ABB Installation Products K655DLR-J0300 15/25kV, 600 Amp, Direct Test Elbow, DeadBreak, Cable Insulation .980-1.180 inches…
UPC: 075114297660
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage class, 600 Amp continuous rating
- Supports .980-1.180" cable insulation diameter
- Accommodates 350 stranded/compressed or 400 solid/compact conductors
- Fully shielded, submersible molded rubber housing (100% peroxide-cured EPDM)
- Direct Test System (EDTS) with insulated port for voltage testing
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amps |
Color | Black |
Conductor Range | 350 kcmil , 400 kcmil |
Connection | Compression |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions, Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | K655DLR |
Size | 0.980-1.180 inches |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arrestors, and fault current indicators. Direct conductor test point equipped elbow |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Direct Test Elbow Connector |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655LR-K0300-SG1
600 Series Elbow with insulated plug, cap, stud, lug and cable adapter, 15/25KV, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185. 200ECS-G1 Jacket Seal and Grounding Kit Included.
K655DLR-M0300
15/25kV, Deadbreak, 600 Series Direct Test Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size kcmil, Compressed Stranded 350 or Solid/Compacted 400.
K655DLR-N0410
15/25kV, 600 Amp, Direct Test Elbow, DeadBreak, Cable Insulation 1.515-1.780 inches, Aluminum Compression Lug, Conductor Size 1000 Stranded/Compressed
K655SR-J0270
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 or Compacted Solid 250 kcmil or mmSquared Compact 125.
K655SR-H0260
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 3/0 or Compacted Solid 4/0 or mmSquared Compact 95.
K655SR-F0270
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 4/0 or Compacted Solid 250 or mmSquared Compact 125.
K655SR-J0280
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 250 or Compacted Solid 300.
K655SR-J0240
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 or Compacted Solid 2/0.Frequently Asked Questions
What voltage ratings does this elbow support?
The K655DLR-J0300 is rated for 15/25kV medium-voltage applications.
What conductor sizes are compatible?
This elbow supports 350 stranded/compressed or 400 solid/compact conductors.
What cable insulation diameter range does it accept?
The unit accommodates cable insulation diameters between .980 and 1.180 inches.
Is this a deadbreak or loadbreak elbow?
The K655DLR-J0300 is a deadbreak elbow, designed for safe connections under no-load conditions.
What material is the compression lug made of?
The compression lug is constructed from aluminum for corrosion resistance and conductivity.
Can this elbow be used for temporary testing?
Yes, the direct test design allows for temporary or permanent test access in medium-voltage systems.
How to Install K655/K675DLR Direct Test Elbow Connectors
This guide provides detailed instructions for the safe and proper installation of 600/900 ampere K655/K675DLR Direct Test Elbow Connectors on 15kV and 25kV class systems, including cable preparation, lug crimping, and connection to mating apparatus.
Estimated time: 2h
Tools needed:
Wire strippers, Crimping tool, Wire brush (for aluminum conductors), Measuring tape or ruler, Hotstick tool (for direct test port operations), Torque wrench
Supplies needed:
Lubricant (supplied with elbow), Compression lug (supplied), Cable adapter (supplied), Insulating plug (supplied), Threaded stud (supplied), Vinyl plastic tape (if applicable), Tape retainer (if applicable), Tape marker (if applicable), Ground wire (minimum No. 14 AWG copper), Suitable ground connector, Waterproofing material (for cable jacket)
- Perform Initial Safety Checks and Component Inspection
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Inspect all parts for damage, rating, and compatibility with mating parts. Ensure all required tools and supplies are at hand and maintain cleanliness throughout the procedure. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit.
- Position Cable and Make Initial Cut
Position the cable in its final assembled location, ensuring enough slack for adequate clearance to remove the elbows. If using concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product.
- Clean Cable Surface and Check for Grounding Devices
Clean the outer surface of the cable for a distance of 24” (610mm) or up to the bent-back concentric neutral wires. If a 20MA or 21MA grounding device or 600ECS Jacket Cable Seal is being used, refer to their specific installation instructions for cable outer jacket removal, shield connection, and grounding. Otherwise, proceed with the following steps for cable preparation.
- Prepare Cable Jacket and Shield
Follow the steps applicable to your cable type: A. Remove the outer jacket to a dimension of 12-3/4” (324mm). B. Fold back shield wires. C. For flat metallic tape shield, remove it and secure with vinyl plastic tape to 10-3/4” (273mm). D. For fabric tape shield, remove it and install a tape retainer and tape marker to 9-3/4” (248mm) and 10-3/4” (273mm) respectively. E. For longitudinally corrugated shield, remove it and install a tape marker flush with the end, to 10-3/4” (273mm). F. For UNISHIELD* or G. LEAD SHEATH CABLE, a 10TL cable shield adapter is required; refer to its instructions. H. For semi-con shield, remove it and install a tape marker to 9-3/4” (248mm) and 10-3/4” (273mm). Do not cut or nick the cable insulation.
- Bevel Insulation and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor for Compression Lug
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. Verify the length of the exposed conductor is between 4-3/8” (111mm) to 4-11/16” (119mm). If the measurement is outside this range, redo the assembly.
- Install and Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping; it must be less than 6-1/2” (165mm). Crimp the compression lug following its supplied instructions, locating the first crimp on the end opposite the cable adapter. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. Verify the distance from the end of the compression lug to the cable adapter after crimping is between 6-1/2” to 7-1/4” (165mm – 184mm). If not, redo the assembly.
- Lubricate and Install Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Product and Install Threaded Stud
DANGER: DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED. Remove protective caps from both the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud (supplied with the elbow) into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean.
- Connect Elbow to Mating Product
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Product (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part.
- Install Insulating Plug and Voltage Detection Cap (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the voltage detection cap on the elbow and push down hard until it snaps into place. Refer to the Direct Voltage Test section in the product documentation for subsequent testing procedures.
- Ground Cable Shield and Waterproof Jacket
Insert one end of a piece of wire (with ampacity at least equivalent to No. 14 AWG copper) through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded; ground according to the instructions supplied with any grounding device used, or through an alternate method if no device is present. It is also recommended to waterproof the cable jacket at this point to prevent moisture from entering the cable.
- Verify Final Torque for L-Kits
CAUTION: When constructing 600amp L-Kits, ensure each component is tightened to the specified torque per the instructions provided with the L-Kit components.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.