ABB Installation Products K656CY-H0260 15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable…
UPC: 783786013173
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15-25kV rated deadbreak separable connector for medium-voltage systems
- Accommodates cable insulation diameters from 0.850" to 1.050"
- 3-way wye configuration for branching applications
- Integrated test point for safe voltage verification without disconnection
Specifications
Amperage Rating | 600 A |
Application | Compact Design is suitable for small vaults and manholes |
Color | Black |
Conductor Range | 3/0 STR/COMPR AWG , 4/0 SOL/COMPT AWG |
Connection | Compression |
Connection Type | Deadbreak Separable Wye Joint |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 37.27 in |
Length | 946.658 mm |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Poles | 3-Way |
Series | 600 Series |
Size | 0.850 to 1.050 inch |
Special Features | Fully Shielded, Fully Submersible, 100 Percent Peroxide Cured EPDM Molded Rubber |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Separable Wye Joint |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15-25 kV |
Width | 8.12 in |
Width | 206.248 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

656ETP-H0260-DRG-S
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. 200ECS Cold-Shrinkable Jacket Seal Included. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.
K655YSR-H0260
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.
K151SR-C2270
15/25kV 200 Amp, Deadbreak Straight Receptacle, Bails are required, but not included, order separately. Cable Insulation Diameter 0.805 inch to 1.060 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
K656LR-K-AC03
15/25kV, 600 Amp, Deadbreak Elbow Connector with Test Point - with Shear Bolt Connector. Includes Elbow Housing, Insulated Plug with Cap, Stud, Shearbolt Lug, Cable Adapter and Lubricant. Cable Insulation Diameter K - 1.090 to 1.310 inch. Tin-Plated Aluminum ShearBolt Lug, Conductor Size AC03 - 500 to 750 kcmil Stranded/Compressed/Solid/Compact.
K152SR-B0220
200 Amp, 15/25kV, Deadbreak Elbow, Straight Receptacle with Test Point, Bails are required but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
K655LR-M-AC03
15/25kV, 600 Amp, Deadbreak Elbow Connector without Test Point - with Shear Bolt Connector. Includes Elbow Housing, Insulated Plug with Cap, Stud, Shearbolt Lug, Cable Adapter and Lubricant. Cable Insulation Diameter M - 1.370 to 1.630 inch. Tin-Plated Aluminum ShearBolt Lug, Conductor Size AC03 - 500 to 750 kcmil Stranded/Compressed/Solid/Compact.
K656LR-N-AC04
15/25kV, 600 Amp, Elbow Connector with Test Point - with Shear Bolt Connector. Includes Elbow Housing, Insulated Plug with Cap, Stud, Shearbolt Lug, Cable Adapter and Lubricant. Cable Insulation Diameter N - 1.550 to 1.780 inch. Tin-Plated Aluminum ShearBolt Lug, Conductor Size AC04 - 750 to 1250 kcmil Stranded/Compressed/Solid/Compact.Frequently Asked Questions
What is the 25kV class impulse withstand rating?
For the 25kV class, the impulse withstand (BIL) is 140kV (1.2 x 50 microsecond wave).
What is the K656CY-HP separable wye joint?
The K656CY-HP is a Deadbreak Separable Wye Joint used to connect cables in a disconnectable 3-way configuration, based on a 3-way bus bar.
What voltage classes does the K656CY-HP support?
The K656CY-HP is rated for both 15kV and 25kV voltage classes.
What is the continuous current rating of the K656CY-HP?
The continuous current rating for the K656CY-HP is 600 Amp for both 15kV and 25kV voltage classes.
What are the 15kV class operating voltage limits?
For the 15kV class, the maximum phase-to-ground operating voltage is 8.3kV and maximum phase-to-phase is 14.4kV.
What are the 25kV class operating voltage limits?
For the 25kV class, the maximum phase-to-ground operating voltage is 16.2kV and maximum phase-to-phase is 28kV.
Which industry standard does the K656CY-HP meet?
The K656CY-HP meets ANSI/IEEE Standard 386, Latest Revision.
What are the key construction features of the K656CY-HP?
It is fully shielded, fully submersible, and made of 100% peroxide cured EPDM molded rubber.
Does the K656CY-HP include an integral test point?
Yes, the K656CY-HP includes an integral capacitive test point.
What components are included in the K656CY-HP kit?
Each kit contains a 3-Way Bus Bar, lubricant, installation instructions, and three straight receptacles.
How to Install K656/K676 Series Deadbreak Receptacles
This guide provides step-by-step instructions for the safe and proper installation of K656/K676 series deadbreak receptacles, including cable preparation, crimping, and final assembly for high voltage electrical systems.
Estimated time: 2h
Tools needed:
Hex wrench, Crimping tool, Wire brush (for aluminum cable), Torque wrench with 15/16 inch socket, 650ATY assembly tool OR 600RRT assembly tool, Wire strippers, Safety solvent, Clean rags
Supplies needed:
Receptacle housings, Cable adapters, I, Wye, or H Center sections (as required), Aluminum holding collars, Lubricant (supplied or ELASTIMOLD approved), Hex-head bolts, Crimp connectors, Belleville washers, Flat washers, Nylon venting rod, No. 14 AWG copper wire (or equivalent), Electrical tape (for markers), Conductive copper strip (for flat metallic tape shielded cable), ECS grounding device (if used), HV insulated cap(s) or connector(s)
- Ensure Safety and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal of parts. This product should only be installed by competent personnel trained in high voltage electrical equipment safety practices. Inspect all package contents and components for completeness, damage, proper rating, and compatibility with mating parts. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors before energizing the circuit.
- Prepare the Cable End
Wipe the outer jacket of the cable clean for a distance of 38 inches (96.5 cm) from the end. Cut the cable end squarely to ensure maximum available length for crimp growth, cutting square with respect to the interface.
- Slide Initial Components onto Cable
If an ECS grounding device is being used, slide its tube onto the cable a distance of 38 inches (96.5 cm). Next, slide the receptacle housing onto the cable a distance of 30 inches (76.2 cm).
- Perform Cable Specific Preparation
Refer to the special cable preparation supplement included with these instructions (Part A for Jacketed Concentric Neutral Cable or Part B for Flat Metallic Tape Shielded Cable with Semi-con Shield). Follow the specific procedure for your cable type, which includes removing the jacket and semi-con shield, beveling the insulation, and thoroughly cleaning the insulation with an approved safety solvent.
- Prepare Conductor and Assemble Retaining Ring
Remove the protruding cable insulation by cutting it even with the end of the cable adapter, ensuring not to cut or nick the cable adapter or conductor. The exposed conductor should measure 4 3/4 to 5 inches (12.06 to 12.7 cm). Assemble the aluminum retaining ring over the conductor and snug it firmly against the cable adapter. Using the provided hex wrench, tighten the socket head screw hand tight. Confirm the exposed conductor now measures 4 3/8 to 4 3/4 inches (11.11 to 12.06 cm); otherwise, redo the assembly.
- Insert Conductor into Crimp Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor immediately before insertion. Fully insert the conductor into the crimp connector barrel, which contains an inhibitor. Measure the distance from the end of the connector to the holding collar; if it exceeds 7 inches (17.78 cm), do not proceed and recheck all previous work.
- Position and Crimp Connectors
Prior to crimping, confirm that all components are positioned correctly and that the bolt holes in the crimp connectors are properly aligned with the bolt holes of the mating part. Crimp the connectors following the instructions packaged with the connectors, rotating each crimp 90 or 180 degrees. After crimping, measure the distance from the end of the connector to the holding collar; if it exceeds 7 inches (17.78 cm), do not proceed and redo all previous work.
- Assemble Washers and Bolt
Assemble the washers and bolt in the following order: place a flat washer against the spade contact, then a Belleville washer (concave side down), followed by the hex-head bolt. Hand tighten the bolt. Do not attempt to move or reposition any part of the assembly after the bolts are tightened, as the splice and cables are now in their final positions.
- Torque Tighten Bolts
Using a torque wrench with a 15/16 inch socket, tighten all bolts to a torque of 50 to 60 ft. lbs. (67.8 to 81.3 Nm).
- Lubricate and Position Receptacle Housing
Apply the supplied or ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the splice section, and the inside mating surface of the receptacle housing. Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the supplied nylon venting rod.
- Complete Housing Assembly with Tool
Attach either the 650ATY assembly tool or the 600RRT assembly tool as shown in its respective instructions. Use the tool to slowly slide the receptacle housing over the splice section until fully seated. WARNING: If using the 600RRT tool, do not place hands on the threaded rod or guide shaft while the tool is in place. Once the housing is fully seated, remove the venting rod.
- Perform Final Checks and Grounding
Check all cable adapters to ensure they are located properly and remove any vinyl tape markers. Complete the installation of the ECS grounding device according to its specific instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings, forming a small loop and twisting tightly, taking care not to damage the eye. Connect this wire to the main ground.
- Repeat for Additional Cables (if applicable)
If installing an 'I', 'Y', or 'H' connector with multiple cables, repeat steps 5 through 12 for each remaining cable to be joined to the receptacle.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.