
ABB Installation Products K655SR-L0230 600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and…
UPC: 075114346146
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating for medium-voltage applications
- Accommodates cable insulation diameters from 1.180" to 1.465"
- Supports 230 AWG compressed-stranded or 1/0 AWG compacted solid conductors
- Fully shielded, submersible molded rubber housing with peroxide-cured EPDM
- Meets ANSI/IEEE Standard 386 with 25kA symmetrical momentary rating
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amps |
Color | Black |
Conductor Range | #1 STR/COMPR AWG , 1/0 SOL/COMPT AWG |
Connection | Compression |
Connection Type | Deadbreak Straight Receptacle |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions, Fully Submersible |
Insulation | True |
Length | 16.98 in |
Length | 431.292 mm |
Material | Housing - EPDM-Rubber |
Material | Aluminum |
Series | 600 Series |
Size | Cable Insulation Diameter 1.180-1.465 inches |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Receptacle |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 7.4800 L |
Package Weight (Metric) | 3.3930 kg |

755LR-H0230
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.
K655SR-K0330-SG3
25KV Straight Receptacle 600 Amps with Cable Adapter, Lug Retainer Ring and Sealing Kit. Cable Insulation Diameter 1.090-1.310 inches, Aluminum Lug, Conductor Size 500-600 kcmil. SG3 - Cold Shrinkable Seal with Copper Braid and Constant Force Spring.
K655DLR-K0300
15/25kV, 600 Amp, Direct Test Elbow, DeadBreak, Cable Insulation 1.090-1.310 inches, Aluminum Compression Lug, Conductor Size 350 Stranded/Compressed or 400 Solid/Compact
K655SR-K-0300
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 350 or Compacted Solid 400 or mmSquared Compact 185.
K656DLR-H0270
600 Amp, 15/25kV, 600 Series Deadbreak Direct Test Elbow with Test Point, (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size AWG Compressed Stranded 4/0 or Compacted Solid 250 kcmil.
K655SR-H0270
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 or Compacted Solid 250 kcmil or mmSquared Compact 125.
K655DLR-J0300
15/25kV, 600 Amp, Direct Test Elbow, DeadBreak, Cable Insulation .980-1.180 inches, Aluminum Compression Lug, Conductor Size 350 Stranded/Compressed or 400 Solid/CompactFrequently Asked Questions
What is the maximum cable insulation diameter supported?
The ABB K655SR-L0230 supports cable insulation diameters ranging from 1.180 inches to 1.465 inches.
What conductor sizes are compatible with this receptacle?
This receptacle is compatible with 230 AWG compressed-stranded or 1/0 AWG compacted solid conductors.
What type of lug is included with the receptacle?
The K655SR-L0230 includes an aluminum compression lug.
What is the voltage rating of this ABB receptacle?
The ABB K655SR-L0230 is rated for 15/25kV.
What is the current rating for this deadbreak receptacle?
The current rating for the ABB K655SR-L0230 is 600 Amps.
How to Install the K655SR/M655SR Deadbreak Straight Receptacle
This guide provides step-by-step instructions for the safe and proper installation of the K655SR and M655SR deadbreak straight receptacles, which provide an in-line cable connection to standard ANSI-386 600 amp 15kV, 25kV or 35kV bushings. Ensure all apparatus are de-energized before starting and that installation is performed by competent personnel trained in high voltage electrical equipment safety practices.
Estimated time: 2h
Tools needed:
5/8-11 tap, Hex wrench, Torque wrench with 15/16 socket, Wire brush, Crimping tool, Wire strippers
Supplies needed:
Receptacle housing, Bushing adapter, Cable adapter, Aluminum holding collar, Hex head bolt, Crimp connector, Belleville washer, Flat washer, Nylon venting rod, Lubricants, Brass bolt, Bushing converter contact, Loctite, Tape marker, No. 14 AWG copper wire or equivalent, Suitable connector for neutral wires, Hose Clamp (M655SR for 35kV only)
- Prepare Apparatus Bushing and Assemble Bushing Converter
De-energize all apparatus. If a stud is present in the apparatus bushing, remove it and re-tap the hole using a 5/8-11 tap. Clean and lubricate the apparatus bushing and bushing converter interface. Apply 3-4 drops of Loctite to the threads of the brass bolt. Assemble the bushing converter onto the apparatus bushing, ensuring the bolt hole faces out, using the 5/8-inch brass bolt. Torque the bolt to 60 ft.-lbs.
- Prepare Cable End
Train the cable end and straighten it into its final position. Cut the cable squarely to ensure maximum available length for crimp growth.
- Manage Concentric Neutral Wires (If Applicable)
If applicable, unwrap the concentric neutral wires a distance of 30 inches (76cm). Do not cut these wires; instead, bend and fold them back out of the way.
- Clean Outer Cable Jacket and Slide Receptacle Housing
Wipe the outer jacket of the cable clean for a distance of 38 inches (96.5cm) or up to the concentric neutral wires. Slide the receptacle housing onto the cable a distance of 30 inches (76cm).
- Prepare Cable Semi-Con Shield
Remove the semi-con shield from the cable and install a tape marker to the dimensions shown in the documentation (10-1/4 inches or 26.04cm from the end, and 11-1/4 inches or 28.58cm for the shield removal length). Be careful not to cut or nick the cable insulation during this process.
- Bevel Cable Insulation and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor should be 4 3/4 inches to 5 inches (12.06cm to 12.7cm). If the length is incorrect, redo the assembly from previous steps.
- Install Holding Collar
Position the holding collar over the conductor and flush against the cable adapter. Using the supplied hex wrench, tighten the setscrew. The exposed conductor length from the holding collar should be 4 3/8 inches to 4 3/4 inches (11.11cm to 12.06cm).
- Prepare and Insert Crimp Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately insert it into the crimp connector, which contains inhibitor. Ensure the conductor is fully inserted into the crimp barrel. Measure the distance from the end of the connector to the holding collar. If this distance is over 7 inches (17.8cm), do not proceed and redo all previous work.
- Confirm Component Orientation and Bolt Hole Alignment
Confirm that all components (Receptacle Housing, Cable Adapter, Crimp Connector, Contact Adapter) are oriented in the correct order as shown in the documentation. Crucially, confirm that the bolt hole in the crimp connector is aligned with the bolt hole in the contact adapter.
- Crimp Connectors
Crimp the connectors following the instructions packaged with the connectors. Rotate each crimp 90 degrees. After crimping, measure the distance from the end of the connector to the holding collar. If this distance is over 7 inches (17.8cm), do not proceed and redo all previous work.
- Assemble Washers and Bolt
Assemble the washers and bolt in the following order: Flat washer against the spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten initially. Using a torque wrench with a 15/16 socket, tighten to 50-60 ft.-lbs. Do not attempt to move or reposition any part of the assembly after the bolts are tightened.
- Apply Lubricant
Generously apply the supplied lubricant or an ELASTIMOLD approved lubricant to the outside of the cable adapter and the area of the bushing adapter as shown in the documentation. DO NOT SUBSTITUTE other lubricants, as they may be harmful to the product or its mating product.
- Seat Receptacle Housing and Ground
Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the supplied nylon venting rod. Slide the receptacle housing onto the bushing converter until it is fully seated. Remove the venting rod. Connect a short piece of No. 14 AWG copper wire (or equivalent) to the grounding eye of the receptacle housing, making a small loop and twisting tightly without damaging the eye. Gather the concentric neutral wires and, using a suitable connector, connect them with the grounding wire.
- Install Hose Clamp (35kV Only)
FOR 35kV ONLY: Position the hose clamp between the locator bumps on the receptacle housing. Tighten the clamp until an audible click is heard.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.
