Authorized ABB Distributor (Installation Products)
ABB - Installation Products K655SR-K2330 - 600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size kcmil Compressed Stranded 500 or Compacted Solid 600 or mmSquared Compact 250/300. Length 17 inches, Diameter 4-1/4 inch.

ABB Installation Products K655SR-K2330 600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and…

UPC: 075114423205


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB K655SR-K2330 is a 600 Amp, 15/25kV deadbreak straight receptacle engineered for high-voltage medium-voltage applications requiring reliable, submersible cable connections. This fully shielded, molded rubber housing receptacle is designed for use with 600 Amp bushings on switchgear, transformers, and other electrical apparatus. The deadbreak design ensures safe connection and disconnection in de-energized states, isolating energized components to prevent arcing or accidental contact. Key specifications include compatibility with compressed stranded conductors up to 500 kcmil, compacted solid conductors up to 600 kcmil, or compact mm² conductors of 250/300. The cable insulation diameter range is 1.090 to 1.310 inches, with a physical length of 17 inches and diameter of 4-1/4 inches. The included copper compression lug delivers a low-resistance, durable electrical connection critical for maintaining system integrity and minimizing power loss. This receptacle meets ANSI/IEEE Standard 386 for 15kV and 25kV voltage classes, with ratings including 8.3kV phase-to-ground and 14.4kV phase-to-phase for 15kV, and 16.2kV phase-to-ground and 28kV phase-to-phase for 25kV. Impulse withstand ratings are 95kV BIL for 15kV and 140kV BIL for 25kV, ensuring robust performance under transient conditions. The product supports continuous 600 Amp operation and 25kA symmetrical momentary ratings for 10 cycles. Applications include utility and industrial power distribution systems where safe, efficient termination of medium-voltage cables is essential. The fully submersible design makes it suitable for harsh environments, including outdoor or underground installations. Optional accessories enable visible external separation, bypass, isolation, dead-ending, grounding, testing, and tap additions, enhancing versatility for complex installations.
  • 600 Amp, 15/25kV deadbreak straight receptacle for medium-voltage applications
  • Compatible with compressed stranded (500 kcmil), compacted solid (600 kcmil), or compact mm² (250/300) conductors
  • Cable insulation diameter range: 1.090 to 1.310 inches; length 17 inches, diameter 4-1/4 inches
  • Meets ANSI/IEEE Standard 386 with 95kV BIL (15kV) and 140kV BIL (25kV) impulse ratings
  • Fully shielded, submersible molded rubber housing for outdoor/underground installations

Specifications

Amperage Rating
600 A
Application
15/25kV, 600 Amps
Color
Black
Conductor Range
500 STR/CMP kcmil , 600 COMPT/SOL kcmil
Connection
Compression
Connection Type
Compression Lug, Deadbreak
Connection Type
Compression Lug
Current Rating
600 A
Environmental Conditions
All Weather Conditions, Fully Submersible
Insulation
True
Length
16.98 in
Length
431.292 mm
Material
Copper, Insulated
Material
Housing - EPDM-Rubber
Mounting Type
Direct Mounting (to bushing)
Series
600 Series
Size
Length 17 inches, Diameter 4.25 inches
Size
Length: 17 inches, Diameter: 4.25 inches
Special Features
Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Deadbreak Straight Receptacle
Voltage Rating
15 to 25 kV
Voltage Rating
15/25 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Bi-Metal Conductor size 2 AWG Stranded/Compressed, 1 AWG Solid/Compact. no Sealing Kit

168FLR1-B5220

Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Bi-Metal Conductor size 2 AWG Stranded/Compressed, 1 AWG Solid/Compact. no Sealing Kit
600 Amp, 15/25kV, 600 Series Deadbreak Direct Test Elbow with Test Point, (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size kcmil Compressed Stranded 1000.

K656DLR-N0410

600 Amp, 15/25kV, 600 Series Deadbreak Direct Test Elbow with Test Point, (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size kcmil Compressed Stranded 1000.
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70. Cold Shrinkable Seal with Copper Rod and Crimp Connector Included.

K656CY-G0250-SG1

15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70. Cold Shrinkable Seal with Copper Rod and Crimp Connector Included.
600 Amp Separable Cable Joints, Straight Receptacle, 15/25KV, Dead Break, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 400 kcmil or Solid Compact 450/500 kcmil or 202.68 mmSquared. Length 17 inch, Widest Diameter 4.19 inch. Includes Straight Receptacle Housing, Cable Adapter, Lug, Adapter Retaining Ring, Washer and Bolts, Lubricant, Installation Instruction Sheet and Crimp Chart.

K655YSR-K0310

600 Amp Separable Cable Joints, Straight Receptacle, 15/25KV, Dead Break, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 400 kcmil or Solid Compact 450/500 kcmil or 202.68 mmSquared. Length 17 inch, Widest Diameter 4.19 inch. Includes Straight Receptacle Housing, Cable Adapter, Lug, Adapter Retaining Ring, Washer and Bolts, Lubricant, Installation Instruction Sheet and Crimp Chart.
15/25kV, 900 Amp, DeadBreak, Elbow with Test Point (includes Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation .850-1.050 inches, Bi-Metal Compression Lug, Conductor Size AWG 2/0 Stranded/Compressed or 3/0 Compact/Solid.

K676LR-H5270

15/25kV, 900 Amp, DeadBreak, Elbow with Test Point (includes Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation .850-1.050 inches, Bi-Metal Compression Lug, Conductor Size AWG 2/0 Stranded/Compressed or 3/0 Compact/Solid.
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 or Compacted Solid 2/0.

K655SR-F0240

600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 or Compacted Solid 2/0.
35kV 600 Series Deadbreak Elbow without Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70. 200ECS Cold-Shrinkable Jacket Seal Included.

755LR-K0250-S

35kV 600 Series Deadbreak Elbow without Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70. 200ECS Cold-Shrinkable Jacket Seal Included.
600 Amp, 15/25kV, 600 Series Deadbreak, Replacement Elbow without Test Point, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0/ Compacted Solid 2/0.

K655RLR-G0240

600 Amp, 15/25kV, 600 Series Deadbreak, Replacement Elbow without Test Point, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0/ Compacted Solid 2/0.

Frequently Asked Questions

What is the K655SR product designed for?

The K655SR provides a fully shielded, submersible cable connection on 15/25kV high-voltage apparatus bushings, allowing a straight cable connection on switchgear.

Can the K655SR be connected or disconnected while energized?

No, the K655SR can only be easily connected or disconnected in a de-energized state.

Is the K655SR suitable for submersible applications?

Yes, the K655SR features a fully shielded and fully submersible molded rubber housing.

What is recommended for metallic tape shield cables?

When using metallic tape shield or drain wire cable, an ECS ground kit/cable seal is recommended.

What materials are used in the K655SR construction?

The K655SR features 100% peroxide-cured construction, including insulation and conductive EPDM materials.

What is the impulse withstand (BIL) for the 15kV class?

The 15kV voltage class has a 95kV BIL impulse withstand rating (1.2 x 50 microsecond wave).

What is the impulse withstand (BIL) for the 28kV class?

The 28kV voltage class has a 140kV BIL impulse withstand rating (1.2 x 50 microsecond wave).

What is the maximum phase-to-ground operating voltage for 28kV class?

For the 28kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV.

What is the maximum phase-to-ground operating voltage for 15kV class?

For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV.

What is the continuous current rating for the K655SR?

The K655SR has a continuous current rating of 600 Amps for both 15kV and 28kV voltage classes.

How to Install the K655SR/M655SR Deadbreak Straight Receptacle

This guide provides step-by-step instructions for the safe and proper installation of the K655SR and M655SR deadbreak straight receptacles, connecting an in-line cable to a standard ANSI-386 600 amp 15kV, 25kV, or 35kV bushing. Ensure all apparatus is de-energized before starting.

Estimated time: 2h

Tools needed:

5/8-11 tap (if applicable), Torque wrench, 5/8 inch socket, Cable cutter, Utility knife, Measuring tape, Hex wrench (supplied), Wire brush (for aluminum cable), Crimping tool, 15/16 inch socket, Screwdriver (for hose clamp, if 35kV)

Supplies needed:

Bushing converter contact, Brass bolt, Loctite, Lubricants (supplied or ELASTIMOLD approved), Receptacle housing, Cable adapter, Tape marker, Aluminum holding collar, Crimp connector, Flat washer, Belleville washer, Hex head bolt, Nylon venting rod (supplied), No. 14 AWG copper wire or equivalent, Suitable connector (for neutral/ground wires), Hose clamp (M655SR for 35kV only), Cleaning cloth/wipes

  1. Prepare Apparatus Bushing

    DANGER: Ensure all apparatus is de-energized. If a stud is present in the apparatus bushing, remove it and re-tap the hole using a 5/8-11 tap. Clean and lubricate the apparatus bushing and bushing converter interface. Assemble the bushing converter onto the apparatus bushing. Apply 3-4 drops of Loctite to the threads of the brass bolt. Assemble the contact adapter to the apparatus bushing, with the bolt hole facing out, using the 5/8 inch brass bolt. Torque to 60 ft.-lbs.

  2. Prepare Cable End

    Train the cable end and straighten it into its final position. Cut the cable squarely to ensure maximum available length for crimp growth. If applicable, unwrap the concentric neutral wires a distance of 30 inches (76cm), but DO NOT CUT them; bend and fold them back out of the way.

  3. Clean Cable Jacket and Install Receptacle Housing

    Wipe the outer jacket of the cable clean for a distance of 38 inches (96.5cm) or up to the concentric neutral wires. Slide the receptacle housing onto the cable a distance of 30 inches (76cm).

  4. Prepare Cable Insulation

    Remove the semi-con shield and install a tape marker to the dimensions shown in the documentation (10-1/4 inches / 26.04cm and 11-1/4 inches / 28.58cm). Do not cut or nick the cable insulation. Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean, then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.

  5. Expose Conductor and Secure Holding Collar

    Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor should be 4 3/4 inches to 5 inches (12.06cm to 12.7cm); otherwise, redo the assembly. Position the holding collar over the conductor and flush against the cable adapter. Using the supplied hex wrench, tighten the setscrew.

  6. Prepare and Position Crimp Connector

    Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately insert it into the crimp connector, which contains inhibitor. Ensure the conductor is fully inserted into the crimp barrel. Measure the distance from the end of the connector to the holding collar. If the distance is over 7 inches (17.8cm), do not proceed and redo all previous work.

  7. Align Components and Crimp Connector

    Confirm that components are oriented in the correct order: Receptacle Housing, Cable Adapter, Crimp Connector, Contact Adapter. CONFIRM THAT THE BOLT HOLE IN THE CRIMP CONNECTOR IS ALIGNED WITH THE BOLT HOLE IN THE CONTACT ADAPTER. Crimp the connectors following the instructions packaged with the connectors, rotating each crimp 90 degrees. After crimping, measure the distance from the end of the connector to the holding collar. If the distance is over 7 inches (17.8cm), do not proceed and redo all previous work.

  8. Assemble and Torque Bolt

    Assemble the washers and hex-head bolt in the following order: Flat washer against the spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten. Using a torque wrench with a 15/16 inch socket, tighten to 50-60 ft.-lbs. Do not attempt to move or reposition any part of the assembly after the bolts are tightened.

  9. Lubricate and Seat Receptacle Housing

    Apply the supplied lubricant or ELASTIMOLD approved lubricant generously to the outside of the cable adapter and the area of the bushing adapter as shown in the documentation. DO NOT SUBSTITUTE other lubricants, as they may be harmful. Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the supplied nylon venting rod. Slide the receptacle housing onto the bushing converter until it is fully seated. Remove the venting rod.

  10. Grounding and Neutral Connections

    Connect a short piece of No. 14 AWG copper wire (or equivalent) to the grounding eye of the receptacle housing. Make a small loop and twist tightly, taking care not to damage the eye. Gather together the concentric neutral wires. Using a suitable connector, connect the neutral wires and the grounding wire.

  11. Secure Hose Clamp (35kV Only)

    FOR 35kV ONLY: Position the hose clamp between the locator bumps on the receptacle housing. Tighten the clamp until an audible click is heard.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.