction, cable adapter, aluminum compression lug, adapter retaining ring, crimp chart, and hardware prepack.
What is recommended for metallic tape shield cables?
When used on metallic tape shield or drain wire cable, an ECS ground kit/cable seal is recommended.
What type of test point does the K656SR have?
The K656SR features a non-corrosive capacitive test point.
What type of housing does the K656SR have?
It features a fully shielded, fully submersible molded rubber housing with 100% peroxide-cured construction.
What standard does the K656SR meet?
The K656SR meets ANSI/IEEE Standard 386, Latest Revision.
What is the momentary current rating?
The momentary current rating for both 15kV and 28kV voltage classes is 25kA Symmetrical for 10 Cycles.
What is the continuous current rating?
The continuous current rating for both 15kV and 28kV voltage classes is 600 Amps.
What are the operating voltage ratings for 28kV class?
For the 28kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV and maximum phase-to-phase is 28kV.
What are the operating voltage ratings for 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV and maximum phase-to-phase is 14.4kV.
What are the insulation diameter requirements?
It is compatible with cable insulation diameters ranging from 0.640 inches to 1.935 inches.
How to Install K656SR and M656SR Straight Receptacles
This guide provides step-by-step instructions for the safe and proper installation of K656SR and M656SR straight receptacles, connecting them to standard ANSI-386 600 amp 15kV, 25kV, or 35kV bushings.
Estimated time: 1h 30m
Tools needed:
5/8-11 tap, Hex wrench, Torque wrench with 15/16 socket, Wire brush (for aluminum cable), Suitable crimping tool, Wire strippers, Measuring tape or ruler
Supplies needed:
Receptacle housing, Bushing adapter, Cable adapter, Aluminum holding collar, Hex head bolt, Hose clamp (35kV only), Crimp connector, Belleville washer, Flat washer, Nylon venting rod, Lubricant (supplied or ELASTIMOLD approved), Brass bolt, Bushing converter contact, Loctite, Tape marker, No. 14 AWG copper wire (or equivalent), Suitable connector for neutral and grounding wires
- Prepare Apparatus Bushing
DANGER: All apparatus must be de-energized during installation or removal of parts. If a stud is present in the apparatus bushing, remove it and re-tap the hole using a 5/8-11 tap. Clean and lubricate the apparatus bushing and bushing converter interface. Assemble the bushing converter onto the apparatus bushing. Apply 3-4 drops of Loctite to the threads of the brass bolt. Assemble the contact adapter to the apparatus bushing, with the bolt hole facing out, using the 5/8” brass bolt. Torque to 60 ft.-lbs.
- Prepare Cable End
Train the cable end and straighten it into its final position. Cut the cable squarely to ensure maximum available length for crimp growth. If applicable, unwrap the concentric neutral wires a distance of 30” (76cm), do not cut them, and bend them back out of the way. Wipe the outer jacket clean a distance of 38” (96.5cm) or up to the concentric neutral wires.
- Install Receptacle Housing and Prepare Cable Insulation
Slide the receptacle housing onto the cable a distance of 30” (76cm). Remove the semi-con shield and install a tape marker to the dimensions shown in the instructions (10-1/4” (26.04cm) from the end of the cable insulation, and 11-1/4” (28.58cm) from the end of the semi-con shield). Do not cut or nick the cable insulation. Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose and Prepare Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor should be 4 3/4” – 5” (12.06cm–12.7cm); otherwise, redo the assembly. Position the holding collar over the conductor and flush against the cable adapter. Using the supplied hex wrench, tighten the setscrew. The bare conductor length from the holding collar should be 4 3/8” – 4 3/4” (11.11cm – 12.06cm).
- Insert and Crimp Conductor
Remove the protective cap from the crimp connector. If using aluminum cable wire, brush the conductor and immediately insert it into the crimp connector, which contains inhibitor. Make sure the conductor is fully inserted into the crimp barrel. Measure the distance from the end of the connector to the holding collar; if it is over 7” (17.8cm), do not proceed and redo all previous work. Confirm that the receptacle housing, cable adapter, crimp connector, and contact adapter are oriented in the correct order, and that the bolt hole in the crimp connector is aligned with the bolt hole in the contact adapter. Crimp the connectors following the instructions packaged with the connectors, rotating each crimp 90 degrees. After crimping, measure the distance from the end of the connector to the holding collar; if it is over 7” (17.8cm), do not proceed and redo all previous work.
- Secure Connection Bolt
Assemble the washers and bolt in the following order: flat washer against the spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten. The splice and cables are now in their final positions. Using a torque wrench with a 15/16 socket, tighten to 50-60 ft.-lbs. Do not attempt to move or reposition any part of the assembly after the bolts are tightened.
- Lubricate and Seat Receptacle Housing
Apply the supplied lubricant or ELASTIMOLD approved lubricant generously to the outside of the cable adapter and the area of the bushing adapter as shown in the documentation. DO NOT SUBSTITUTE other lubricants, as they may be harmful to this product or its mating product. Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the supplied nylon venting rod. Slide the receptacle housing onto the bushing converter until it is fully seated. Remove the venting rod.
- Connect Grounding and Neutral Wires
Connect a short piece of No. 14 AWG copper wire (or equivalent) to the grounding eye of the receptacle housing. Make a small loop and twist tightly, taking care not to damage the eye. Gather together the concentric neutral wires. Using a suitable connector, connect the neutral wires and the grounding wire.
- Position Hose Clamp (35kV Only)
FOR 35kV ONLY: Position the hose clamp between the locator bumps on the receptacle housing. Tighten the clamp until an audible click is heard.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.