ABB Installation Products 756LR-P0380-SG3 15/25/35kV, 600 Amp, Deadbreak Elbow, with Test Point (includes Plug, Cap, Stud, Lug and…
UPC: 075114322966
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Voltage rating: 15/25/35 kV with 600 A current rating
- Deadbreak elbow with integrated test point for safe voltage verification
- Cable insulation diameter compatibility: 1.725–1.935 inches
- Aluminum lug for 750 kcmil stranded compressed conductors
- Includes SG3 cold shrinkable sealing kit with copper braid and constant force spring
Specifications
Amperage Rating | 600 A |
Application | 15/25/35kV, 600 Amps |
Color | Black |
Conductor Range | 700 to 750 kcmil , 900 kcmil |
Connection | Compression |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | SG3 Sealing Kit - Cold Shrinkable Seal with Copper Braid and Constant Force Spring |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

776LR-P2380-SG3
900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included. Cable Insulation Diameter 1.725 inch to 1.935 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
252LR-C5220
25 kV, 200 Amp, Deadbreak, Elbow Connector with Test Point, No Sealing Kit, Cable Insulation Diameter - .805-1.060 inch, Bi-Metal Lug, Conductor Size #2 Stranded/Compressed or #1 Solid/Compact. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide.
252LRJS-C5240
25 kV, 200 Amp, Deadbreak, Elbow Connector with Test Point, with Jacket Seal, Cable Insulation Diameter - .805-1.060 inch. Bi-Metal Lug, Conductor Size 240 - 1/0 Stranded/Compressed or 2/0 Compact/Solid. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide.
376LR-J2240
35KV, 200 Amp, Loadbreak Elbow, with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0.
252LR-B5220
25 kV, 200 Amp, Deadbreak, Elbow Connector with Test Point, No Sealing Kit, Cable Insulation Diameter - .635-.905 inch, Bi-Metal Lug, Conductor Size #2 Stranded/Compressed or #1 Solid/Compact. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide.
756LR-Q0410-SG3
15/25/35kV, 600 Amp, Deadbreak Elbow, with Test Point (includes Plug, Cap, Stud, Lug and Cable Adapter), Cable Insulation Diameter 1.910-2.120 inches, Aluminum Lug, Conductor Size 1000 kcmils Stranded Compressed, With SG3 Sealing Kit - Cold Shrinkable Seal with Copper Braid and Contant Force Spring.
756LR-L0280-SG3
15/25/35kV, 600 Amp, Deadbreak Elbow, with Test Point (includes Plug, Cap, Stud, Lug and Cable Adapter), Cable Insulation Diameter 1.180-1.465 inches, Aluminum Lug, Conductor Size 250 kcmils Stranded Compressed, With SG3 Sealing Kit - Cold Shrinkable Seal with Copper Braid and Contant Force Spring.
756LR-M0330-SG3
15/25/35kV, 600 Amp, Deadbreak Elbow, with Test Point (includes Plug, Cap, Stud, Lug and Cable Adapter), Cable Insulation Diameter 1.370-1.630 inches, Aluminum Lug, Conductor Size 500 kcmils Stranded Compressed, With SG3 Sealing Kit - Cold Shrinkable Seal with Copper Braid and Contant Force Spring.Frequently Asked Questions
What is the maximum current rating of this elbow?
The elbow has a continuous current rating of 600 amperes.
What cable insulation diameter range does this elbow accommodate?
The elbow fits cable insulation diameters between 1.725 and 1.935 inches.
What conductor size is compatible with this elbow?
The elbow is designed for 750 kcmil stranded compressed conductors.
Does this elbow include a test point?
Yes, the elbow features an integrated test point for safe voltage verification.
What sealing kit is included with this elbow?
The elbow includes the SG3 cold shrinkable sealing kit with copper braid and constant force spring.
Is this elbow suitable for deadbreak applications?
Yes, the elbow is designed for deadbreak applications, allowing safe operation under load.
What material is the lug made from?
The lug is constructed from aluminum for corrosion resistance and conductivity.
How to Install 756/776LR Deadbreak Elbow Connectors
This guide provides detailed instructions for the safe installation of 756LR and 776LR deadbreak elbow connectors. These connectors enable fully shielded, submersible cable connections to high voltage apparatus for 35kV class systems.
Estimated time: 2h
Tools needed:
Crimp tool, Wire brush, Hotstick, Suitable sensing device (for capacitive test points), Torque wrench, Wire strippers, Cleaning supplies
Supplies needed:
756/776LR Elbow Connector kit (Elbow, Cable Adapter, Compression Lug, Insulating Plug, Crimp connector, Lubricant, Stud Prepack), Tape marker, Grounding device (e.g., 20MA, 21MA, 600ECS, 10TL) or equivalent grounding wire, No. 14 AWG Copper wire (or equivalent ampacity) for grounding, Silicone lubricant, Protective caps (if not included in kit)
- Prioritize Safety and Inspect Components
DANGER: Ensure all apparatus are de-energized before starting installation. This product must be installed only by competent personnel trained in high voltage safety practices. Inspect all kit contents for completeness, damage, proper rating, and compatibility with mating parts. Read these instructions entirely before beginning.
- Position and Clean the Cable
Position the cable in its final assembled location, ensuring enough slack for elbow removal. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer jacket of the cable for a distance of 24 inches (610mm).
- Prepare the Cable for Connection
Follow the specific cable preparation instructions for your cable type (e.g., Unishield, Jacketed, Non-Jacketed). Remove the outer jacket (if applicable) and prepare the cable insulation and semi-con shield to the specified dimensions as indicated in the provided diagrams. If using a grounding device or cable seal, refer to its specific instructions for jacket removal and shield connection.
- Install Cable Adapter and Prepare Conductor
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker. Remove the protruding cable insulation, cutting it even with the end of the cable adapter, ensuring the exposed conductor length is between 4-3/8 inches (111mm) and 4-3/4 inches (121mm). Do not nick the cable adapter or conductor.
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it. Measure the 'Check Dimension' before crimping; it must be less than 7 inches (178mm). Crimp the compression lug according to its supplied instructions. After crimping, wipe off any excess inhibitor. The distance from the end of the compression lug to the cable adapter should be between 6-7/8 inches (175mm) and 7-5/8 inches (194mm).
- Install the Elbow Connector
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Verify the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Connect to Mating Apparatus
WARNING: Do not connect or disconnect mating products while energized, and do not energize while disconnected. Remove protective caps from both the elbow and the mating part. Hand tighten the supplied threaded stud into the mating part if it lacks one. Clean and lubricate both the elbow and the mating part. Push the elbow onto the mating part, aligning the compression lug hole with the stud. For the opposite end, clean and lubricate the mating part, insert it into the elbow, engage threads, hand tighten, and then torque according to the mating part's instructions.
- Ground the Cable Shield and Install Insulating Plug (Optional)
Insert a No. 14 AWG Copper wire (or equivalent) through the grounding eye, twist to form a loop, and connect it to ground using a suitable connector. Ensure the cable shield is properly grounded, either via a grounding device or an alternate method. If using an insulating plug as a mating part, clean and lubricate its inner surface and the voltage detection cap, then push the cap onto the elbow until it snaps into place. Waterproof the cable jacket to prevent moisture ingress.
- Perform Voltage Test (Post-Installation)
CAUTION: The voltage test point is a capacitance device, not directly connected to the conductor. Remove the test point cap with a hotstick by peeling it off at an angle. Use a suitable sensing device designed for capacitive test points to determine if the cable is energized, following the manufacturer's directions for the meter. Do not use conventional voltage measuring equipment. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means to prevent serious injury. After testing, clean and lubricate the inside of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.