ABB Installation Products K656CETP-K0330 25kV, 600 Amps, Deadbreak Combo Elbow Tap Plug with Test Point. Cable Insulation…
UPC: 075114338585
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25kV phase-to-phase maximum voltage rating with 125kV BIL impulse withstand
- 600 Amp continuous current rating with 25kA symmetrical momentary current capability
- Integrated 200 Amp loadbreak tap for safe energized operations
- Accommodates cable insulation diameters from 1.090 to 1.310 inches
- Includes test point for voltage verification without de-energizing circuits
Specifications
Amperage Rating | 600 A |
Application | 600 Amps, 25kV Connector |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | Reducing Tap Plug with Stud, Cable Adapter, and Lug. Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | ComboT Elbow with Test Point |
Voltage Rating | 25 kV |
Width | 13.31 in |
Width | 338.074 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K675LR-M2330
900 Amp, 15/25kV, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
K656CETP-J0270
25kv, 600 Amp Series, Deadbreak Combo-T. Connector Elbow with Intergral 200 Amp Loadbreak Tap Plug with Test Point. Cable Insulation Diameter 0.980 to 1.180 inches (24.9-30.0mm). Aluminum Conductor Material, Conductor Code 270 - 4/0 Stranded/Compressed or 250 Solid/Compact. No Sealing Kit.
K675LR-K5330
15/25kV, 600 Amp, Deadbreak Elbow with Test Point. Cable Insulation Diameter 1.090-1.310 inches (27.686-33.274mm). Bi-Metal Lug, 500 kcmil Stranded/Compressed or 600 kcmil Solid/Compact.
K656LR-K2260
1525kV, 600 Amp, Deadbreak Elbow with Test Point. Cable Insulation Diameter 1.090-1.310 inches (27.686-33.274mm). Copper Lug, 3/0 Stranded/Compressed or 4/0 Solid/Compact or 95 mmsq.
K656LR-M0410-SG2
15/25kv, 600 Amp, Deadbreak Elbow with Test Point and Sealing Kit. Cable Insulation Diameter 1.370-1.630 inch (34.798-41.402mm). Universal Aluminum Compression Lug. 410 Wire Size - 1000 kcmil Stranded/Compressed. Sealing Kit SG2 - Cold-Shrinkable Seal with Copper Rod and Constant Force Spring.
K655LR-LM0380-S
15/25kV, 600 Amp, Deadbreak Elbow Connector without Test Point, with Seal kit. Cable Insulation Diameter 1.280 - 1.430 inches (32.512-32.322mm). Aluminum Compression Lug. Conductor Size 380 - 700/750 kcmil Stranded/Compressed or 900 kcmil Solid/Compact.
K656LR-K2260-SG3
1525kV, 600 Amp, Deadbreak Elbow with Test Point. Cable Insulation Diameter 1.090-1.310 inches (27.686-33.274mm). Copper Lug, 3/0 Stranded/Compressed or 4/0 Solid/Compact or 95 mmsq. SG3 - Cold-Shrinkable Seal with Copper Braid and Constant Force Spring.
K655LR-K0270-S
15/25kV, 600 Amp, Deadbreak Elbow Connector without Test Point, with Seal kit. Cable Insulation Diameter 1.090 - 1.310 inches (27.686-33.274mm). Aluminum Compression Lug. Conductor Size 270 - 4/0 Stranded/Compressed or 250 kcmil Solid/Compact.Frequently Asked Questions
What is the continuous current rating of this ABB tap plug?
This ABB tap plug has a continuous current rating of 600 Amps.
What cable insulation diameter range does this elbow tap plug support?
The K656CETP-K0330 supports cable insulation diameters from 1.090 to 1.310 inches.
What conductor size is compatible with the aluminum lug?
The aluminum lug is designed for 500 kcmil stranded or compressed conductors.
What is the maximum operating voltage for this elbow tap plug?
The ABB K656CETP-K0330 Deadbreak Combo Elbow Tap Plug is rated for 25kV operating voltage.
Does this kit include installation hardware?
Yes, the kit includes housing, stud, compression lug, lubricant, cable adapter, and installation instructions.
How to Install 655/656/675/676CETP Deadbreak Elbow Connectors
This guide provides detailed instructions for the safe and proper installation of 655/656/675/676CETP deadbreak elbow connectors, including cable preparation, lug crimping, and final assembly for high voltage apparatus.
Estimated time: 2h
Tools needed:
Crimping tool, Torque wrench, 600AT assembly tool (or 600ATM), Hotstick, Suitable sensing device (for voltage test), Wire brush, Wire strippers, Cable knife
Supplies needed:
Lubricant (supplied), Vinyl plastic tape, Grounding wire (at least No. 14 AWG Copper), Suitable connector (for grounding wire), Silicone grease
- Prepare for Installation
DANGER: All apparatus must be de-energized during installation or removal. Inspect all parts for damage, proper rating, and compatibility. Check package contents for completeness. Have all required tools at hand and maintain cleanliness throughout the procedure.
- Position and Cut Cable
Position the cable in its final assembled position with enough slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product.
- Clean Cable and Prepare Outer Jacket/Shield
Clean the outer surface of the cable for 24” (610mm) or up to the bent back concentric neutral wires. Remove the outer jacket to the specified dimension. Fold back shield wires. Remove flat metallic tape shield and secure with vinyl plastic tape. For other shield types (fabric, corrugated, Unishield, lead sheath), refer to specific instructions. Remove semi-con shield, ensuring not to cut or nick the cable insulation.
- Prepare Cable Insulation and Install Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and lubricate the cable insulation, working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor and Crimp Lug
Remove protruding cable insulation even with the end of the cable adapter, ensuring the exposed conductor length is 4 3/8”–4 11/16” (111mm–119mm). Do not cut or nick the cable adapter or conductor. For copper, fully insert conductor into the lug. For aluminum, wire brush and immediately insert. Measure the 'Check Dimension' (less than 6 1/2” (165mm)). Crimp the lug per its instructions. Wipe excess inhibitor. Verify lug-to-adapter distance is 6 1/2”–7 1/4” (165mm–184mm).
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Connect Elbow to Mating Product
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and mating part. Install the stud into the apparatus by hand until fully seated. Clean and lubricate both the elbow and the mating part. Push the elbow onto the mating part. Use the appropriate 600AT or 600ATM assembly tool to engage and torque the contact assembly (19-25 ft/lbs for older products, 50-60 ft/lbs for newer; do not exceed 60 ft/lbs).
- Ground the Cable Shield
Insert one end of a grounding wire (at least No. 14 AWG Copper) through the grounding eye and twist to form a small loop, avoiding damage to the eye. Connect this wire to ground using a suitable connector. Ensure the cable shield is grounded, either through a grounding device or an alternate method. Waterproof the cable jacket to prevent moisture ingress.
- Install Loadbreak Interface (If Applicable)
Clean and lubricate the entire loadbreak interface and the appropriate DR(G), ESA, GLR, or LR connector. Install the DR(G), ESA, GLR, or LR to the tap plug interface following the instructions supplied with those specific products.
- Verify Seating and Perform Voltage Test
Confirm complete assembly by ensuring no portion of the colored interface sleeve is visible from the side. WARNING: For voltage testing, remove the test point cap with a hotstick, peeling it off at an angle. Use a suitable sensing device designed for capacitive test points; do not use conventional voltage measuring equipment. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone grease and replace it.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.