
Contact for Pricing
Overview
- 25kV voltage rating, 200 Amp continuous current capacity
- DeadBreak to LoadBreak transition for safe disconnection under load
- Peroxide-cured EPDM insulation and jacket for environmental resistance
- All-copper current path for low electrical resistance and heat generation
- Hex-broach design for torque-controlled installation and ground wire provision
Specifications
Amperage Rating | 200 A |
Insulation | EPDM Rubber |
Material | EPDM-Rubber |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Bushing Adapter |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656CETP-J0270
25kv, 600 Amp Series, Deadbreak Combo-T. Connector Elbow with Intergral 200 Amp Loadbreak Tap Plug with Test Point. Cable Insulation Diameter 0.980 to 1.180 inches (24.9-30.0mm). Aluminum Conductor Material, Conductor Code 270 - 4/0 Stranded/Compressed or 250 Solid/Compact. No Sealing Kit.
252LR-B2035-S
12/20 24kV, 250 Amp, Deadbreak, Elbow Connector with Test Point, with Sealing Kit, Cable Insulation Diameter - 16.13 mm - 22.90 mm, Copper Compression Lug, Conductor Size 35mm. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide. IEC Standard.
262LR-E2250-S
25kV, 200 Amps, Loadbreak Elbow, Cable Insulation Diameter 1.090-1.310 inches, (27.69-33.27 mm), Copper Conductor, Conductor Size 2/0 Stranded/Compressed, 3/0 Solid/Compact. With Test Point. Kit Contains Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Lubricant, Installation Instruction Sheet and Crimp Chart. S - Cold Shrinkable Jacket Seal.
162A4-C5270
15kV, 200 Amp, Loadbreak Elbow with Bushing Insert Kit with Test Point, Cable Insulation Diameter C - 0.805 to 1.060 inch (20.45-26.92mm). Bi-Metal Compression Lug, Conductor Size 270 -4/0 Stranded/Compressed or 250 kcmil Solid/Compact.
252LR-B2050
12/20 24kV, 250 Amp, Deadbreak, Elbow Connector with Test Point, No Sealing Kit, Cable Insulation Diameter - 16.13 mm - 22.90 mm, Copper Compression Lug, Conductor Size 50mm. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide. IEC Standard.
M465LR-P2330
35kV, 630 Amp, Deadbreak Elbow, No Test Point, IEC-IEEE, No Sealing Kit. Cable Insulation Diameter 1.725 to 1.935 inch, Copper Lug, Wire Range 500 kcmil Stranded/Compressed or 600 kcmil Solid Compact or 250/300 mm2. 10.36 inch (264.1mm) x 13 inch (330.2mm) from Bottom to Center of Bushing. Includes Elbow Connector Housing, Compression Lug, Stud, Insulated Plug with Cap, Lubricant, Cable Adapter, Installation Instructions and Crimp Chart.
M465LR-N-2290
35kV, 630 Amp, Deadbreak Elbow, No Test Point, IEC-IEEE, No Sealing Kit. Cable Insulation Diameter 1.515 to 1.780 inch, Copper Lug, Wire Range 300 kcmil Stranded/Compressed or 350 kcmil Solid Compact or 150 mm2. 10.36 inch (264.1mm) x 13 inch (330.2mm) from Bottom to Center of Bushing. Includes Elbow Connector Housing, Compression Lug, Stud, Insulated Plug with Cap, Lubricant, Cable Adapter, Installation Instructions and Crimp Chart.
M465LR-L-2230
35kV, 630 Amp, Deadbreak Elbow, No Test Point, IEC-IEEE, No Sealing Kit. Cable Insulation Diameter 1.180 to 1.465 inch, Copper Lug, Wire Range 1 Stranded/Compressed or 1/0 Solid Compact or 50 mm2. 10.36 inch (264.1mm) x 13 inch (330.2mm) from Bottom to Center of Bushing. Includes Elbow Connector Housing, Compression Lug, Stud, Insulated Plug with Cap, Lubricant, Cable Adapter, Installation Instructions and Crimp Chart.Frequently Asked Questions
What is the momentary and fault close rating?
The 2701DLA has a 10kA Symmetrical 10 Cycles Momentary & Fault Close rating.
What is the corona extinction voltage?
The corona extinction voltage for the 2701DLA is 19kV AC at 3pC sensitivity.
What is the DC 15-minute withstand voltage?
The 2701DLA has a 78kV DC 15-minute withstand rating.
What is the AC one-minute withstand voltage?
The 2701DLA has a 40kV AC one-minute withstand rating.
What items are included in the 2701DLA kit?
Each kit contains one 2701DLA Bushing Insert, one protective shipping cap (2701-APC-1), one lubricant (82-08), and one Installation Instruction (IS-1243).
Does the 2701DLA have a provision for a ground wire?
Yes, the 2701DLA bushing adapter includes a provision for a ground wire connection.
What is the 2701DLA bushing adapter designed for?
The 2701DLA bushing adapter converts 180 series deadbreak epoxy bushings to a loadbreak bushing. It serves as an interface for connecting shielded cable to various apparatus.
What is the maximum operating voltage for the 2701DLA?
The maximum phase-to-ground operating voltage for the 25kV class 2701DLA is 15.2kV. The maximum phase-to-phase voltage is 26.3kV.
What is the continuous current rating of the 2701DLA?
The 2701DLA bushing adapter has a continuous and loadbreak current rating of 200 Amps.
What industry standards does the 2701DLA meet?
The 2701DLA bushing adapter meets ANSI/IEEE Standard 386, Latest Revision.
How to Install the 2701DLA Deadbreak to Loadbreak Adapter
This guide provides step-by-step instructions for safely installing the 2701DLA Deadbreak to Loadbreak Adapter, converting 180 series deadbreak epoxy bushings to loadbreak bushings. Ensure all apparatus is de-energized before beginning installation.
Supplies needed:
DLA Adapter, Bail Prepack (4 Hook Bolts, 4 Wing Nuts, 1 Bail Plate), Silicone Lubricant, Nylon Rod, Wire (No. 14 AWG Copper or equivalent), Suitable connector (for grounding)
- De-energize Apparatus and Perform Initial Checks
DANGER: All apparatus must be de-energized during installation or removal of parts. Inspect the contents of the package to ensure they are complete and undamaged. Check all components for proper fit with the cable and/or mating products. Read the entire installation instructions before starting.
- Install Adapter onto Apparatus Bushing
Inspect the apparatus bushing to ensure it is dry and free from all contaminants. Remove the protective shipping cover from the adapter. Lubricate the apparatus bushing and adapter interface with the supplied silicone lubricant. DO NOT SUBSTITUTE other lubricants. Insert the supplied nylon rod into the adapter interface to exhaust trapped air during assembly. Push the adapter firmly onto the apparatus bushing.
- Remove Nylon Rod
Carefully remove the nylon rod from the adapter by pulling it in the direction shown in the diagram (away from the bushing).
- Connect Grounding Wire
Insert one end of a piece of wire, with ampacity at least equivalent to No. 14 AWG Copper, through the grounding eye and twist to make a small loop, ensuring not to damage the eye. Connect this wire to ground using a suitable connector.
- Assemble Hold Down Bail
Assemble the bail plate, the four hook bolts, and the four wing nuts to hold the adapter in place. Hand tighten the wing nuts, keeping the bail plate parallel to the bushing mounting surface. The bail plate and hook bolts secure the adapter during elbow assembly/disassembly and provide a ground for the adapter's semi-conductive jacket.
- Prepare Loadbreak Interface
Clean and lubricate the loadbreak interface of the adapter with the supplied lubricant. Install the mating products (e.g., elbow connector, insulated cap, or grounding elbow) to the bushing interface following their respective instructions. If the adapter loadbreak interface is not immediately mated, replace the protective cap. Do NOT energize or submerge the adapter with the protective cap on.
- Verify Final Assembly
Confirm that the assembly of an insulated cap or elbow is complete by ensuring no portion of the red (for 1601DLA) or blue (for 2701DLA) interface sleeve is visible when viewed from the side.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.