ABB Installation Products 25PCJ1H1240 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786663392
Contact for Pricing
Minimum Qty: 15
Multiplier: 15
*Contact for lower quantities*
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25kV Voltage Rating
- Style 1 Straight Splice
- Accommodates 0.850-1.050 inch Cable Insulation Diameter
- Supports 1/0 AWG Stranded and 2/0 AWG Solid Aluminum Conductors
- Fully Shielded and Fully Submersible Design
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 1/0 STR AWG , 2/0 SOL AWG |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 14-3/8 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.6700 L |
Package Weight (Metric) | 0.7580 kg |

25PCJ2J1240-H1240
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
35PCJ1N
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch.
15PCJ2H127P-G124P
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. With Customer Specific Modifications
15PCJ1G2220
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Copper Conductor. Conductor Size AWG Stranded #2/Solid #1.
35PCJ1Q1410
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.900 inch to 2.120 inch. Aluminum Conductor. Conductor Size AWG Stranded 1000.
25PCJ1L1270
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
35PCJ1J1240
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
15PCJ1H2290
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Copper Conductor. Conductor Size AWG Solid 350.Frequently Asked Questions
Can copper connectors be used with aluminum conductors?
No, copper compression connectors included in some kits are suitable for splicing copper conductors to copper conductors only. They should not be used on aluminum conductors.
What are the main applications for PCJ power cable joints?
PCJ power cable joints are suitable for straight splicing of similar cables or transition splicing of different cable sizes. They can be installed in direct-burial, underground vault, and overhead applications.
What types of cables can PCJ power cable joints splice?
PCJ power cable joints can splice two similar cables or transition splice different cable sizes up to 1250 kcmil. They are compatible with copper or aluminum conductors.
What voltage classes are available for PCJ joints?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
What are the two styles of PCJ power cable joints?
Style 1 is for straight splicing of two similar cables. Style 2 includes separate cable adapters for transition splicing between two different cable sizes.
What cable types are compatible with PCJ power cable joints?
They are designed for UD cable with concentric neutral and extruded insulation shielding. They also work with fabric-tape shielded or lead-jacketed cables using proper adapters.
Which safety standards do PCJ power cable joints meet?
The shield design meets IEEE 592 standard. The connectors meet ANSI 119.4 Class A and Class 3 ratings.
What is the continuous current rating of PCJ joints?
The continuous current rating for PCJ power cable joints is equal to that of the cable rating.
What is the short-time current rating for PCJ joints?
The short-time current rating for PCJ power cable joints is equal to that of the cable rating, up to 35 kA.
What conductor materials are supported by PCJ joints?
PCJ joints support copper or aluminum conductors. Kits are available with aluminum connectors for aluminum-to-aluminum or aluminum-to-copper, and copper connectors for copper-to-copper.
How to Install the ABB 15/25/35PCJ1 Series Straight Joint
This guide provides detailed instructions for installing the ABB 15/25/35PCJ1 series straight joint, a permanent, fully shielded, and submersible solution for connecting wire shielded cables with aluminum or copper conductors. Ensure all apparatus is de-energized before beginning.
Estimated time: 1h 30m
Tools needed:
Cable cutting tool, Wire strippers, Wire-brush (for aluminum conductors), Crimping tool, T&B WT3D tool (recommended for 35kV Deltect cable ties)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), User-supplied connector (for grounding), Deltect Cable ties (TYD5135, for 35kV only), #14 AWG copper wire or equivalent (if shield wires are smaller than #14 AWG)
- Prepare Cables for Joint Centerline
De-energize all apparatus before beginning installation. Overlap both cables and cut them to 12 inches (305mm) from the intended centerline of the joint. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm) from the centerline. Fold back the shield wires on both cables. Finally, cut both cables precisely at the joint centerline.
- Prepare Cable 1 and Store Housing
Taper the edge of Cable 1's insulation from 1/2 inch to 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield of Cable 1. Lubricate the inside bore of the joint housing on both ends. Slide the joint housing onto Cable 1, pushing it up to the shield wires for temporary storage.
- Prepare Cables for Splice Installation
Carefully remove the cable insulation and then the insulation shield from both Cable 1 and Cable 2 to the dimensions specified in the 'X' and 'Y' table provided with the splice. WARNING: Do not cut or nick the cable insulation or conductor during this process.
- Install the Splice
If conductors are aluminum, wire-brush them thoroughly and immediately insert them into the splice. Verify the conductor insertion dimension against the 'Max Check Before' table; if it exceeds the maximum, redo the assembly. Crimp the splice according to the manufacturer's recommendations provided with the splice. Wipe off any excess inhibitor. Check the distance between the cable insulations against the 'Max Check After' table; if it exceeds the maximum, redo the assembly. Remove any sharp protrusions or burrs created during crimping, ensuring all metal chips/filings are removed from the splice and joint assembly area. Clean the cables where indicated and lubricate them in the direction of the arrows to create a build-up or ramp of lubricant at the edge of the insulation shield.
- Complete Joint Assembly
Slide the joint housing into its final position, ensuring proper positioning by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield. For 35kV ONLY: Install two DELTECt Cable ties on each end of the cable entrance, placing the outer ties approximately 1/4 inch from the splice edge and the second ties approximately 1/4 inch from the first, offsetting their locking heads. Use the T&B WT3D tool (not included) to tighten and trim the ties. Remove and discard the yellow pin from the joint grounding eye. Retrain the shield wires and secure them to the ends of the joint as shown in the diagram. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, repeating for Cable 2. If shield wires are smaller than #14 AWG, use a separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and the remaining shield wires using an appropriate user-supplied connector. Reconstruct the cable jacket (where applicable) over both cables and the joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.