ABB Installation Products K655BLR-H0280 15/25kV 600 Series Deadbreak Elbow without Test Point (with Stud), Cable Insulation…
UPC: 783786651924
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage rating
- Accommodates 0.850" to 1.050" cable insulation diameter
- Aluminum compression lug for conductor connection
- Suitable for 250 kcmil stranded / 300 kcmil solid conductors
- ABB - Installation Products manufacturer
Specifications
Application | 15/25 kV, 600 Amps |
Connection | Compression |
Connection Type | Compression |
Material | Aluminum |
Material | Aluminum Compression Lug |
Series | 600 Series |
Size | 0.850 inch to 1.050 inch |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Elbow without Test Point |
Voltage Rating | 15/25kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 4.0000 L |
Package Weight (Metric) | 1.8140 kg |

K655BLR-K0330
600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 500 /Solid 600 /mmSquared 250/300.
K650CPSP
600 Amp, 15/25kV, Deadbreak, Connecting Plug. Widest Diameter 3 inches. With Factory assembled Stud which is not field removable.
L1601-PC-S2R-WG
35kv, Short Shank Well without Bail Tabs and with Replaceable Well Stud (2-3/4 inch Bushing Shank Length), With Gasket
K656LINKCLRM0360BDRG
600 Amp, 25kV, Deadbreak, Cam-Op Connector Kit. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400. With Insulated Cap, With Test Point.
K655BLR-H0240
15/25kV 600 Series Deadbreak Elbow without Test Point (with Stud), Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0.
K655BLR-N0410
15/25kV 600 Series Deadbreak Elbow without Test Point (with Stud), Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.
200ECS-G3-60
15/25/35kv, Cold-Shrinkable Seal kit, Size range .80 inch to 1.5 inch jacket diameters, maximum installed diameter is approximately 2 inches. 60 inch long braidFrequently Asked Questions
What is the voltage rating of the K655BLR-H0280 deadbreak elbow?
The ABB K655BLR-H0280 deadbreak elbow has a voltage rating of 15/25kV.
What cable insulation diameters does this deadbreak elbow support?
This deadbreak elbow supports cable insulation diameters ranging from 0.850 inches to 1.050 inches.
What type of lug is included with the K655BLR-H0280?
The K655BLR-H0280 includes an aluminum compression lug for conductor connection.
What conductor sizes are compatible with this deadbreak elbow?
It is compatible with compressed stranded conductors up to 250 kcmil and compacted solid conductors up to 300 kcmil.
Does the K655BLR-H0280 have a test point?
No, this model of the deadbreak elbow does not include a test point.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation, wiring, and initial setup of K655/K675LR and 655/675LR Deadbreak Elbow Connectors, designed for high voltage systems.
Estimated time: 1h 30m
Tools needed:
Wire brush, Crimping tool, Hotstick, Suitable sensing device (for capacitive test points), Torque wrench
Supplies needed:
K655/K675LR or 655/675LR Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug, Lubricant (silicone), Threaded Stud, Wire (min. No. 14 AWG Copper for grounding), Suitable connector (for grounding wire), HV insulated cap(s) or connector(s)
- Perform Pre-Installation Checks and Safety Procedures
DANGER: De-energize all apparatus in the work area before installation or removal. Do not touch or move energized products. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices. Follow all individual user, local, national work rules, and electrical standards. De-energize all deadbreak connectors before operating. Inspect all parts for damage, rating, and compatibility with mating parts. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit. Check package contents for completeness and ensure all components fit properly with the cable and/or mating products. Read all instructions completely before starting and have all required tools at hand, maintaining cleanliness throughout the procedure.
- Prepare the Cable for Installation
Assemble the cable in its final position, ensuring enough slack to allow adequate clearance for removing the elbows. If using concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product.
- Clean the Cable Outer Surface
Clean the outer surface of the cable for a distance of 24” (610mm) or up to the bent back concentric neutral wires.
- Prepare the Cable End
Refer to specific instructions for 20MA/21MA grounding devices, 600ECS Jacket Cable Seals, UNISHIELD*/LEAD SHEATH cable (which requires a 10TL cable shield adapter), or JACKETED/NON-JACKETED cable. For JACKETED/NON-JACKETED cable, remove the outer jacket (if applicable) and prepare the cable end to the specified dimensions (e.g., 9-3/4”, 10-3/4”, 12-3/4” for insulation, semi-con shield, and tape marker respectively, from the mating product end).
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare the Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor must be between 4-1/4” – 4-9/16” (108mm-116mm). If the length is outside this range, redo the assembly.
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping; this dimension must be less than 6-3/8”. If not, redo the assembly. Crimp the compression lug following the crimping instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping must be between 6-3/8” to 7-1/8” (162mm-181mm). If not, redo the assembly.
- Install the Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter is still flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare Mating Products
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud (supplied with the elbow) into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean.
- Connect the Elbow to the Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect the Opposite Mating Part
Clean and lubricate the mating part for the opposite end of the elbow. Insert the mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part.
- Install Insulating Plug (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps securely into place.
- Ground the Cable Shield
Insert one end of a wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded; ground it according to the instructions supplied with the grounding device. If no grounding device is used, ground the shield through an alternate approved method. It is also recommended to waterproof the cable jacket at this point to prevent moisture from entering the cable.
- Perform Voltage Test
WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the specific meter used. Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly in line with the test point assembly. Test with a suitable sensing device, specifically designed for separable connectors with capacitive test points, to determine if the cable is energized. Contamination, moisture, dirt, or using the wrong measuring equipment can provide a false 'no voltage' indication on an energized elbow. To prevent serious or fatal injury, treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.