ABB Installation Products K151SP-B0270 200 Amp, 15/25kV, Deadbreak Elbow, Straight Plug, Bails are required but not included…
UPC: 783786803392
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 200 Amp current rating
- 15/25kV voltage class
- Straight plug configuration
- Accommodates 0.635" - 0.905" cable insulation diameter
- Includes aluminum compression lug for 4/0 AWG stranded / 250 AWG solid conductors
Specifications
Amperage Rating | 200 A |
Application | Designed to Terminate UD Cable having Concentric Neutral and Extruded instalation shielding |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Environmental Conditions | Fully Shielded, Fully Submersible |
Insulation | True |
Length | 8.81 in |
Length | 223.774 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for ground wire connection. Wide cable range with minimum number of sizes. No Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Plug |
Voltage Rating | 15 to 25 kV |
Width | 2.55 in |
Width | 64.77 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656CETP-J0270
25kv, 600 Amp Series, Deadbreak Combo-T. Connector Elbow with Intergral 200 Amp Loadbreak Tap Plug with Test Point. Cable Insulation Diameter 0.980 to 1.180 inches (24.9-30.0mm). Aluminum Conductor Material, Conductor Code 270 - 4/0 Stranded/Compressed or 250 Solid/Compact. No Sealing Kit.
274ELR-88110-5270
200 Amp, 25kV, Loadbreak Repair Elbow Connector with Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 3-1/4 inches in length. Includes 02509X long Bi-Metal Contact. Cable Insulation Diameter 0.880 inch to 1.100 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
K151SR-A0240
200 Amp, 15/25kV, Deadbreak Elbow, Straight Receptacle, Bails are required but not included, order separately. Cable Insulation Diameter 0.575 inch to 0.740 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 or Solid 2/0 or mmSquared 53.49.
167RLR-K5240
200 Amp, 15kV, Loadbreak Replacement Elbow Connector without Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.
168RLR-K-5260
200 Amp, 15kV, Loadbreak Replacement Elbow Connector with Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.
K151SR-C0260
200 Amp, 15/25kV, Deadbreak Elbow, Straight Receptacle, Bails are required but not included, order separately. Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 3/0 or Solid 4/0 or mmSquared 85.01.
K151SR-A0250
200 Amp, 15/25kV, Deadbreak Elbow, Straight Receptacle, Bails are required but not included, order separately. Cable Insulation Diameter 0.575 inch to 0.740 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 or Solid 3/0 or mmSquared 67.43.
376LR-L-5270-S
200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. 200ECS Jacket Seal Included.Frequently Asked Questions
What conductors are copper compression lugs suitable for?
Copper compression lugs are suitable for all copper conductors only.
What cables can the K151SP terminate?
It terminates UD cable with concentric neutral and extruded insulation shielding, and other cables with a proper Elastimold® cable shield adapter.
What conductor sizes does the K151SP accommodate?
The K151SP accommodates conductor sizes from No. 4 solid through 4/0 stranded.
What cable insulation diameters are supported?
It supports cable insulation diameters from .575 inches to 1.220 inches.
What Elastimold products are compatible with K151SP?
The K151SP is designed to mate with K151T tee splices and K151SR straight receptacles.
What is the 15kV class max operating voltage?
For the 15kV class, the maximum phase-to-ground operating voltage is 8.3kV.
What is the 25kV class max operating voltage?
For the 25kV class, the maximum phase-to-ground operating voltage is 15.2kV.
What is the continuous current rating?
The continuous current rating for both 15kV and 25kV voltage classes is 200 Amp.
What is the 15kV class impulse withstand rating?
For the 15kV class, the impulse withstand (BIL) is 95kV.
What is the 25kV class impulse withstand rating?
For the 25kV class, the impulse withstand (BIL) is 125kV.
How to Install the K151SP Straight Plug
This guide provides detailed instructions for installing the K151SP Straight Plug, designed for connecting solid dielectric type cables to other ELASTIMOLD products on 15kV and 25kV class systems. It covers cable preparation, crimping, assembly, and connection to a mating receptacle. All apparatus must be de-energized during installation, and work should only be performed by competent personnel trained in high voltage electrical equipment safety.
Estimated time: 1h 30m
Tools needed:
Cable cutting tool, Wire strippers, Wire brush, Crimping tool, Rag, Solvent applicator
Supplies needed:
K151SP Straight Plug, Conductor Contact (female), Nylon Venting Rod, Lubricant (supplied with kit), Crimp Chart (supplied with kit), Solid dielectric type cable, Silicone grease, ELASTIMOLD bail, Copper wire (#14 AWG or equivalent), Sealing material, Approved solvent, ECS or MA grounding device (optional)
- Prepare Cable Jacket and Shield
Cut and remove the cable jacket. For Jacketed Concentric Neutral, remove 8 inches, ensuring sufficient neutral wires for grounding. For Copper Tape Shield, remove 7-1/2 inches of jacket and 6-1/2 inches of copper tape shield from the cable end. If using an ECS or MA grounding device, follow its specific jacket cut-back instructions.
- Remove Insulation and Prepare Conductor
Remove 7/8 to 1 inch of cable insulation and conductive shield. For #1 stranded/compr. and #1/0 compt./solid aluminum cable, remove 1-3/4 to 1-7/8 inches. Cut squarely, do not pencil. Wire brush bare aluminum conductors and immediately insert them into the crimp barrel containing inhibitor.
- Crimp Socket Terminal
Crimp the socket terminal onto the bared conductor, holding the crimp barrel against the cable insulation. Refer to the supplied crimp chart. Start crimps at the crimp line imprinted on the barrel and rotate each successive crimp or indent 90 degrees. Carefully wipe any excess inhibitor from the contact and cable insulation.
- Clean and Pencil Insulation
Temporarily remove the plastic pin. Remove the semi-conductive shield 7-3/4 to 7-13/16 inches back from the end of the socket with a straight, smooth, squared cut; do not cut or nick the insulation. Replace the plastic pin. Pencil insulation 1/8 inch. Clean the outer jacket and thoroughly clean the insulation with an approved solvent, wiping from the cable end toward the outer jacket. If using an ECS or MA grounding device, install it per its instructions.
- Lubricate Cable and Slide Collar
Slide the collar, smaller end first, onto the cable. Keep cable insulation and the plug clean. Apply the supplied lubricant sparingly to the cable as shown and to the inside of the housing. Do not substitute other lubricants, as they may be harmful to the product or its mating part.
- Insert Cable into Plug Housing
Push the cable into the housing. Ensure the leading edge of the socket contact is flush with the front edge of the plug. Remove the plastic pin from the socket and discard it.
- Connect Plug to Mating Receptacle
Lubricate the nose of the plug with silicone grease. Place the nylon rod into the receptacle face until it bottoms (approximately 1-3/4 inches), ensuring the rod is not cut. Insert the plug assembly into the receptacle as far as possible. Pull out the nylon rod. Secure the electrical connection with an ELASTIMOLD bail, referencing the Bailing Instruction Sheet (150TB-4).
- Connect System Ground
If an ELASTIMOLD grounding device is not being used, connect a length of #14 AWG (or equivalent) copper wire through the grounding tab and twist tightly. Connect this grounding assembly to the system ground by merging it with the cable shield of each cable. Seal the grounding wires and connections to prevent corrosion.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.