ABB Installation Products K656LR-G0220 15/25kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug…
UPC: 783786055227
Contact for Pricing
Call (262) 252-1600 or email [email protected] for pricing and availability.
Overview
- 15/25kV rated deadbreak elbow with test point
- Accommodates cable insulation .760 to .950 inch
- Supports #2 stranded/compressed or #1 compact/solid conductors
- Includes insulated plug, cap, stud, lug, and cable adapter
- Aluminum compression lug for secure mechanical and electrical connections
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amp Deadbreak Elbow Connection |
Color | Black |
Conductor Range | #2 STR/COMPR AWG , #1 SOL/COMPT AWG |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected using Standard Hand Tools and Equipment in a De-Energized State. Non-Corrosive, Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 6.4000 L |
Package Weight (Metric) | 2.9030 kg |

K655LR-F5220
25kV, 600 Amp, Deadbreak Elbow, No Sealing Kit, without Test Point, Cable Insulation .640-.820 inches, Bi-Metal Lug, Conductor Size AWG Compressed/Stranded #2 or Compacted/Solid #1 or mm2 Compact 35.
K656LR-G0230
15/25kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Cable Insulation .760 to .950 inch. Aluminum Lug, Conductor Size #1 Stranded/Compressed or 1/0 Compact/Solid
K656LR-H0270-SG3
600 Amp, 15/25kv, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation .850 to 1.050 inch. Aluminum Lug, Conductor Size 4/0 stranded/compressed or 250 Compact/solid. With Cold Shrinkable Seal with Copper Braid and Constant Force Spring.
K656LR-G0250-SG3
600 Amp, 15/25kv, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation .760 to .950 inch. Aluminum Lug, Conductor Size 2/0 stranded/compressed or 3/0 Compact/solid. With Cold Shrinkable Seal with Copper Braid and Constant Force Spring.
K656LR-F0240-SG3
600 Amp, 15/25kv, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation .640 to .820 inch. Aluminum Lug, Conductor Size 1/0 stranded/compressed or 2/0 Compact/solid. With Cold Shrinkable Seal with Copper Braid and Constant Force Spring.
252LR-A5220
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.575-0.740 inches (14.61-18.80mm), Bi-Metal Lug, Conductor Size 220 - #2 Stranded/Compressed, #1 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
252LR-A5210
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.575-0.740 inches (14.61-18.80 mm), Bi-Metal Lug, Conductor Size 210 - #3 Stranded/Compressed, #2 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.Frequently Asked Questions
What voltage rating does this deadbreak elbow support?
The K656LR-G0220 is rated for 15/25kV applications.
What cable insulation sizes are compatible?
The elbow accommodates cable insulation diameters from 0.760 to 0.950 inches.
What conductor sizes does this elbow support?
It supports #2 stranded/compressed or #1 compact/solid conductors.
Is a test point included with this elbow?
Yes, the K656LR-G0220 includes a test point for voltage verification.
What material is the compression lug made of?
The compression lug is made of aluminum.
Can this elbow be used with hot-stick tools?
Yes, the deadbreak design allows for hot-stick operation for safe installation.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides detailed instructions for the installation and setup of 600-ampere or 900-ampere K655/K675LR deadbreak elbow connectors. These connectors provide fully shielded, fully submersible deadfront cable connections to high voltage apparatus.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Wire brush, Hotstick, Suitable voltage sensing device, Torque wrench
Supplies needed:
K655/K675LR Deadbreak Elbow Connector Kit, Insulating Plug (if applicable), Lubricant, Silicone lubricant, Grounding wire (minimum No. 14 AWG Copper), Suitable grounding connector, Waterproofing material, Tape marker
- De-energize and Inspect Apparatus
Ensure all apparatus is de-energized before beginning installation or removal of parts. Do not touch or move energized products. Inspect all parts for damage, proper rating, and compatibility with mating parts.
- Verify Package Contents and Compatibility
Check the contents of the package to ensure all components are complete and undamaged. Verify that all components fit properly with the cable and/or mating products.
- Gather Tools and Maintain Cleanliness
Have all required tools at hand before starting the procedure. Maintain cleanliness throughout the entire installation process to prevent contamination.
- Position and Cut Cable
Assemble the cable in its final position with enough slack for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Surface
Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires.
- Prepare Cable Jacket and Shield
Follow the specific cable preparation steps (A, B, or C) that apply to your cable type (e.g., non-jacketed, jacketed, Unishield, lead sheath). Remove the outer jacket (if applicable) and prepare the cable to the specified dimensions for insulation, semi-con shield, and tape marker locations.
- Bevel Insulation and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Verify Conductor Length
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The exposed conductor length must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If not, redo the assembly.
- Insert Conductor into Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug.
- Crimp Compression Lug
Measure the 'Check Dimension' before crimping; it should be less than 6-3/8 inches. Crimp the compression lug following the crimping instructions supplied with the lug. Locate the first crimp on the end closest to the cable adapter.
- Clean Lug and Verify Dimensions
Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping must be between 6-3/8 inches to 7-1/8 inches (162mm-181mm). If not, redo the assembly.
- Lubricate and Install Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further.
- Verify Adapter Flushness and Remove Tape
Ensure the cable adapter is still flush with the tape marker. If not, reposition the cable adapter. Once confirmed, remove the tape marker.
- Prepare Mating Parts
Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud supplied with the elbow into the mating part, if the mating part is not already equipped with a stud.
- Clean and Lubricate Mating Surfaces
Clean and lubricate both the elbow and the mating part with the supplied lubricant. Keep all surfaces clean during this process.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part. Do not connect or disconnect mating products while energized.
- Connect Opposite Mating Part
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to the instructions supplied with it.
- Install Insulating Plug Cap (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place it on the elbow and push down hard until the cap snaps into place.
- Connect Grounding Wire
Insert one end of a wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop, ensuring not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded according to instructions or an alternate method.
- Waterproof Cable Jacket
Waterproof the jacket of the cable at this point to prevent moisture from entering the cable, using appropriate waterproofing material.
- Remove Test Point Cap
Remove the test point cap with a hotstick. When removing, peel off at an angle rather than pulling directly in line with the test point assembly.
- Perform Voltage Test
WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Test with a suitable sensing device, made for use with separable connectors with capacitive test points, to determine if the cable is energized. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means.
- Replace Test Point Cap
After voltage detection has been made, clean and lubricate the inside surface of the cap with silicone lubricant and replace it securely on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.