ABB Installation Products K656LR-K2260 1525kV, 600 Amp, Deadbreak Elbow with Test Point. Cable Insulation Diameter 1.090-1.310…
UPC: 075114340144
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV voltage rating
- 600 Amp current rating
- Integrated test point for diagnostics
- Accommodates cable insulation diameter: 1.090-1.310 inches (27.686-33.274mm)
- Copper lug for 3/0 Stranded/Compressed, 4/0 Solid/Compact, or 95 mmsq cable
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amp Deadbreak Elbow Connection |
Color | Black |
Conductor Range | 3/0 STR/COMPR AWG , 4/0 SOL/COMPT AWG |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected using Standard Hand Tools and Equipment in a De-Energized State. Non-Corrosive, Capacitive Test Point. Cold-Shrinkable Seal with Copper Braid and Constant Force Spring |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655YSR-H0260
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.
K656LR-M0410-SG2
15/25kv, 600 Amp, Deadbreak Elbow with Test Point and Sealing Kit. Cable Insulation Diameter 1.370-1.630 inch (34.798-41.402mm). Universal Aluminum Compression Lug. 410 Wire Size - 1000 kcmil Stranded/Compressed. Sealing Kit SG2 - Cold-Shrinkable Seal with Copper Rod and Constant Force Spring.
K655LR-LM0380-S
15/25kV, 600 Amp, Deadbreak Elbow Connector without Test Point, with Seal kit. Cable Insulation Diameter 1.280 - 1.430 inches (32.512-32.322mm). Aluminum Compression Lug. Conductor Size 380 - 700/750 kcmil Stranded/Compressed or 900 kcmil Solid/Compact.
K656LR-K2260-SG3
1525kV, 600 Amp, Deadbreak Elbow with Test Point. Cable Insulation Diameter 1.090-1.310 inches (27.686-33.274mm). Copper Lug, 3/0 Stranded/Compressed or 4/0 Solid/Compact or 95 mmsq. SG3 - Cold-Shrinkable Seal with Copper Braid and Constant Force Spring.
K655LR-K0270-S
15/25kV, 600 Amp, Deadbreak Elbow Connector without Test Point, with Seal kit. Cable Insulation Diameter 1.090 - 1.310 inches (27.686-33.274mm). Aluminum Compression Lug. Conductor Size 270 - 4/0 Stranded/Compressed or 250 kcmil Solid/Compact.
756LR-M2330
35kV, 600 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 1.370-1.630 inches (34.798-41.402mm), Copper Lug, Conductor Size 330 - 500kcmil Stranded/Compressed, 600kcmil Solid/Compact. Kit Includes Elbow Connector Housing, Stud, Insulated Plug with Cap, Cable Adapter, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 12.28 x 13.93 inches, 3.37 and 3.83 inch diameters.
K656LR-K0330-SG3
15/25kV, 600 Amp, Deadbreak Elbow Connector without Test Point, with Seal kit. Cable Insulation Diameter 1.090 - 1.310 inches (27.686-33.274mm). Aluminum Compression Lug. Conductor Size 330 - 500 kcmil Stranded/Compressed or 600 kcmil Solid/Compact. SG3 - Cold-Shrinkable Seal with Copper Braid and Constant Force Spring.
K656CETP-H0230
25kv, 600 Amp Series, Deadbreak Combo-T. Connector Elbow with Integral 200 Amp Loadbreak Tap Plug with Test Point. Cable Insulation Diameter 0.850-1.050 inches (21.6-26.7 mm). Aluminum Conductor Material, Conductor Code 230 - #1 Stranded/Compressed or 1/0 Solid/Compact. No Sealing Kit.Frequently Asked Questions
What is the maximum operating voltage for the K656LR elbow connector?
For the 15kV voltage class, the maximum operating voltage is 8.3kV phase-to-ground. For the 28kV voltage class, it is 16.2kV phase-to-ground.
What conductor sizes can the K656LR handle?
The K656LR can be used with conductor sizes ranging from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the continuous current rating for this deadbreak elbow?
The K656LR elbow connector has a continuous current rating of 600 Amps.
Is a grounding device recommended for metallic tape shield or drain wire cable?
Yes, when used on metallic tape shield or drain wire cable, an ECS cable seal grounding device for safety is highly recommended.
What is the impulse withstand rating for the 28kV voltage class?
For the 28kV voltage class, the impulse withstand rating is 140kV BIL (1.2 x 50 microsecond wave).
What is the AC one-minute withstand voltage for the 15kV class?
The AC one-minute withstand voltage for the 15kV voltage class is 34kV.
What is the range of insulation diameters supported by the K656LR?
The K656LR supports insulation diameters ranging from 0.640 inches to 1.935 inches.
What is the corona extinction level for the 15kV voltage class?
The corona extinction level for the 15kV voltage class is 11kV AC at 3pC sensitivity.
What are the momentary current ratings for the K656LR?
The K656LR has a momentary current rating of 25kA Sym for 10 Cycles.
What is the DC 15-minute withstand voltage for the 28kV class?
For the 28kV voltage class, the DC 15-minute withstand voltage is 84kV.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for installing K655/K675LR Deadbreak Elbow Connectors, designed for fully shielded, submersible deadfront cable connections to high voltage apparatus and for splicing 600-ampere or 900-ampere systems.
Estimated time: 1h 30m
Tools needed:
Cable cutter, Wire strippers, Knife, Beveling tool, Crimping tool, Torque wrench, Hotstick, Suitable sensing device (for capacitive test points)
Supplies needed:
K655/K675LR Deadbreak Elbow Connector, Cable adapter, Compression lug, Insulating plug (if applicable), Silicone lubricant, Threaded stud (if needed), Cable (appropriate type for application), Tape marker, No. 14 AWG Copper wire (or equivalent), Grounding connector, HV insulated cap(s) or connector(s)
- Prepare Cable for Assembly
DANGER: All apparatus must be de-energized during installation or removal of parts. Assemble the cable in its final assembled position with enough slack to provide adequate clearance for removing the elbows. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the center line of the mating product.
- Clean Cable Outer Surface
Clean the outer surface of the cable a distance of 24 inches (610mm) or up to the bent back concentric neutral wires.
- Prepare Cable (Jacket Removal and Shield Preparation)
Remove the outer jacket (where applicable) and prepare the cable as shown in the diagrams, ensuring correct dimensions for cable insulation, semi-con shield, and tape marker. If using a 20MA or 21MA grounding device, 600ECS Jacket Cable Seal, or 10TL cable shield adapter for UNISHIELD* or LEAD SHEATH cable, refer to the specific installation instructions supplied with those products.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean, then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. Ensure the length of the exposed conductor is between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If not, redo the assembly.
- Crimp Compression Lug
For copper conductor, fully insert the conductor into the compression lug. For aluminum conductor, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping; it should be less than 6-3/8 inches. If not, redo the assembly. Crimp the compression lug following the crimping instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. Verify the distance from the end of the compression lug to the cable adapter after crimping is between 6-3/8 inches to 7-1/8 inches (162mm-181mm). If not, redo the assembly.
- Install Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter is still flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Products
DANGER: DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZED WHILE DISCONNECTED. Remove protective caps from the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud supplied with the elbow into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert the mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to its supplied instructions.
- Install Insulating Plug (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow. Push down hard until the cap snaps into place. Follow voltage test directions after this step.
- Ground the Cable Shield
Insert one end of a No. 14 AWG Copper wire (or equivalent ampacity) through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect the wire to ground using a suitable connector. The shield of the cable must be grounded. Ground according to the instructions supplied with the grounding device. If no grounding device is used, ground the shield through an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture entry.
- Torque Components (for 600A L-Kits)
CAUTION: When constructing 600amp L-Kits, ensure each component is tightened to the specified torque per its instructions.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the specific meter used. Test with a suitable sensing device, designed for separable connectors with capacitive test points, to determine if the cable is energized. To prevent serious or fatal injury, treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means, as contamination, moisture, or incorrect equipment can provide a false 'no voltage' indication. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.