- 2 Inch Straight Malleable Iron Chase Connector
- Liquidtight Insulated Design
- Electro-Zinc Plating for Corrosion Resistance
- Durable Malleable Iron Construction
- Secure Termination for Industrial Applications
Specifications
Finish | Electro Zinc Plating |
Material | Malleable Iron |
Size | 2 Inch |
Standard | UL E23018, CSA |
Type | Chase Connectors-Straight |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 2.0500 L |
Package Weight (Metric) | 0.9300 kg |

5368
2-1/2 Inch Straight Malleable Iron Chase Liquidtight Insulated Connector With Electro-Zinc Plating
5372
1/2 Inch 90 Degree Malleable Iron Chase Liquidtight Insulated Connector With Electro-Zinc Plating
5371
3/8 Inch 90 Degree Malleable Iron Chase Liquidtight Insulated Connector With Electro-Zinc Plating
5373
3/4 Inch 90 Degree Malleable Iron Chase Liquidtight Insulated Connector With Electro-Zinc PlatingFrequently Asked Questions
What are the applications for these liquid-tight fittings?
These fittings are used in outdoor or indoor locations exposed to moisture, for bonding flexible liquid-tight metallic conduit to enclosures. They protect against water, oils, cutting fluids, and mild acids.
Are these fittings suitable for hazardous locations?
Yes, they are suitable for Class I Division 2, Class II Division 1 & 2 Hazardous Locations per NEC® Section 500 and CE Code.
What voltage can these fittings be used with?
These fittings are suitable for use in electrical circuits up to 1,000 V.
What are the ingress protection ratings?
The fittings offer UL Listed Type 3, 3R, 4, 6, 12, 13 ratings and IEC IP66, IP67, IP68, IP69 ratings.
What materials are used for the fittings?
Trade sizes 3/8 inches to 1 1/4 inches are steel with a Zinc Chromate finish, while 1 1/2 inches to 6 inches are malleable iron with a Zinc Chromate finish.
What types of fitting bodies are offered?
The fittings are available in straight, 45°, and 90° body configurations, all with NPT threads.
What trade sizes are available for these fittings?
These fittings are available in trade sizes from 3/8 inches to 6 inches (12mm to 153mm).
What is the operating temperature range?
The general operating temperature range is -20 to +105°C (-4 to +221°F) for UL/CSA, and -25 to +105°C (-13 to +221°F) for IEC/CE.
What are the primary certifications for these fittings?
These fittings meet UL 514B, CSA C22.2 No. 18.3, and IEC 61386-1, -23 requirements for liquid-tight fittings. They also conform to RoHS.
What are the primary certifications for these fittings?
These fittings meet UL 514B, CSA C22.2 No. 18.3, and IEC 61386-1, -23 requirements for liquid-tight fittings. They also conform to RoHS.
How to Install T&B Liquidtight Connectors
This guide provides step-by-step instructions for the proper installation of T&B liquidtight flexible metallic conduit connectors, ensuring high performance and reliability in electrical installations.
Estimated time: 30m
Tools needed:
Hacksaw, Power band saw, Metal jig, Smooth jaw wrench, Hand protection, Eye protection
Supplies needed:
Liquidtight flexible metallic conduit, T&B Liquidtight connector, T&B 140 series locknuts (optional), T&B 5260 series sealing gaskets (optional), PVC cement (optional)
- Review Safety Information and Disconnect Power
Before starting, read and understand all instructions and safety information. Disconnect power to the electrical system to prevent electric shock. Wear hand and eye protection. Ensure installation is performed by a qualified electrician in accordance with national and local electrical codes.
- Prepare the Flexible Conduit
Cut the flexible metallic conduit with a clean, square end. Use a metal jig, a sharp hacksaw with a 32 Tooth/inch blade, or a power band saw with a 24-32 Tooth/inch wavy set blade operating at no more than 400 feet per minute. Do not use an abrasive wheel for cutting the conduit.
- Assemble the Connector Components
For 5000, 7000, 9000 series, and PVC coated 3300 series connectors, slide the gland nut onto the conduit, then slide on the nylon sealing ring, and finally thread in the Safe Edge™ Cone. For PVC coated connectors, tighten with a smooth jaw wrench; if gouging occurs exposing metal, apply PVC cement. For knockout applications, use T&B® 140 series locknuts and 5260 series sealing gaskets (purchase separately). For 7000 and 9000 series, order the locknut separately.
- Mount the Connector to the Knockout Box
Insert the connector body through the knockout hole in the box wall. Position the 'Box side' of the connector correctly on the outside of the box. For 5365 to 5370 series, ensure the captive 'O' ring is correctly positioned. For Chase® connector assemblies, the Chase® Nipple goes inside the knockout. Achieve lock-up by tightening the Chase® Nipple to the body or by turning the body onto the Chase® Nipple.
- Tighten the Gland Nut and Locknut
Securely tighten the gland nut to the connector body to fasten the conduit. Refer to the provided torque table for the specific tightening torque based on the fitting's trade size (e.g., 3/8" requires 200 lb.-in., 1/2" requires 300 lb.-in., 1" requires 700 lb.-in.). Ensure the locknut is also securely tightened to the box wall.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.