ABB Installation Products 376LR-L-5270-S 200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter…
UPC: 783786962297
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Bi-metal compression lug supports 4/0 AWG stranded or 250 kcmil solid conductors
- Cable insulation diameter range: 1.180–1.465 inches (30.0–37.2 mm)
- Non-corrosive capacitive test point for safe energized circuit verification
- Fully shielded, submersible EPDM housing with hot stick and ground provisions
- Includes 200ECS Jacket Seal for environmental protection
Specifications
Amperage Rating | 200 A |
Application | 35 kv, 200 Amp |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection | Push-In |
Connection Type | Compression Lug |
Current Rating | 200 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Bi-Metal, Poly |
Material | Housing - EPDM-Rubber |
Size | Cable Insulation Diameter 1.180 inch to 1.465 inch |
Special Features | 35kV, 200 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for hot stick operation. Provision for ground wire connection. Non-Corrosive Capacitive Voltage Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 10.5 IN x 19.12 IN x 12.5 IN |
Package Dimensions (L x W x H) | 26.67 cm x 48.5648 cm x 31.75 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

375LR-L-2270
200 Amp, 35kV, Loadbreak Elbow Connector without Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
167RLR-G5230-S
200 Amp, 15kV, Loadbreak Replacement Elbow Connector without Test Point, Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact. 200ECS Jacket Seal Included.
K151SP-C2250
200 Amp, 15/25kV, Deadbreak Elbow, Straight Plug, Bails are required but not included, order separately. Cable Insulation Diameter 0.805 inch to 1.060 inch. Copper Compression Lug, Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
274ELR-88110-5250
200 Amp, 25kV, Loadbreak Repair Elbow Connector with Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 3-1/4 inches in length. Includes 02509X long Bi-Metal Contact. Cable Insulation Diameter 0.880 inch to 1.100 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
274FLR3-B0240
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Capactive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 1/0 AWG Stranded Compressed, 2/0 AWG Solid Compact
274FLR3-B0250
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Capactive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 2/0 AWG Stranded Compressed, 3/0 AWG Solid Compact
274FLR3-A0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Capactive Test Ports, Large Housing, Cable Insulation Diameter 0.575 inch - 0.740 inch / 15-19mm, Aluminum Conductor size 2 AWG Stranded Compressed, 1 AWG Solid Compact
274FLR3-B0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Capactive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 2 AWG Stranded Compressed, 1 AWG Solid CompactFrequently Asked Questions
What is the maximum voltage rating for this elbow connector?
The ABB 376LR-L-5270-S is rated for 35kV.
What cable insulation diameter range does this connector support?
This loadbreak elbow connector supports cable insulation diameters from 1.180 inches to 1.465 inches.
What conductor sizes can be terminated with the bi-metal lug?
The bi-metal compression lug can accommodate compressed stranded conductor sizes of 4/0 AWG and solid conductor sizes up to 250 kcmil (126.67 mm²).
Does this connector include a jacket seal?
Yes, the 200ECS Jacket Seal is included with the 376LR-L-5270-S.
What is the purpose of the test point on this connector?
The integrated test point allows for safe and convenient testing of energized circuits.
How to Install the 376LR Loadbreak Elbow Connector
This guide provides step-by-step instructions for the safe installation and initial connection of the 376LR Loadbreak Elbow Connector to UD cable and a 35kV class bushing.
Estimated time: 1h 30m
Tools needed:
Probe wrench, Crimp tool, Wire brush, Hotstick
Supplies needed:
Lubricant (Do Not Substitute), No. 14 AWG / 2.5mm copper wire (or equivalent), Grounding connector, UD cable
- Perform Pre-Installation Checks
Check the package contents to ensure they are complete and undamaged. Verify all components for proper fit with the cable and mating products. Test the threads by threading the probe into the compression lug; replace any damaged components if resistance is encountered prior to full assembly. Ensure all required tools are at hand and maintain cleanliness throughout the procedure. DANGER: All apparatus must be de-energized during installation. This product must be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment.
- Train and Cut Cable
Train the UD cable to ease future operation. Cut any excess cable squarely at the center line of the bushing.
- Prepare Cable End
Unwrap and bind the concentric neutral wires 8-1/2 inches back from the end of the cable. Remove the shield and insulation from the cable end, cutting squarely and taking care not to nick the conductor. Wire brush bare aluminum conductors and immediately install the compression lug, rotating it to spread the inhibitor. Position the compression lug so its contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe excessive inhibitor from the outside of the lug and cable. Remove the insulation shield as shown and bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble the Elbow Connector
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant ONLY; do not substitute. Slide the elbow connector onto the cable with a back-and-forth twisting motion, then wipe off all excess grease. Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, taking care not to cross-thread; the probe must turn freely for approximately four turns before becoming snug. Tighten the probe with a wrench until the wrench bends.
- Connect Concentric Neutral Wires
Using a separate copper wire (No. 14 AWG / 2.5mm or equivalent), insert one end through the grounding eye on the elbow and twist it tight, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector. Provide adequate slack in the neutral wires for elbow operation.
- Connect Elbow to Bushing (De-energized)
LUBRICATE ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. If an insulated cap is present on the bushing, remove it by attaching a hotstick tool to its pulling eye. Securely fasten a hotstick to the loadbreak connector pulling eye. After establishing firm footing and positive control of the elbow connector, insert the probe tip approximately 2 inches into the bushing. Immediately push the elbow home with a fast, firm, straight motion, applying sufficient force to engage the internal lock on the elbow connector and bushing interface. Do not hold the elbow in the partially inserted position.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.