Authorized ABB Distributor (Installation Products)
ABB - Installation Products 25PCJ1H2220 - 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Copper Conductor. Conductor Size AWG Stranded #2/Solid #1.

ABB Installation Products 25PCJ1H2220 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…

UPC: 783786822836


Documents & Media
BrochureInstallation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

This joint is engineered to accommodate cable insulation diameters ranging from 0.850 inches to 1.050 inches, identified by the 'H' symbol in the insulation diameter range. It is specifically designed for use with copper conductors, supporting both stranded AWG #2 and solid AWG #1 conductor sizes. The single-piece housing construction simplifies installation and ensures a robust seal, crucial for protecting the cable splice from environmental factors and electrical interference in medium-voltage power distribution systems. Key specifications include: * **Voltage Rating:** 25kV * **Cable Insulation Diameter Range:** 0.850" (min) to 1.050" (max) * **Conductor Type:** Copper * **Conductor Size:** AWG #2 Stranded / AWG #1 Solid * **Housing Style:** Style 1, Single Piece * **Catalog Number:** 25PCJ1H2220 This product is a vital component for utility companies, industrial facilities, and other organizations requiring secure and long-lasting power cable terminations. The UNSPSC code for this product is 39121452, classifying it under Electrical power distribution equipment. Ensure proper application within its specified voltage and conductor size parameters for optimal performance and safety. The ABB 25PCJ1H2220 provides a reliable solution for 25kV cable jointing, emphasizing functionality and dependability in power transmission and distribution networks. The product includes the power cable joint housing, a connector, lubricant tube, installation instructions, and a crimp chart.
  • 25kV voltage rating for medium-voltage applications
  • Style 1 single-piece housing for simplified installation and robust sealing
  • Designed for cable insulation diameters from 0.850 to 1.050 inches
  • Suitable for copper conductors, including AWG #2 stranded and AWG #1 solid
  • Includes housing, connector, lubricant, installation instructions, and crimp chart

Specifications

Application
For Direct Burial, Vault, Submersible and Other Severe Service Applications
Color
Black
Conductor Range
#2 STR AWG , #1 SOL AWG
Connection
Compression
Insulation
Yes
Material
Copper
Material
EPDM Rubber
Number Of Conductors
2
Series
25PCJ1H
Series
25PCJ1
Series
Style 1
Size
0.850-1.050 inch insulation diameter, AWG #2 stranded / #1 solid
Size
0.850-1.050 inch
Size
0.850 inch to 1.050 inch
Size
14-3/8 inch long
Special Features
Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable
Standard
IEEE Standard 404
Type
Power Cable Joint
Voltage Rating
25 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Copper Conductor. Conductor Size AWG Stranded #2/Solid #1.

25PCJ1G2220

25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Copper Conductor. Conductor Size AWG Stranded #2/Solid #1.
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Solid 500.

15PCJ1M1310

15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Solid 500.
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Solid 350.

15PCJ1K2290

15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Solid 350.
28kV Power Cable Joint Style 1 with Single Piece Housing for Canada, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 500.

28PCJ1L1330

28kV Power Cable Joint Style 1 with Single Piece Housing for Canada, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 500.
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Solid 500.

25PCJ2M2310

25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Solid 500.
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 350. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.

15PCJ2L1300-J1270

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 350. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Solid 500.

15PCJ1L2310

15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Solid 500.
69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 4, Housing Size 5, Connector type Aluminum

69TCJS4-5-1

69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 4, Housing Size 5, Connector type Aluminum

Frequently Asked Questions

What is the insulation diameter range for this cable joint?

This ABB 25kV power cable joint is designed to accommodate cable insulation diameters ranging from 0.850 inches to 1.050 inches.

What conductor types does the 25PCJ1H2220 support?

The 25PCJ1H2220 supports copper conductors, specifically AWG #2 stranded and AWG #1 solid.

What is the voltage rating of this ABB cable joint?

This ABB power cable joint is rated for 25kV applications.

What is the manufacturer of the 25PCJ1H2220 cable joint?

The manufacturer of the 25PCJ1H2220 is ABB - Installation Products.

How to Install the 15/25/35PCJ1 Series Straight Joint

This guide provides detailed instructions for the permanent, fully shielded, and submersible installation of the 15/25/35PCJ1 series straight joint. It covers preparation, splicing, and final assembly for aluminum to aluminum and/or aluminum to copper conductor, wire shielded cables. Ensure all apparatus is de-energized before beginning.

Estimated time: 2h

Tools needed:

Wire brush, Cable knife/stripper, Crimping tool, Deburring tool or file, T&B WT3D tool (recommended for 35kV cable ties)

Supplies needed:

Joint Housing (15/25/35PCJ1), Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Appropriate connector (for grounding wires), DELTEC Cable ties (TYD5135, for 35kV only), #14 AWG copper wire (or equivalent, if shield wires are smaller)

  1. Safety and Initial Inspection

    Before starting, ensure all apparatus is de-energized. Inspect the package contents for completeness and damage. Verify all components fit properly with the cable and mating products. Have all required tools ready and maintain cleanliness throughout the procedure. Failure to follow safety instructions can result in serious injury or death.

  2. Prepare Cables for Joint Centerline

    Overlap both cables and cut them to 12 inches (305mm) from the joint's centerline to ensure sufficient shield wire length for rejoining. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires. Finally, cut both cables precisely at the joint's centerline.

  3. Prepare Cable 1 and Store Housing

    Taper the edge of Cable 1 from 1/2 inch to 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Slide the housing onto Cable 1, pushing it up to the shield wires.

  4. Prepare Cables for Splice Installation

    Carefully remove the cable insulation and then the insulation shield from both Cable 1 and Cable 2. Refer to the document's 'X' and 'Y' dimensions based on conductor size (500-750 MCM or 1000 MCM). DO NOT cut or nick the cable insulation or conductor during this process.

  5. Install and Crimp the Splice

    If conductors are aluminum, wire-brush them thoroughly and immediately insert them into the splice. Check the dimension against the 'Max Check Before' table provided in the documentation; if it exceeds, redo the assembly. Crimp the splice following its specific recommendations. Wipe off any excess inhibitor. Check the distance between cable insulations against the 'Max Check After' table; if it exceeds, redo the assembly. Remove any sharp protrusions or burrs from crimping and ensure all metal chips/filings are cleared from the splice and joint area.

  6. Clean and Lubricate for Housing Assembly

    Clean the cables where indicated. Lubricate the cables in the direction of the arrows to create a build-up or ramp of lubricant at the edge of the insulation shield, preparing for the housing slide.

  7. Complete Joint Housing Assembly

    Slide the joint housing into its final position. Ensure proper positioning by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield. For 35kV applications ONLY, install two DELTEC Cable ties (TYD5135) on each end of the cable entrance, 1/4 inch from the splice edge and 1/4 inch from the first, with offset locking heads. Use the T&B WT3D tool to tighten and trim. Also for 35kV, remove and discard the yellow pin from the joint grounding eye.

  8. Connect Grounding and Reconstruct Jacket

    Retrain the shield wires and secure them to the ends of the joint. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use a separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and the remaining shield wires using an appropriate connector. Finally, reconstruct the cable jacket (where applicable) over both cables and the joint housing.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.