Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 200 Amp current rating
- 25,000 Volt (25KV) operating voltage
- 3-point junction configuration
- Load break capability for safe switching
- Manufactured by ABB Installation Products
Specifications
Amperage Rating | 200 A |
Application | Designed for subsurface, vault or padmount applications and can be used for sectionalizing, looping, tapping, and equipment bypass |
Color | Black |
Connection Type | Load Break |
Current Rating | 200 A |
Environmental Conditions | Fully Shielded, Fully Submersible |
Insulation | True |
Material | Housing - Molded Rubber |
Poles | 3 |
Standard | ANSI/IEEE Standard 386 |
Type | Loadbreak 3-Way Junction |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 14.6000 L |
Package Weight (Metric) | 6.6230 kg |

YFC 1/0
Copper Flood-Seal Street and Highway Lighting Compression Fuse and Disconnect Kits - YY-Type, fused, conductor size main 1/0, tap 14-6
SLK 102 M
Flood-Seal Street and Highway Lighting Mechanical Fuse and Disconnect Kits, In-Line Variable-Range, fused, conductor range stranded 1/0-2, and solid 2-14
SDK 2
Copper Flood-Seal Street and Highway Lighting Compression Non-Fused Kits - In-Line, Single Housing, wire size stranded 4 and solid 2
BY 320 C
Aluminum Insulated Y-Type Mechanical Streetlight Connector - Three Conductor, Wire Range #14-2/0 CU-AL, 1-27/32 inch x 3/4 inch x 9/16 inch with (3) 7/16-20 UNF-2B Holes on one side that intersects with (3) 31/64 inch Diameter through holes, includes Gray PVC Boot with dimensions 1-29/32 inch x 2-5/8 inch x 1-1/32 inch and Lubricant.
SDT 2
Copper Flood-Seal Street and Highway Lighting Compression Non-Fused Kits - In-Line, Twin Housing, wire size stranded 2
DYC 4
Flood-Seal Street and Highway Lighting Mechanical Fuse and Disconnect Kits Y-Type with Crimped Lug Connectors, non-fused, wire size stranded 4, copper run, copper tap fused, installing dies 5/16,8,TP,29Frequently Asked Questions
What is the product model number?
The product model number is 274J3. It is a 25kV 200A Loadbreak 3-Way Junction with a stainless steel bracket.
What products are compatible with the ELASTIMOLD junction?
It provides mating for other Elastimold® loadbreak type products, including 25kV Family of Elbow Connectors, 370GLR Grounding Elbow, 370TR Test Rod, and 273/274DRG Insulated Cap.
What is the fault close rating for the junction?
The fault close rating is 10kA Sym for 10 Cycles Momentary & Fault Close.
What is the impulse withstand rating (BIL)?
The impulse withstand rating (BIL) is 125kV. This is based on a 1.2 x 50 microsecond wave.
How do I order the 274J3 with "U" style mounting straps?
To order the junction with "U" style mounting straps, add "-5" at the end of the catalog number.
What is included in the 274J3 kit?
Each kit contains one basic molded junction (274J3), two protective shipping caps (2701-41), two tubes of lubricant (82-08), and one installation instruction (IS-0798).
What type of mounting hardware is included?
The junction includes mounting hardware for flat or curved mounting positions. Universal brackets accommodate curved or flat surfaces and provide tilt mounting angles from 0° to 90° in 15° increments.
What standards does the 274J3 junction meet?
The 274J3 junction meets ANSI/IEEE Standard 386, Latest Revision.
What is the continuous and loadbreak current rating?
The continuous and loadbreak current rating for the junction is 200 Amp. It is rated for 200-ampere loadmake/loadbreak operation.
What is the operating voltage for the 274J3 junction?
The operating voltage is 15.2kV Phase-to-Ground. The maximum phase-to-phase voltage is 26.3kV.
How to Install the Elastimold 274J3(1) Loadbreak Junction
This guide provides step-by-step instructions for the universal mounting and initial setup of the Elastimold 274J3(1) Two-, Three-, or Four-Point Loadbreak Junction on flat or curved surfaces. Ensure all apparatus are de-energized before beginning installation.
Estimated time: 45m
Tools needed:
Wrench/Socket set, Screwdriver, Marker or Pencil, Wire strippers, Cleaning cloth
Supplies needed:
Elastimold 274J3(1) Loadbreak Junction (assembled with back plate), Universal mounting brackets (2) with hardware, Lubricant (supplied), Mounting bolts (user supplied, 17/32 inch / 13mm diameter), Grounding wire (No. 10 Solid to No. 1 Stranded), Mating products (e.g., elbow connectors, insulated caps), Elastimold 273DR Insulated Cap (if interfaces are unused)
- De-energize Apparatus
Before beginning installation, ensure all apparatus connected to or near the junction are completely de-energized. Failure to do so can result in serious or fatal injury.
- Inspect and Prepare Components
Check the package contents to ensure all parts are complete and undamaged. Verify that all components, including the junction and mating products, fit properly. Have all required tools and supplies ready.
- Position and Mark Mounting Brackets
Loosely attach the universal mounting brackets to the junction's back plate. Position the assembled junction against the desired mounting surface (flat or curved), adjust the brackets for proper alignment, and mark their exact location on the wall.
- Mount Brackets to Surface
Detach the universal mounting brackets from the junction back plate. Securely mount the brackets to the wall using user-supplied bolts (17/32 inch / 13mm diameter) at the marked locations. You may invert one or both brackets to adjust the distance between bolt centers if needed.
- Fasten Junction to Brackets
With the universal mounting brackets securely installed, fasten the junction (with its back plate attached) to the mounted brackets. Ensure that the parking stands on the junction are in the upright position.
- Adjust and Secure Mounting Angle
Adjust the junction's mounting angle to the desired position (0 to 90 degrees above or below horizontal in 15-degree increments). Once positioned, securely tighten all bolts to prevent any movement during operation.
- Ground the Back Plate
Connect a grounding wire (No. 10 Solid to No. 1 Stranded) to the provided grounding lug on the back plate. Ensure the connection is secure and the junction is properly grounded.
- Prepare and Install Mating Products
Thoroughly wipe the bushing interface clean of any contaminants. Apply the supplied lubricant to the bushing interface. Install the mating products (e.g., elbow connectors or insulated caps) to the bushing inserts, following their specific installation instructions.
- Verify Mating Product Seating
Confirm that the mating products are fully seated. Complete assembly is indicated by no portion of the yellow band being visible when viewed from the side.
- Install Insulated Caps on Unused Interfaces
If any operating interfaces are not utilized, install an Elastimold 273DR insulated cap on each unused interface before energizing the circuit. Do NOT use protective shipping covers for this purpose, as they are not insulated.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.