Overview
- 900 Amp continuous current rating for medium-voltage systems
- Fully shielded, dead-front submersible design for safe operation
- Supports cable insulation diameters from 1.370" to 1.630"
- Compatible with conductor sizes from AWG 500/kcmil to 600/kcmil
- Meets ANSI/IEEE Standard 386 for medium-voltage cable accessories
Specifications
Amperage Rating | 900 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Connection | Compression |
Environmental Conditions | All Weather Conditions, Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 15 to 25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655LR-J0330
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300.
K656ETP-H5260-S-TL
600 Amp, 25kV, Deadbreak Elbow, Window Op Connector Kit with Test Point. Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95. Cold-Shrinkable Jacket Seal Included. With Sheild Adapter.
K656L2-L0330
600 Amp, 15/25kV, 2-Way L-Kit, with Test Point. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
K656L4-H5270-S
600 Amp, 15/25kV, 4-Way L-Kit, with Test Point. Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold-Shrinkable Jacket Seal Included.
K656ETP-M0380
600 Amp, 25kV, Deadbreak Elbow, Window Op Connector Kit with Test Point. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
755L3-K5270-SG3
600 Amp, 35kV, 600 Series Deadbreak 3-Way L-Kit. 200ECS-G3 Jacket Seal and Grounding Kit Included.
K655L2-L0330
15/25kV 600 Series Deadbreak 2-Way L-Kit, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
K655L2-M0330-S
600 Amp, 2 Way L Kit, DeadBreak, 15/25KV, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 500 kcmil or Compacted Solid 600 kcmil. Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
What components are included in a K675LR kit?
Each kit includes an elbow connector housing, a copper compression lug, a copper stud, an insulated plug with cap, lubricant tubes, a cable adapter, and installation instructions.
What is the primary application of the K675LR elbow connector?
The K675LR provides fully shielded, dead-front submersible cable connections to high-voltage apparatus.
What is the maximum voltage rating for the K675LR?
The K675LR elbow connector can be used through 28kV.
What conductor sizes are compatible with the K675LR?
It supports conductor sizes from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What insulation diameters does the K675LR support?
The K675LR supports cable insulation diameters ranging from .640 in to 1.935 in.
What other Elastimold products are compatible with K675LR?
The K675LR can be mated with Elastimold products including K675CP, K675BIP, K675RTP, K675RTW, K675S1, K650J2, K650J3, and K650J4.
What are the 15kV operating voltage ratings?
For 15kV, the maximum phase-to-ground operating voltage is 8.3kV, and the maximum phase-to-phase is 14.4kV.
What is the continuous current rating for the K675LR?
The K675LR has a continuous current rating of 900 Amps for both 15kV and 28kV voltage classes.
What are the 28kV operating voltage ratings?
For 28kV, the maximum phase-to-ground operating voltage is 16.2kV, and the maximum phase-to-phase is 28kV.
Is the K675LR elbow connector submersible?
Yes, the K675LR features a fully shielded, fully submersible molded rubber housing.
How to Install Elastimold 655/675LR and K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of Elastimold 655/675LR and K655/K675LR deadbreak elbow connectors on 15kV and 25kV class systems, including cable preparation, lug crimping, and grounding.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Cable preparation tools, Wire brush (for aluminum conductor), Crimping tool (with crimp chart), Measuring tape or ruler, Hotstick, Suitable voltage sensing device (for capacitive test points), Torque wrench
Supplies needed:
Elbow connector (655/675LR or K655/K675LR), Cable adapter, Compression lug, Insulating plug (if applicable), Lubricant (silicone lubricant), Threaded stud (from stud prepack), Cable (concentric neutral, unishield, lead sheath, jacketed, or non-jacketed), Grounding device (e.g., 20MA, 21MA, 600ECS, or alternate method), Connection wire (minimum No. 14 AWG Copper ampacity), Suitable connector (for grounding wire), Waterproofing material (for cable jacket), HV insulated cap(s) or connector(s) (to replace shipping covers)
- Perform Initial Safety Checks and Inspection
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Ensure installation is performed by competent personnel trained in high voltage electrical equipment safety practices. Inspect all parts for damage, proper rating, and compatibility with mating parts. Check package contents to ensure completeness. Read all instructions before starting and have all required tools at hand, maintaining cleanliness throughout the procedure. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit.
- Assemble and Clean the Cable
Assemble the cable in its final position, ensuring enough slack for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent back concentric neutral wires.
- Prepare the Cable
Follow the specific cable preparation steps based on your cable type. If using a 20MA or 21MA grounding device or 600ECS Jacket Cable Seal, refer to their supplied instructions for outer jacket removal, shield connection, and grounding. For UNISHIELD* or LEAD SHEATH cable, refer to the 10TL cable shield adapter instructions for cable preparation. For jacketed and non-jacketed cables, remove the outer jacket (if applicable) and prepare the cable according to the provided diagrams, ensuring correct dimensions for cable insulation, semi-con shield, and tape marker.
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare the Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Exercise caution not to cut or nick the cable adapter or the conductor. The length of the exposed conductor must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If the length is outside this range, redo the assembly.
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping; this dimension should be less than 6-3/8 inches. If not, redo the assembly. Crimp the compression lug following the crimping instructions supplied with the lug. After crimping, wipe all excess inhibitor from the compression lug and cable adapter surface. The distance from the end of the compression lug to the cable adapter after crimping should be between 6-3/8 inches to 7-1/8 inches (162mm-181mm). If not, redo the assembly.
- Install the Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until the elbow cannot advance further. Verify that the cable adapter is still flush with the tape marker; if not, reposition the cable adapter. Once confirmed, remove the tape marker.
- Prepare Mating Products
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from both the elbow and the mating part. Hand tighten the threaded stud, supplied with the elbow, into the mating part if the mating part is not already equipped with a stud. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring all surfaces remain clean.
- Connect the Elbow to the Mating Part
Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part.
- Connect the Opposite End of the Elbow
Clean and lubricate the mating part intended for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the specific instructions supplied with that mating part.
- Install Insulating Plug (If Applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps securely into place. Proceed to the voltage test directions.
- Ground the Cable Shield
Insert one end of a piece of wire, with ampacity at least equivalent to No. 14 AWG Copper, through the grounding eye and twist it to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded; ground it according to the instructions supplied with your grounding device. If no grounding device is used, ensure the shield is grounded through an alternate approved method. It is also recommended to waterproof the jacket of the cable at this point to prevent moisture from entering the cable.
- Torque Components for 600-amp L-Kits
CAUTION: When constructing 600-amp L-Kits, ensure that each component is tightened to its specified torque according to the instructions provided with the L-Kit.
- Perform Voltage Test
WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the specific meter used. Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly in line with the assembly. Test with a suitable sensing device, designed for separable connectors with capacitive test points, to determine if the cable is energized. Contamination, moisture, dirt, or using the wrong measuring equipment can provide a false 'no voltage' indication. To prevent serious or fatal injury, treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.