ABB Installation Products 35PCJ1M1330 35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786653256
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Single-piece molded elastomer housing for simplified installation
- Accommodates cable insulation diameters from 1.370 to 1.630 inches
- Rated for 500 AWG stranded aluminum conductors
- 200kV BIL impulse withstand and 69kV AC withstand capability
- Fully shielded, fully submersible design for direct burial or vault installation
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 500 kcmil |
Connection | Compression |
Connection Type | Compression Lug |
Current Rating | 35 kA (short-time) |
Insulation | Yes |
Material | Aluminum |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Series | 35PCJ1M1330 |
Size | Cable Insulation Diameter 1.370 inch to 1.630 inch |
Size | 1.370-1.630 inch (cable insulation diameter) |
Size | 14-3/8 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.7500 L |
Package Weight (Metric) | 0.7940 kg |

35PCJ1M1310
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Solid 500.
35PCJ1M2310
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Solid 500.
35PCJ1M2330
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Stranded 500.
35PCJ1N1310
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Conductor. Conductor Size AWG Solid 500.
35PCJ1N1360
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Conductor. Conductor Size AWG Solid 750.
35PCJ1N1410
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Conductor. Conductor Size AWG Stranded 1000.
25PCJ1N2410
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Copper Conductor. Conductor Size AWG Stranded 1000.
25PCJ2-DP0597069
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. DP0597059.Frequently Asked Questions
What is the overall length of a 15PCJ1FX joint?
The overall length (Dimension A) for a 15PCJ1FX Style 1 joint is 10 1/4 inches.
What is the minimum cable insulation diameter for 35PCJ-1?
For the 35PCJ-1, the minimum cable insulation diameter is 0.850 inches, corresponding to symbol H.
What is the short-time current rating for PCJ joints?
The short-time current rating for PCJ power cable joints is equal to that of the cable rating, up to 35 kA.
What standards do PCJ joint components meet?
The shield design meets IEEE 592 standard, and the connectors meet ANSI 119.4 Class A and Class 3 ratings.
Can copper connectors be used with aluminum conductors?
No, copper compression connectors are suitable for splicing copper conductors to copper conductors only and should NOT be used on aluminum conductors.
What is the AC withstand voltage for a 25 kV PCJ joint?
A 25 kV class PCJ joint has an AC withstand at 60 Hz for 1 minute of 52 kV.
What are the installation environments for PCJ joints?
These joints provide a permanent, fully shielded, fully submersible splice suitable for direct-burial, underground vault, and overhead applications.
What is the BIL impulse withstand for a 35 kV PCJ joint?
For a 35 kV class PCJ joint, the BIL impulse withstand (1.2 x 50 μsec. wave) is 300 kV.
What is the continuous current rating of PCJ joints?
The continuous current rating for PCJ power cable joints is equal to that of the cable rating.
What is the maximum conductor size for PCJ power cable joints?
Elastimold PCJ power cable joints can accommodate conductor sizes up to 1250 kcmil.
How to Install the 35PCJ1 Series Straight Joint
This guide provides step-by-step instructions for the permanent, fully shielded, and submersible installation of the 35PCJ1 series straight joint for aluminum or copper conductor, wire shielded cables.
Estimated time: 2h
Tools needed:
Cable Stripping Tool, Measuring Tape, Wire Brush, Crimping Tool, T&B WT3D Tool (for 35kV cable ties), Utility Knife
Supplies needed:
35PCJ1 Series Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Appropriate Connector (for grounding wires), DELTECt Cable Ties (TYD5135, for 35kV only), #14 AWG Copper Wire (or equivalent, if shield wires are smaller), Inhibitor (for aluminum conductors)
- Perform Initial Safety Checks and Cable Preparation
DANGER: Ensure all apparatus is de-energized before beginning installation. Inspect all package contents and components for completeness, damage, and compatibility with the cable. Overlap both cables and cut them to 12 inches (305mm) from the joint centerline. Remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm) where applicable. Fold back the shield wires and then cut both cables at the joint centerline.
- Prepare Cable 1 and Store Joint Housing
Taper the edge of Cable 1's insulation shield from 1/2 inch (13mm) to 1-1/2 inches (38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Carefully slide the joint housing onto Cable 1, pushing it up to the shield wires. Then, carefully remove the cable insulation and the insulation shield from both cables, ensuring not to cut or nick the cable insulation or conductor.
- Install and Crimp the Splice
If conductors are aluminum, wire-brush them thoroughly and immediately insert them into the splice. Crimp the splice according to its provided recommendations. Wipe off any excess inhibitor. Remove any sharp protrusions or burrs generated during crimping, ensuring all metal chips and filings are cleared from the splice and joint assembly area before proceeding. Clean the cables where indicated and lubricate them in the direction of the arrows to create a build-up or ramp of lubricant at the edge of the insulation shield.
- Complete Joint Assembly and Grounding
Slide the joint housing into its final position, ensuring proper placement by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield. For 35kV installations ONLY: Install two DELTECt Cable ties on each end of the cable entrance, approximately 1/4 inch (6mm) from the splice edge, with the second tie 1/4 inch from the first and locking heads offset. Use a T&B WT3D tool to tighten and trim the ties. Remove and discard the yellow pin from the joint grounding eye. Retrain the shield wires and secure them to the ends of the joint. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and remaining shield wires using an appropriate connector. Finally, reconstruct the cable jacket (where applicable) over both cables and the joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.