ABB Installation Products K655DLR-K0300 15/25kV, 600 Amp, Direct Test Elbow, DeadBreak, Cable Insulation 1.090-1.310 inches…
UPC: 075114257640
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV Voltage Rating
- 600 Amp Current Rating
- DeadBreak Direct Test Elbow Design
- Accommodates 1.090-1.310 inch Cable Insulation
- Aluminum Compression Lug for 350 Stranded/Compressed or 400 Solid/Compact Conductors
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amps |
Color | Black |
Conductor Range | 350 kcmil , 400 kcmil |
Connection | Compression |
Connection Type | Direct Test Elbow, DeadBreak |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions, Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | K655DLR |
Size | 1.090-1.310 inches |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arrestors, and fault current indicators. Direct conductor test point equipped elbow |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Direct Test Elbow Connector |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

756LR-M0300-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. Cold-Shrinkable Jacket Seal Included.
K655SR-K-0300
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 350 or Compacted Solid 400 or mmSquared Compact 185.
K656DLR-H0270
600 Amp, 15/25kV, 600 Series Deadbreak Direct Test Elbow with Test Point, (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size AWG Compressed Stranded 4/0 or Compacted Solid 250 kcmil.
K655SR-H0270
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 or Compacted Solid 250 kcmil or mmSquared Compact 125.
K655DLR-J0300
15/25kV, 600 Amp, Direct Test Elbow, DeadBreak, Cable Insulation .980-1.180 inches, Aluminum Compression Lug, Conductor Size 350 Stranded/Compressed or 400 Solid/Compact
K655DLR-M0300
15/25kV, Deadbreak, 600 Series Direct Test Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size kcmil, Compressed Stranded 350 or Solid/Compacted 400.
K655DLR-N0410
15/25kV, 600 Amp, Direct Test Elbow, DeadBreak, Cable Insulation 1.515-1.780 inches, Aluminum Compression Lug, Conductor Size 1000 Stranded/CompressedFrequently Asked Questions
What is the voltage rating of the K655DLR-K0300?
The ABB K655DLR-K0300 has a voltage rating of 15/25kV.
What is the current rating for this direct test elbow?
This direct test elbow, model K655DLR-K0300, is rated for 600 Amps.
What cable insulation diameters can this elbow accommodate?
The K655DLR-K0300 is designed to fit cable insulation diameters ranging from 1.090 to 1.310 inches.
What conductor sizes are compatible with the aluminum compression lug?
The aluminum compression lug is compatible with 350 stranded/compressed or 400 solid/compact conductor sizes.
What type of elbow is the K655DLR-K0300?
The K655DLR-K0300 is a DeadBreak Direct Test Elbow.
How to Install K655/K675DLR Direct Test Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of K655/K675DLR Direct Test Elbow Connectors, including cable preparation, component assembly, and connection to high voltage apparatus.
Estimated time: 1h 30m
Tools needed:
Crimping Tool, Wire Brush (for aluminum conductors), Hotstick Tool (for testing port operations), Wire Strippers, Measuring Tape
Supplies needed:
K655/K675DLR Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack, Vinyl Plastic Tape (if applicable), Tape Retainer (if applicable), Tape Marker (if applicable), Ground Wire, Suitable Ground Connector
- Prepare the Cable for Installation
Position the cable so it is located in the final assembled position with enough slack to provide adequate clearance for removing the elbows. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from center line of the mating product. Clean the outer surface of the cable a distance of 24” (610mm) or up to the bent back concentric neutral wires. DANGER: Ensure all apparatus is de-energized before starting installation.
- Perform Cable Jacket and Shield Preparation
Refer to the specific instructions for your cable type (e.g., outer jacket, shield wires, flat metallic tape shield, fabric tape shield, longitudinally corrugated shield, UNISHIELD, lead sheath, or semi-con shield) to remove the outer jacket and shield to the specified dimensions. Install tape markers or retainers as required. Do not cut or nick the cable insulation. If using a 20MA/21MA grounding device or 600ECS Jacket Cable Seal, refer to their specific instructions.
- Install Cable Adapter and Prepare Conductor
Bevel the cable insulation end at a 45-degree angle, approximately 1/4” (6mm) back. Clean and lubricate the cable insulation, working toward the semi-con shield. Install the cable adapter, small end first, until flush with the tape marker edge. Remove protruding cable insulation, cutting it even with the cable adapter end. Verify exposed conductor length is 4-3/8” (111mm) to 4-11/16” (119mm). Do not cut or nick the cable adapter or conductor.
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it. Measure the 'Check Dimension' before crimping (must be less than 6-1/2” (165mm)). Crimp the compression lug following its instructions. Wipe all excess inhibitor. Verify the distance from the lug end to the cable adapter is 6-1/2” to 7-1/4” (165mm – 184mm) after crimping.
- Install the Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Connect to Mating Product
Remove protective caps from the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud (supplied with the elbow) into it. Clean and lubricate both the elbow and the mating part. Push the elbow onto the mating part, aligning the compression lug hole with the stud. DANGER: Do NOT connect or disconnect mating products while energized. Do NOT energize while disconnected.
- Complete Opposite End Connection (if applicable)
If connecting the opposite end of the elbow, clean and lubricate the mating part. Insert the mating part into the elbow, engage threads, and hand tighten. Torque the mating part according to its specific instructions. If an insulating plug is used, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow, pushing down until it snaps into place.
- Ground the Cable Shield
Insert one end of a wire (at least No. 14 AWG copper) through the grounding eye and twist to form a small loop. Connect this wire to ground using a suitable connector. Ensure the cable shield is grounded according to instructions supplied with any grounding device, or via an alternate method. Waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Direct Voltage Test (Optional)
If performing a direct voltage test, use only the appropriate direct voltage test port adapter and meter (e.g., 200TC-1, 200TC-2, 200TC-4). Read and understand separate operating instructions for the test port adapter and meter. DANGER: Inserting any object other than the appropriate direct voltage test port adapter and meter into the direct test port or in close proximity can cause electric shock, resulting in serious or fatal injury.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.