ABB Installation Products 376LR-J2240 35KV, 200 Amp, Loadbreak Elbow, with Test Point, Cable Insulation Diameter 0.980 inch to…
UPC: 075114328180
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV, 200 Amp continuous and loadbreak rating
- Fully shielded, submersible molded rubber housing with peroxide-cured EPDM
- Integrated non-corrosive capacitive voltage test point for safe energized testing
- Accommodates cable insulation diameters 0.980" to 1.180" (24.89-29.97mm)
- Long bi-metal compression lug for AWG 1/0 compressed stranded and AWG 2/0 solid conductors
- Hot stick operation provision with visible disconnect interface
- Meets ANSI/IEEE Standard 386 with 150kV BIL impulse withstand
- 10kA symmetrical momentary and fault close capability
Specifications
Amperage Rating | 200 A |
Application | 35 kv, 200 Amp |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Connection | Push-In |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Size | Cable Insulation Diameter 0.980 inch to 1.180 inch |
Special Features | 35kV, 200 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for hot stick operation. Provision for ground wire connection. Non-Corrosive Capacitive Voltage Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

375LR-K-5240
35kV 200 Amp, Loadbreak Elbow Connector without Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
252LR-B5220
25 kV, 200 Amp, Deadbreak, Elbow Connector with Test Point, No Sealing Kit, Cable Insulation Diameter - .635-.905 inch, Bi-Metal Lug, Conductor Size #2 Stranded/Compressed or #1 Solid/Compact. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide.
756LR-Q0410-SG3
15/25/35kV, 600 Amp, Deadbreak Elbow, with Test Point (includes Plug, Cap, Stud, Lug and Cable Adapter), Cable Insulation Diameter 1.910-2.120 inches, Aluminum Lug, Conductor Size 1000 kcmils Stranded Compressed, With SG3 Sealing Kit - Cold Shrinkable Seal with Copper Braid and Contant Force Spring.
756LR-L0280-SG3
15/25/35kV, 600 Amp, Deadbreak Elbow, with Test Point (includes Plug, Cap, Stud, Lug and Cable Adapter), Cable Insulation Diameter 1.180-1.465 inches, Aluminum Lug, Conductor Size 250 kcmils Stranded Compressed, With SG3 Sealing Kit - Cold Shrinkable Seal with Copper Braid and Contant Force Spring.
756LR-M0330-SG3
15/25/35kV, 600 Amp, Deadbreak Elbow, with Test Point (includes Plug, Cap, Stud, Lug and Cable Adapter), Cable Insulation Diameter 1.370-1.630 inches, Aluminum Lug, Conductor Size 500 kcmils Stranded Compressed, With SG3 Sealing Kit - Cold Shrinkable Seal with Copper Braid and Contant Force Spring.
262LR-A5220
25kV, 200 Amp, Loadbreak Elbow, with Test Point, Cable Insulation Diameter .575-.740 inches, Bi-Medal Lug, Conductor Size #2 AWG Stranded Compressed or #1 AWG Compact/Solid. No Sealing Kit.
376LR-K2240
35KV, 200 Amp, Loadbreak Elbow, with Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0.
756LR-N0410
35kV, 600 Amps, Deadbreak Elbow with Test Point. Cable Insulation Diameter Range 1.515 to 1.780 inch, Aluminum Lug, Conductor Size 1000 Stranded/Compressed. No Sealing Kit.Frequently Asked Questions
What is the corona extinction voltage?
The corona extinction voltage is 26kV AC at 3p.C. sensitivity.
What conductor materials are compatible with the copper lug?
The copper compression lug is suitable for all copper conductors only.
What conductor materials are compatible with the bi-metal lug?
The bi-metal compression lug, with its universal aluminum barrel, is suitable for both copper and aluminum conductors.
What is the DC fifteen-minute withstand rating?
The DC fifteen-minute withstand rating for the 376LR elbow is 103kV DC.
What is the AC one-minute withstand rating?
The AC one-minute withstand rating for the 376LR elbow is 50kV AC.
What is the impulse withstand rating?
The impulse withstand rating (BIL) is 150kV (1.2 x 50 microsecond wave).
What cable insulation diameters are compatible?
The 376LR elbow connects to cables with insulation diameters from .850 inches (21.6mm) to 1.465 inches (37.2mm).
Is the 376LR elbow submersible?
Yes, the 376LR elbow features a fully shielded, fully submersible molded rubber housing.
Can the 376LR elbow be used with hot stick tools?
Yes, the 376LR elbow includes provisions for energized operation using standard hot stick tools for loadmaking/loadbreak operation and a visible disconnect.
What type of compression lug is standard?
A long bi-metal compression lug is standard with the 376LR elbow connector.
How to Install Elastimold 375LR/376LR Loadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and initial setup of Elastimold 375LR and 376LR Loadbreak Elbow Connectors, designed for terminating UD cables to 35kV class bushings.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Crimp tool, Wire brush, Hotstick, Suitable sensing device for capacitive test points
Supplies needed:
Compression Lug, Probe, Lubricant (Do Not Substitute), No. 14 AWG / 2.5mm Copper Wire, Grounding Connector
- Prepare for Installation and Ensure Safety
DANGER: Ensure all apparatus is de-energized before beginning installation or removal of parts, except for test point caps and indicators. This product must be installed only by competent personnel trained in high voltage safety practices. Inspect all package contents and components for damage, proper rating, and compatibility with cable and mating products. Read all instructions thoroughly before starting.
- Prepare the Cable
Train the cable to ease operation, ensuring a minimum of 20 inches beyond the end of the cable pad mount transformer. Cut excess cable squarely at the center line of the bushing. Unwrap and bind concentric neutral wires 8-1/2 inches back from the cable end. Remove the shield and insulation, cutting squarely without nicking the conductor. Wire brush bare aluminum conductors and immediately install the compression lug, rotating to spread inhibitor. Align the lug's threaded hole with the bushing bore. Crimp the lug according to the crimp chart, starting at the mark and rotating 180 degrees for each successive crimp. Carefully wipe off any excess inhibitor. Remove the insulation shield as shown in the template, beveling the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble the Elbow Connector
Lubricate the cable insulation and the inside of the elbow housing using only the supplied lubricant; do not substitute. Slide the elbow connector onto the cable with a back-and-forth twisting motion, then wipe off all excess grease. Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, ensuring it turns freely for approximately four turns before becoming snug. Tighten the probe with the probe wrench until the wrench bends, indicating proper torque.
- Connect the Concentric Neutral
Insert one end of a separate No. 14 AWG (2.5mm) copper wire or equivalent through the grounding eye on the elbow. Twist it tight, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector. Ensure adequate slack in the wires to allow for elbow operation.
- Connect the Elbow to the Bushing
DANGER: Lubricate the receptacle portion of the elbow connector and the mating bushing only if both the transformer and elbow are known to be de-energized. Securely fasten a hotstick to the loadbreak connector pulling eye. If present, remove the insulated cap from the bushing using the hotstick. Withdraw the elbow from the apparatus parking stand with a fast, straight, firm motion, being careful not to place it near a ground plane. Insert the probe tip approximately 2 inches into the bushing, then immediately push the elbow home with a fast, firm, straight motion, applying sufficient force to engage the internal lock.
- Perform Voltage Test (376LR Only)
For 376LR models, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The test point is a capacitance device; do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points to determine if the cable is energized. Contamination or incorrect equipment can cause a false 'no voltage' indication. Treat the elbow as energized until confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone grease and replace it tightly on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.