ABB Installation Products 25PCJ1N2410 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786661718
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25kV Voltage Rating
- Single-Piece Housing for simplified installation
- Accommodates Cable Insulation Diameter: 1.515" - 1.780"
- Designed for 1000 AWG Stranded Copper Conductors
- ABB Installation Products Quality
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 1000 kcmil |
Connection | Compression |
Insulation | Yes |
Material | Copper |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Series | Style 1 |
Size | 15-3/4 inch long |
Size | 1.515 inch to 1.780 inch |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 4.5000 L |
Package Weight (Metric) | 2.0410 kg |

25PCJ1M1400
25 kV, Power Cable Joint, Style 1 - 14-3/8 X 2-25/32 inches, Cable Insulation Diameter - 1.370-1.630 inches, Aluminum Connector, Conductor Size - 1000 kcmil.
25PCJ2-DP0597069
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. DP0597059.
35PCJ1M1310S
35kV Power Cable Joint Style 1, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 400 /Compacted Solid 450 /mmSquared Compact 240. Cold Shrinkable Jacket Seal included.
35PCJ1M1380
35kV Power Cable Joint Style 1, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 700/750, Solid 900.
35PCJ1N1360S
35kV Power Cable Joint Style 1, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400. Cold Shrinkable Jacket Seal included.
35PCJ1M1400
35 kV, Power Cable Joint, Style 1 - 14-3/8 X 2-25/32 inches, Cable Insulation Diameter - 1.370-1.630 inches, Aluminum Connector, Conductor Size - 1000 kcmil.
35PCJ1N1330
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Conductor. Conductor Size AWG Stranded 500.
35PCJ1N1330-S
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Conductor. Conductor Size AWG Stranded 500. Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
Can copper connectors be used on aluminum conductors?
No, copper compression connectors are suitable for copper-to-copper connections only and should not be used on aluminum conductors.
What are Elastimold PCJ power cable joints?
They are permanently crimped connectors inside EPDM rubber housings, designed for splicing power cables. They offer proven reliability and versatility for various installations.
What are the available voltage classes?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
What conductor types are compatible?
These joints can be used with both copper and aluminum conductors, accommodating a wide range of sizes up to 1250 kcmil.
What are the two styles of PCJ joints?
Style 1 is for straight splicing of two similar cables. Style 2 uses separate cable adapters for transition splicing between different cable sizes.
Where can PCJ power cable joints be installed?
They are suitable for direct-burial, underground vault, and overhead applications, providing a permanent, fully shielded, and submersible splice.
What is the maximum conductor size supported?
Elastimold PCJ power cable joints can be used with conductors up to 1250 kcmil.
What is the continuous current rating?
The continuous current rating for PCJ power cable joints is equal to that of the cable rating.
What is the short-time current rating?
The short-time current rating is equal to that of the cable rating, up to 35 kA.
What standards do PCJ joints meet?
The shield design meets IEEE 592 standard, and the connectors meet ANSI 119.4 Class A and Class 3 ratings.
How to Install the 15/25/35PCJ1 Series Cable Joint
This guide provides detailed instructions for installing the 15/25/35PCJ1 series permanent, fully shielded, and submersible cable joint. It is designed for aluminum to aluminum and/or aluminum to copper conductors on wire shielded cables.
Estimated time: 2h
Tools needed:
Wire brush, Crimping tool, Cable jacket removal tool, Cable insulation removal tool, Insulation shield removal tool, Measuring tape, Burr removal tool, T&B WT3D tool (recommended for 35kV cable ties)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Connector (user supplied for grounding), #14 AWG copper wire or equivalent (if shield wires are smaller than #14 AWG), DELTECt Cable ties TYD5135 (for 35kV only)
- Ensure Safety and Prepare Components
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. This product should be installed only by competent personnel trained in high voltage electrical equipment safety. Inspect all parts for damage, rating, and compatibility with mating parts. Check contents of the package to ensure they are complete and undamaged. Have all required tools at hand and maintain cleanliness throughout the procedure.
- Prepare Cables for Splicing
Overlap both cables and cut them to 12 inches (305mm) from the center line of the joint to ensure sufficient length of shield wires. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires. Finally, cut both cables at the center line of the joint.
- Prepare Cable 1 and Store Housing
Taper the edge of Cable 1 at least 1/2 inch (13mm) to no greater than 1-1/2 inches (38mm). Clean and lubricate the insulation shield of Cable 1. Lubricate the inside bore of the joint housing on both ends. Slide the housing onto Cable 1, pushing it up to the shield wires.
- Prepare Cables for Splice Installation
Carefully remove the cable insulation and then the insulation shield from both cables according to the dimensions provided in the document (e.g., 'Y' and 'X' dimensions for 500-750 MCM and 1000 MCM conductors). WARNING: DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR during this process.
- Install the Splice
If conductors are aluminum, wire-brush them and immediately insert them into the splice. Check the dimension against the 'Max Check Before' table. Crimp the splice following the recommendations provided with it. Wipe off all excess inhibitor. Check the distance between cable insulations against the 'Max Check After' table; redo assembly if it exceeds the maximum. Remove any sharp protrusions or burrs generated during crimping and ensure all metal chips/filings are removed from the splice and joint assembly area. Clean cables where indicated and lubricate in the direction of arrows to provide a build-up of lubricant at the edge of the insulation shield.
- Complete Joint Assembly and Grounding
Slide the housing into its final position, ensuring proper placement by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield. For 35kV ONLY: Install two DELTECt Cable ties on each end of the cable entrance, approximately 1/4 inch (6mm) from the edge of the splice and then 1/4 inch from the first with offset locking heads. Remove and discard the yellow pin from the joint grounding eye. Retrain the shield wires and secure them to the ends of the joint. Insert one of the shield wires from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and remaining shield wires using an appropriate connector. Finally, reconstruct the cable jacket (where applicable) over both cables and the joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.