ABB Installation Products K655YSR-H0260 600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter…
UPC: 783786022021
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp current rating for high-power applications.
- 15-25 kV voltage rating for medium-voltage systems.
- Accommodates cable insulation diameters from 0.850 to 1.050 inches.
- Integrated aluminum compression lug for secure connections.
Specifications
Amperage Rating | 600 A |
Application | These Connectors allow a straight cable connection on Switchgear or Electrical Apparatus equipped with 600 Amp Bushings |
Color | Black |
Conductor Range | 3/0 STR/COMPR AWG , 4/0 SOL/COMPT AWG |
Connection | Compression |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 16.98 in |
Length | 431.292 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, Fully Submersible, Can be easily Connected or Disconnected in a De-Energized State |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Receptacle |
Voltage Rating | 15 to 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656LR-H0260-SG3
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 3/0 or Compact/Solid 4/0 or mm2 Compact 95. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K151SR-C2270
15/25kV 200 Amp, Deadbreak Straight Receptacle, Bails are required, but not included, order separately. Cable Insulation Diameter 0.805 inch to 1.060 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
K656LR-K-AC03
15/25kV, 600 Amp, Deadbreak Elbow Connector with Test Point - with Shear Bolt Connector. Includes Elbow Housing, Insulated Plug with Cap, Stud, Shearbolt Lug, Cable Adapter and Lubricant. Cable Insulation Diameter K - 1.090 to 1.310 inch. Tin-Plated Aluminum ShearBolt Lug, Conductor Size AC03 - 500 to 750 kcmil Stranded/Compressed/Solid/Compact.
K152SR-B0220
200 Amp, 15/25kV, Deadbreak Elbow, Straight Receptacle with Test Point, Bails are required but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
K655LR-M-AC03
15/25kV, 600 Amp, Deadbreak Elbow Connector without Test Point - with Shear Bolt Connector. Includes Elbow Housing, Insulated Plug with Cap, Stud, Shearbolt Lug, Cable Adapter and Lubricant. Cable Insulation Diameter M - 1.370 to 1.630 inch. Tin-Plated Aluminum ShearBolt Lug, Conductor Size AC03 - 500 to 750 kcmil Stranded/Compressed/Solid/Compact.
K656LR-N-AC04
15/25kV, 600 Amp, Elbow Connector with Test Point - with Shear Bolt Connector. Includes Elbow Housing, Insulated Plug with Cap, Stud, Shearbolt Lug, Cable Adapter and Lubricant. Cable Insulation Diameter N - 1.550 to 1.780 inch. Tin-Plated Aluminum ShearBolt Lug, Conductor Size AC04 - 750 to 1250 kcmil Stranded/Compressed/Solid/Compact.
K655YSR-F0210
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compacted Solid #2.
K656CY-J0270
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.Frequently Asked Questions
What is the voltage rating of this ABB receptacle?
The ABB K655YSR-H0260 deadbreak straight receptacle has a voltage rating of 15-25 kV.
What is the maximum current this receptacle can handle?
This ABB receptacle is rated for a maximum current of 600 Amps.
What cable insulation diameters does this receptacle support?
The receptacle supports cable insulation diameters ranging from 0.850 inches to 1.050 inches.
What type of lug is used for connection?
This receptacle features an aluminum compression lug for electrical connections.
How to Install K656/676 Deadbreak Receptacles
This guide provides step-by-step instructions for installing K656/K676 series deadbreak receptacles, designed for splicing and tapping solid dielectric type cables rated for 600 ampere at 15kV and 25kV.
Estimated time: 2h
Tools needed:
Hex wrench, Torque wrench with 15/16” socket, Wire brush (for aluminum cable), 650ATY assembly tool OR 600RRT assembly tool, Approved safety solvent, Rag
Supplies needed:
Receptacle housings, Cable adapters, I, Wye or H Center sections, Aluminum holding collars, Lubricant (supplied or ELASTIMOLD approved), Hex-head bolts, Crimp connectors, Belleville washers, Flat washers, Nylon venting rod, No. 14 AWG copper wire (or equivalent), Tape (for markers, if needed), Conductive copper strip (for flat metallic tape shielded cable)
- Ensure Safety and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal. Do not touch or move energized products. This product should be installed only by competent personnel trained in high voltage electrical equipment. Inspect all parts for damage, rating, and compatibility with mating parts. Check package contents to ensure they are complete and undamaged. Confirm all components fit properly with the cable and/or mating products.
- Perform Initial Cable Preparation
Wipe the outer jacket clean for 38 inches and cut the cable end squarely. If using an ECS grounding device, slide the tube onto the cable 38 inches. Slide the receptacle housing onto the cable 30 inches. IMPORTANT: Refer to the special cable preparation supplement (Part A for Jacketed Concentric Neutral or Part B for Flat Metallic Tape Shielded Cable) included with these instructions and follow the detailed procedure for your specific cable type, which includes jacket removal, semi-con removal, insulation beveling, and thorough cleaning.
- Prepare the Conductor
Remove the protruding cable insulation, cutting it even with the end of the cable adapter. Ensure the exposed conductor measures 4 3/4” – 5”. Assemble the aluminum retaining ring over the conductor, snugging it firmly against the cable adapter. Using the provided hex wrench, tighten the socket head screw hand tight. Confirm the exposed conductor now measures 4 3/8” to 4 3/4”. If measurements are incorrect, redo the assembly.
- Connect and Crimp the Conductor
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately insert it fully into the crimp connector (which contains inhibitor). Measure the distance from the end of the connector to the holding collar; it must be 6 3/4” – 7” maximum. Repeat steps for any remaining cables. Prior to crimping, confirm components are positioned correctly and bolt holes in the crimp connectors align with mating part bolt holes. Crimp the connectors following their instructions, rotating each crimp 90 or 180 degrees. Re-measure the distance from the end of the connector to the holding collar; it must still be 6 3/4” – 7” maximum.
- Assemble and Torque Bolts
Assemble the washers and bolt in the following order: flat washer against spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten the assembly. The splice and cables are now in their final positions; do not attempt to move or reposition any part after bolts are tightened. Using a torque wrench with a 15/16” socket, tighten all bolts to 50 to 60 ft. lbs.
- Lubricate and Position Receptacle Housing
Apply the supplied lubricant or an ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the area of the splice section, and the inside mating surface of the receptacle housing. Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the nylon venting rod (supplied).
- Complete Receptacle Housing Assembly
Attach the appropriate assembly tool (650ATY or 600RRT) as shown in the instructions. For 650ATY, ensure the 'U' shaped yoke is over the splice section and the 'C' shaped yoke is over the receptacle housing, then slowly raise the handle. For 600RRT, slide the housing by turning the hex nut. WARNING: Do not place hand on threaded rod or guide shaft with the assembly tool in place. Once the housing is fully over the splice section, remove the venting rod. Repeat steps for any remaining cables.
- Perform Final Checks and Grounding
Check all cable adapters to ensure they are located properly and remove all vinyl tape markers. Complete the installation of any ECS grounding device according to its specific instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings. Make a small loop and twist tightly, taking care not to damage the eye, then connect to ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.