ABB Installation Products K655YSR-L2360 600 Amp Separable Cable Joints, Straight Receptacle, 15/25KV, Dead Break, Cable…
UPC: 783786392766
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating with 25kA symmetrical momentary rating for 10 cycles
- Accommodates cable insulation diameters from 1.180" to 1.465"
- Supports compressed stranded conductors up to 650 kcmil, solid conductors up to 750 kcmil, or 400 mm²
- Dead break design allows connections under load for enhanced safety
- Fully shielded, submersible, and 100% peroxide-cured rubber housing for durability
Specifications
Amperage Rating | 600 A |
Application | These Connectors allow a straight cable connection on Switchgear or Electrical Apparatus equipped with 600 Amp Bushings |
Color | Black |
Conductor Range | 650 kcmil , 750 to 800 kcmil |
Connection | Compression |
Connection Type | Dead Break Straight Receptacle |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 16.98 in |
Length | 431.292 mm |
Material | Housing - EPDM-Rubber |
Material | Copper, Rubber (Peroxide-Cured) |
Poles | 1 |
Series | K655YSR |
Size | Cable Insulation Diameter 1.180 inch to 1.465 inch |
Special Features | Fully Shielded, Fully Submersible, Can be easily Connected or Disconnected in a De-Energized State |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Receptacle |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655L3-LM0360
15/25kV 600 Series Deadbreak 3-Way L-Kit, Cable Insulation Diameter 1.280 inch to 1.430 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.
K656CH-N0380
600 Amp, 15/25 kV, Separable H Joint package 4-Way with Test Point, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
K656CH-J0320
600 Amp, 15/25 kV, Separable H Joint package 4-Way with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.
K656CH-DP0593508
600 Amp, 15/25KV, Separable H Joint package 4-Way with Test Point, N0360 - Cable Insulation Diameter 1.515 inch to 1.780 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 650 or Compacted/Solid 750. N0360 - Cable Insulation Diameter 1.515 inch to 1.780 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 650 or Compacted/Solid 750. K0360 - Cable Insulation Diameter 1.090 inch to 1.310 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 650 or Compacted/Solid 750. K0260 - Cable Insulation Diameter 1.090 inch to 1.310 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 3/0 or Compacted/Solid 4/0.
K656CH-H0250
600 Amp, 15/25 kV, Separable H Joint package 4-Way with Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
K655YSR-J0320
600 Amp Separable Cable Joints, Straight Receptacle, 15/25KV, Dead Break, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 450 or Solid 500/550.
K655YSR-K0330
600 Amp Separable Cable Joints, Straight Receptacle, 15/25KV, Dead Break, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 500 or Solid 600 or mmSquared 250/300.
K151-SR-C2240
Straight Receptacle, 200 Amp, DeadBreak, 15/25KV, Cable Insulation Diameter 0.805 inch to 1.060 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 1/0 or Solid 2/0 or mmSquared 53.49.Frequently Asked Questions
What is the K655YSR product designed for?
The K655YSR provides a fully shielded, submersible cable connection on 15/25kV high-voltage “I”, “Y”, or “H” Bus. It allows a straight cable connection on switchgear or electrical apparatus with 600 Amp bushings.
What is the maximum operating voltage for 25kV class?
For the 25kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV, and the maximum phase-to-phase is 28kV.
How is the K655YSR connected or disconnected?
The K655YSR can be easily connected or disconnected using standard hand tools and equipment. This must be done in a de-energized state.
What material is the K655YSR constructed from?
The K655YSR features 100% peroxide-cured construction, including insulation and conductive EPDM materials.
Is the K655YSR submersible?
Yes, the K655YSR features a fully shielded and fully submersible molded rubber housing.
What is the impulse withstand (BIL) for 25kV?
For the 25kV voltage class, the Basic Impulse Level (BIL) is 140kV. This is based on a 1.2 x 50 microsecond wave.
What is the impulse withstand (BIL) for 15kV?
For the 15kV voltage class, the Basic Impulse Level (BIL) is 95kV. This is based on a 1.2 x 50 microsecond wave.
What is the maximum operating voltage for 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV, and the maximum phase-to-phase is 14.4kV.
What cable insulation diameters does it accommodate?
The K655YSR accommodates cable insulation diameters from .640 inches to 1.935 inches.
What conductor sizes are compatible with K655YSR?
The K655YSR is compatible with aluminum and copper conductors ranging from #2 AWG to 1250 kcmil.
How to Install K656/676 Series Deadbreak Receptacles
This guide provides step-by-step instructions for the safe and proper installation of K656/676 series deadbreak receptacles, designed for splicing and tapping solid dielectric cables rated for 600A at 15kV and 25kV. Detailed cable preparation for jacketed concentric neutral cables is included.
Estimated time: 1h 30m
Tools needed:
Cable stripping tools, Measuring tape, Wire brush (for aluminum cable), Hex wrench (supplied), Torque wrench (with 15/16 inch socket), Rag, Approved safety solvent, 650ATY or 600RRT assembly tool
Supplies needed:
Receptacle housings, Cable adapters, I, Wye or H Center sections, Aluminum holding collars, Lubricant (supplied or ELASTIMOLD approved), Hex-head bolts, Crimp connectors (with inhibitor for aluminum), Belleville washers, Flat washers, Nylon venting rod, Electrical tape, No. 14 AWG copper wire (for grounding), ECS grounding device (optional)
- Ensure Safety and Inspect Parts
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Inspect all components for damage, proper rating, and compatibility with mating parts before beginning installation. Failure to follow these instructions will result in damage to the product and serious or fatal injury.
- Perform Initial Cable Preparation
Wipe the outer jacket of the cable clean for a distance of 38 inches (96.5 cm) from the end. Cut the cable end squarely to ensure maximum available length for crimp growth. IMPORTANT: Maintain cleanliness throughout the procedure.
- Slide Initial Components onto Cable
If using an ECS grounding device, slide the ECS tube onto the cable a distance of 38 inches (96.5 cm). Next, slide the receptacle housing onto the cable a distance of 30 inches (76.2 cm).
- Prepare Jacketed Concentric Neutral Cable
From the end of the cable, measure 13-3/4 inches (34.9 cm) and remove the cable jacket with a straight, smooth cut, taking care not to damage the neutral wires. Bend the neutral wires back and out of the way. From the end of the cable, measure 10-1/4 inches (26 cm) and remove the semi-con shield from the insulation with a straight, smooth, 'squared' cut, ensuring not to cut or nick the insulation. At a point 1 inch (2.5 cm) from the end of the semi-con shield, wrap two turns of tape to serve as a marker. Bevel the end of the insulation at a 45-degree angle, approximately 1/4 inch (0.6 cm) back. Thoroughly clean the insulation with an approved safety solvent, wiping from the end of the cable toward the outer jacket to remove all traces of semi-conducting residue. Apply supplied lubricant sparingly along the cable as shown in the original documentation and lubricate the inside of the cable adapter. Slide the adapter, small end first, over the cable with a twisting motion until the end of the adapter is flush with the tape marker.
- Remove Protruding Cable Insulation
Remove any protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor should measure 4-3/4 inches to 5 inches (12.1 cm - 12.7 cm). If not, redo the assembly.
- Assemble Aluminum Retaining Ring
Assemble the aluminum retaining ring over the conductor and snug it firmly against the cable adapter. Using the hex wrench provided, tighten the socket head screw hand tight. Confirm the exposed conductor now measures 4-3/8 inches to 4-3/4 inches (11.1 cm - 12.1 cm). If not, redo the assembly.
- Prepare and Insert Conductor into Crimp Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor immediately before inserting it into the crimp connector, which contains inhibitor. Ensure the conductor is fully inserted into the crimp barrel. Measure the distance from the end of the connector to the holding collar. If this distance is over 7 inches (17.78 cm), do not proceed; recheck all previous work.
- Repeat for Additional Cables
If installing an 'I', 'Y', or 'H' connector requiring multiple cables, repeat steps 5 through 7 for each remaining cable to be joined.
- Align Components and Crimp Connectors
Prior to crimping, confirm that all components are positioned correctly and that the bolt holes in the crimp connectors are properly aligned with the bolt holes of the mating part. Crimp the connectors following the instructions packaged with the connectors, rotating each crimp 90 or 180 degrees. After crimping, measure the distance from the end of the connector to the holding collar. If the distance is over 7 inches (17.78 cm), do not proceed; redo all previous work.
- Assemble Washers and Bolt
Assemble the washers and bolt in the following order: place the flat washer against the spade contact, then the Belleville washer (with the concave side down), followed by the hex-head bolt. Hand tighten the bolt. Clean and lubricate the area as shown in the original documentation.
- Torque Bolts to Specification
Using a torque wrench with a 15/16 inch socket, tighten all bolts to 50 to 60 ft. lbs. (67.8 to 81.3 Nm). The splice and cables are now in their final positions; do not attempt to move or reposition any part of the assembly after the bolts are tightened.
- Lubricate and Position Receptacle Housing
Apply the supplied lubricant or an ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the area of the splice section, and the inside mating surface of the receptacle housing. Slide the receptacle housing over the cable adapter and up to the edge of the interface (as shown in the documentation). Insert the nylon venting rod (supplied).
- Seat Receptacle Housing with Assembly Tool
Attach either the 650ATY or 600RRT assembly tool as shown in the documentation. For the 650ATY, ensure the 'U' shaped yoke is over the splice section and the 'C' shaped yoke is over the receptacle housing, then slowly raise the handle to slide the receptacle housing over the splice section. For the 600RRT, slide the receptacle housing over the interface by turning the hex nut on either side of the tool. WARNING: Do not place your hand on the threaded rod or guide shaft with the assembly tool in place. Once the housing is seated, remove the venting rod.
- Complete Final Checks and Grounding
Repeat steps 12 and 13 for any remaining cables. Check all cable adapters to ensure they are located properly and remove all vinyl tape markers. For grounding, complete the installation of an ECS grounding device according to its instructions, or connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings, making a small loop and twisting tightly without damaging the eye, then connect to ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.