ABB Installation Products K655BLR-N0410 15/25kV 600 Series Deadbreak Elbow without Test Point (with Stud), Cable Insulation…
UPC: 783786834815
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage rating for medium-voltage applications
- Deadbreak design enables safe load-break operations without system de-energization
- Accommodates cable insulation diameters from 1.515" to 1.780"
- Integrated 1000 kcmil aluminum compression lug for reliable conductor termination
- Molded EPDM construction for environmental resistance in harsh outdoor conditions
Specifications
Application | 15/25 kV, 600 Amps |
Connection | Compression |
Connection Type | Deadbreak with Stud |
Material | Aluminum |
Material | EPDM, Aluminum |
Series | 600 Series |
Size | 1.515-1.780 inch (cable insulation diameter) |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Elbow without Test Point |
Voltage Rating | 15/25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655BLR-K0330
600 Series Elbow with out Test Point, With Stud, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 500 /Solid 600 /mmSquared 250/300.
200ECS-G3-60
15/25/35kv, Cold-Shrinkable Seal kit, Size range .80 inch to 1.5 inch jacket diameters, maximum installed diameter is approximately 2 inches. 60 inch long braid
K650BIP-15PACK
15/25kV 600 Series Deadbreak Insulated Plug (with Cap). Material Epoxy, Length 4.5 inch, Widest Diameter 3 inch. - Pack of 15
600ECS-G3-60
15/25/35kv, Cold-Shrinkable Seal kit, Size range 1.28 inch to 2.30 inch jacket diameters, maximum installed diameter is approximately 2.75 inches. 60 inch long Braid
K1601PC-S2-CK3H
15/25kv, 200 Amp Bushing Clamp and Gasket Kit with 3-Holes. For use on Bushing Well without Bail Tabs only.
750S1-CK
35kv, 600 Amp, Short 2-15/16 inch Shank Bushing with out Stud, with standard aluminum conductor rod, includes 5/8-11 threaded hole at elbow end, includes shipping cap, With Clamp, GasketFrequently Asked Questions
What other Elastimold products are compatible with K655BLR?
The K655BLR can be mated with Elastimold products like K651CP, K650BIP, K650RTP, K650RTW, K650S1, K650J2, K650J3, or K650J4.
What is the one-minute AC withstand voltage for the K655BLR?
The one-minute AC withstand is 34kV for the 15kV class and 45kV for the 28kV class.
What is included in the K655BLR kit?
Each kit contains one K655BLR elbow connector housing, one tube of lubricant 82-08, one stud 650SA, and one installation instruction IS-0249.
What functions do optional accessories provide for K655BLR?
Optional accessories allow for visible external separation, by-pass, isolation, dead-ending, grounding, testing, and adding taps, surge arrestors, or fault current indicators.
How is the K655BLR connected or disconnected?
The K655BLR can be easily connected or disconnected using standard hand tools and equipment when in a de-energized state.
What are the key features of the K655BLR elbow housing?
It is a fully rated 15/25kV, 600 Amp deadbreak elbow with a fully shielded, submersible molded rubber housing made of 100% peroxide-cured EPDM materials.
What is the corona extinction voltage for the K655BLR?
The corona extinction voltage is 11kV AC for the 15kV class and 21.5kV AC for the 28kV class, both at 3pC sensitivity.
What is the 15-minute DC withstand voltage for the K655BLR?
The 15-minute DC withstand is 53kV for the 15kV class and 84kV for the 28kV class.
What is the BIL impulse withstand rating for the K655BLR?
The BIL impulse withstand is 95kV for the 15kV class and 140kV for the 28kV class.
What is the maximum operating voltage for the 28kV class?
For the 28kV class, the maximum phase-to-ground operating voltage is 16.2kV and phase-to-phase is 28kV.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and connection of K655/K675LR deadbreak elbow connectors to high voltage apparatus. It covers cable preparation, connector assembly, and initial grounding procedures.
Estimated time: 1h 30m
Tools needed:
Cutting tool, Wire brush, Crimping tool, Torque wrench, Hotstick, Suitable sensing device, Suitable grounding connector
Supplies needed:
Elbow connector, Cable adapter, Compression lug, Insulating plug (if applicable), Lubricant (silicone), Threaded stud (if not pre-equipped), No. 14 AWG Copper wire (or equivalent), Tape marker, HV insulated cap(s) or connector(s)
- De-energize Apparatus and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Inspect all parts for damage, proper rating, and compatibility with mating parts. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors before submerging or energizing.
- Prepare Cable for Connection
Assemble the cable in its final position with enough slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent back concentric neutral wires. Remove the outer jacket (if applicable) and prepare the cable insulation and semi-con shield according to the specific cable type (e.g., jacketed, non-jacketed, unishield, lead sheath).
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor and Crimp Compression Lug
Remove the protruding cable insulation by cutting it even with the end of the cable adapter, ensuring not to cut or nick the cable adapter or conductor. The exposed conductor length must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm). Fully insert the conductor into the compression lug (wire brush aluminum conductors immediately before insertion). Measure the 'Check Dimension' before crimping (must be less than 6-3/8 inches). Crimp the lug following its instructions. Wipe all excess inhibitor from the lug and cable adapter. The distance from the end of the lug to the cable adapter after crimping must be between 6-3/8 inches and 7-1/8 inches (162mm-181mm).
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Verify the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Connect Elbow to First Mating Part
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud (supplied with the elbow) into the mating part if it's not already equipped. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean. Push the elbow onto the mating part, aligning the hole in the compression lug with the stud.
- Connect Elbow to Second Mating Part or Insulating Plug
Clean and lubricate the mating part for the opposite end of the elbow. Insert the mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its supplied instructions. If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow, pushing down hard until it snaps into place.
- Ground the Cable Shield
Insert one end of a wire (at least No. 14 AWG Copper) through the grounding eye and twist to make a small loop, ensuring not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions supplied with any grounding device or use an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test (Verification)
Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the meter used. Test with a suitable sensing device to determine if the cable is energized. Contamination, moisture, dirt, or incorrect equipment can cause a false 'no voltage' indication. Treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means to prevent serious or fatal injury. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.