- 600 Amp, 15kV Deadbreak Stick-Op Connector Kit
- Accommodates cable insulation diameter from 0.980" to 1.180"
- Features an aluminum compression lug for secure connections
- Compatible with 3/0 AWG stranded, 4/0 AWG solid, and 95 mm² compact conductors
- Includes insulated cap for enhanced safety and protection
Specifications
Amperage Rating | 600 to 200 A |
Application | Connect 600 Amp interface to 200 Amp Loadbreak Tap |
Color | Black |
Conductor Range | 3/0 STR/COMPR AWG , 4/0 SOL/COMPT AWG |
Connection Type | Deadbreak Stick-Op Connector |
Current Rating | 600 A |
Enclosure | Yes, EPDM Rubber |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Material | Aluminum Compression Lug |
Series | 600 Series |
Size | Cable Insulation Diameter 0.980 inch to 1.180 inch |
Special Features | Reducing Tap Plug 600 to 200 Amps. Provides an External Visible Break by Hotstick Removal of the Elbow |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Stick Op Reducing Tap Plug Connector |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

161LR-B5260
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
655LRTP-J0260-DRG-S
600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, With Insulated Cap. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95. 200ECS Cold-Shrinkable Jacket Seal Included.
756LRTP-K0270-DRG
600 Amp, 35kV, Deadbreak, Stick-Op Connector Kit, with Capacitive test point, Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. With Insulated Cap.
K655LRTP-K0300
600 Amp, 25kV, Stick-Op Connector Kit. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185.
756LRTP-P0410-DRGS
600 Amp, 35kV, Deadbreak, Stick-Op Connector Kit, with Capacitive test point, Aluminum Compression Lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Conductor Size AWG or kcmil, Compressed Stranded 1000. With Insulated Cap. Cold-Shrinkable Jacket Seal Included.
K656LRTP-P0380-DRG
600 Amp, 25kV, Deadbreak, Stick-Op Connector Kit with Test Point, Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. With Insulated Cap.
656CETPJ0270DRG-S
15kV, 600 Amp Combo T, carries current. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. 200ECS Cold-Shrinkable Jacket Seal Included.
675CETP-L2330
15kV, 200/900 Amp Series Loadbreak, ComboT Elbow with 200 Amp Reducing Tap Plug, Stud, Cable Adapter and Lug Kit without Test Point. Cable Insulation Diameter 1.180-1.465 inches (30.0-37.2mm). Copper Lug, 330-Conductor Size 500 kcmil Stranded/Compressed or 600 kcmil Solid/Compact or 250/300 mmsq. Includes Elbow Housing, Stud, Compression Lug, Tube of Lubricant, Cable Adapter, Installation Instructions and Crimp Chart. No Sealing Kit.Frequently Asked Questions
What is the maximum voltage rating for this connector kit?
The ABB 655LRTP-J0260-DRG connector kit has a maximum voltage rating of 15kV.
What is the current carrying capacity of this connector kit?
This connector kit is rated for 600 Amps.
What is the range of cable insulation diameters supported?
The connector kit supports cable insulation diameters ranging from 0.980 inches to 1.180 inches.
What type of lug material is used in this kit?
This kit features an aluminum compression lug.
What conductor sizes are compatible with this connector?
It is compatible with compressed stranded 3/0 AWG, compacted solid 4/0 AWG, and compact 95 mm² conductors.
How to Install and Remove the Elastimold 160DRG/167DRG Insulated Cap with Ground Lead
This guide provides instructions for the safe installation and removal of the Elastimold 160DRG and 167DRG insulated caps, designed for insulating, shielding, and watersealing 15kV class loadbreak bushing interfaces. Ensure all apparatus is de-energized during installation or removal.
Estimated time: 15m
Tools needed:
Hotstick
Supplies needed:
Insulated Cap with Ground Lead, Lubricant
- Connect Grounding Wire
Connect the free end of the electrostatic grounding wire to the system ground, ensuring enough slack for hot-stick operation. CAUTION: Train the grounding wire to avoid contact with the bushing interface during operation.
- Prepare Insulated Cap
Remove the protective cover from the insulated cap. Lubricate the cap's internal mating surface using only the supplied lubricant or ELASTIMOLD approved lubricants. DO NOT SUBSTITUTE. Keep the internal mating surface free from dirt and grime. Always replace the protective cover when not in use.
- Install Insulated Cap
Firmly attach a hotstick to the insulated cap's pulling eye. Insert the male contact of the insulated cap into the loadbreak bushing, and push it home with a fast, firm, straight motion. Make certain it is fully mated, with the locking ring seated. Detach the hotstick from the insulated cap.
- Remove Insulated Cap
Attach a hotstick to the pulling eye of the insulated cap. Before pulling, rotate the insulated cap clockwise while in the mated position to break surface friction. Pull the receptacle off with a fast, firm, straight motion to complete the operation. Remove the electrostatic grounding wire of the insulated cap from the system ground. Replace the protective cover on the insulated cap to keep its internal surface clean.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.