ABB Installation Products 252LR-D2120 12/20 (24) kV, 250 Amp, Deadbreak, Elbow Connector with Test Point, No Sealing Kit…
UPC: 075114391092
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 24 kV rated voltage for medium-voltage applications
- 250 Amp continuous current rating
- Deadbreak design with integrated test point for safe testing
- Accommodates cable insulation diameters from 22.61mm to 30.99mm
- Includes copper compression lug for 120mm² conductors, lubricant, and installation accessories
Specifications
Amperage Rating | 250 A |
Application | 12/20 (24) kV |
Color | Black |
Conductor Range | 120 mm2 |
Connection | Compression |
Environmental Conditions | Harsh Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | Robust Stainless Steel Pulling Eye. Dual Grounding Eye Positions. Designed to Remain Fully Operational in Harsh Conditions |
Standard | IEC 60502-4, CEN 629.1 S2 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 15 to 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

252LR-E2120-G
12/20kV (24 kV), IEC 250 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 1.09-1.31 inches (27.48-33.27mm), Copper Lug, Conductor Size 120 mm2. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Standard Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter. Includes Bonding/Grounding Wire. IEC 60502-4, CEN 629.1 S2.
162LR-B5240-CS2089
200 Amp, 15kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. Includes 62 inch Ground Lead Installed Through Grounding Eye Utilizing Rivet.
K656LR-JAC02
15/25kV, 600 Amps, Separable Cable joint Elbow with Test Point, Includes Elbow Connector Housing, Insulated Plug with Cap, Stud, Shear Bolt Lug, Cable Adapter and Lubricant. Cable Insulation Range 0.98 to 1.18 inch. Shear Bolt Lug AC02 Range 4/0 to 500 kcmil Stranded - Compressed - Solid - Compact.
262LR-C2250
28kV, 200 Amps, Loadbreak Elbow Connector with Test Point, No Sealing Kit, .805 inch - 1.060 Inch Cable Insulation Diameter, 2/0 Stranded or Compressed, 3/0 Solid or Compact Wire Size, Copper Compression Lug. Contains Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Tube of Lubricant, Crimp Chart and Installation Instructions.
K655ESA-18-CS2090
Shielded Surge Arrester, ESA Elbow Surge Arrester, 15/25kV, 600 Amp, MCOV KV RMS is 15.30. Any Customer Modifications CS2090 - For AISI 316 Grade Stainless Steel External Components Only.
K151SR-A2250
200 Amp, 15/25kV, Deadbreak Elbow, Straight Receptacle, Bails are required but not included, order separately. Cable Insulation Diameter 0.575 inch to 0.740 inch. Copper Compression Lug. 2/0 Stranded or Compressed, 3/0 Solid or Compact Wire Size. Includes Straight Receptacle Housing, Receptacle Pin Connector, Lubricant, Installation instructions and Crimp Chart
K655ETP-K0270-DRG-S
25kV, 600 Amp Deadbreak, Test and Ground Connector Kit. Cable Insulation Diameter 1.182 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG Compressed/Stranded 4/0 to Compacted/Solid 250 kcmil. With Insulated Cap and Shrink-Fit Jacket Seal Kit.Frequently Asked Questions
What if my cable insulation OD is less than 14.61 mm?
If the insulation OD is lower than 14.61 mm, use cable adapter 160CA-W, where "W" indicates the insulation OD range.
What items are included in the connector kit?
Each kit contains an elbow connector housing, copper lug, probe, probe wrench, standard bail assembly, lubricant, installation instructions, crimp chart, and a V.D. cap-peroxide.
Is the copper lug suitable for all conductor types?
No, the copper lug is suitable for all copper conductors only.
What is the voltage rating of this connector?
The Elastimold IEC 250 amp deadbreak elbow connector is rated for 12/20 (24) kV.
What standards does the elbow connector meet?
The Elastimold IEC 250 amp deadbreak elbow connector meets IEC 60502-4 and CEN 629.1 S2 standards. It is also KEMA certified.
What if my cable insulation OD is less than 14.61 mm?
If the insulation OD is lower than 14.61 mm, use cable adapter 160CA-W, where "W" indicates the insulation OD range.
What items are included in the connector kit?
Each kit contains an elbow connector housing, copper lug, probe, probe wrench, standard bail assembly, lubricant, installation instructions, crimp chart, and a V.D. cap-peroxide.
Is the copper lug suitable for all conductor types?
No, the copper lug is suitable for all copper conductors only.
What is the voltage rating of this connector?
The Elastimold IEC 250 amp deadbreak elbow connector is rated for 12/20 (24) kV.
What standards does the elbow connector meet?
The Elastimold IEC 250 amp deadbreak elbow connector meets IEC 60502-4 and CEN 629.1 S2 standards. It is also KEMA certified.
How to Install 252LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 252LR Deadbreak Elbow Connectors, designed to terminate UD jacketed and non-jacketed cables and connect to 12/20 (24)kV 250 ampere deadbreak bushings or accessory devices. All apparatus must be de-energized during installation.
Estimated time: 1h 30m
Tools needed:
Wrench, Hotstick (fully insulated), Wire brush, Crimp tool (refer to lug chart), Wire strippers, Suitable sensing device (for capacitive test points)
Supplies needed:
Elbow Connector Housing, Compression Lug, Probe, Probe Contact, Lubricant (supplied), Hold-down Bail, No. 14 AWG / 2.5mm copper wire, Appropriate connector (for neutral to ground), Cold shrink tube (optional, for sealing kits), Conductive copper tape (optional, for copper tape shield cable), HV insulated cap(s) or connector(s) (if replacing shipping covers)
- Perform Initial Safety Checks and Cable Training
DANGER: Ensure all apparatus is de-energized before beginning installation. Inspect all parts for damage, correct rating, and compatibility with mating parts. Read the entire installation instruction, check package contents, and verify the elbow housing cable entrance size and compression lug size for proper fit. Train the cable to ensure sufficient slack for ease of operation. Based on your cable type (non-jacketed concentric neutral, jacketed concentric neutral, jacketed with drain wires, or jacketed copper tape shield), follow the specific instructions in the product documentation for initial jacket removal, unwrapping/binding neutral or drain wires, and cutting the cable squarely at the bushing centerline. If using a sealing kit, slide the cold shrink tube onto the cable at this stage.
- Prepare Conductor and Insulation
Remove 2-1/8” (55mm) of the shield and insulation from the cable end, cutting squarely and taking care not to nick the conductor. Wire brush bare aluminum conductors thoroughly and immediately place the compression lug over the conductor, rotating to spread the inhibitor. Position the compression lug so its threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe any excess inhibitor from the outside of the lug and cable. Remove the insulation shield as shown in the product documentation (typically 6-7/8” (175mm) from the cable end) and bevel the insulation end 1/8” (5mm) maximum. Thoroughly clean the insulation to remove all traces of dirt or excess inhibitor.
- Assemble Elbow Connector
Clean the cable insulation and the inside of the elbow housing, then lubricate with the supplied lubricant. DO NOT SUBSTITUTE other lubricants as they may be harmful. Slide the elbow connector onto the cable using a back-and-forth twisting motion. Wipe off all excess lubricant. Align the elbow with the compression lug’s threaded hole. Thread the probe into the lug by hand, taking care not to cross-thread, then tighten with the supplied wrench until the wrench bends.
- Assemble Hold-down Bail
Place the hold-down bail into the hold-down bracket, ensuring it is properly seated and ready for securing the elbow.
- Connect Concentric Neutral
Using a separate No. 14 AWG / 2.5mm copper wire or equivalent, insert one end through the grounding eye on the elbow and twist tightly, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector, providing adequate slack in the wires for elbow operation.
- Connect Elbow to Bushing Plug
Clean the receptacle portion of the elbow connector and the mating bushing. Lubricate these surfaces ONLY IF the transformer and elbow are known to be de-energized. Use a fully insulated hot stick to place the elbow onto the bushing. DO NOT OPERATE BY HAND. DO NOT SEPARATE IF ENERGIZED.
- Secure Elbow with Bail
Pull the hold-down bail up over the crown or top of the elbow so that the eyebolt on the bail is directly over the operating eye. Tighten down on the elbow locator by turning the eyebolt in a clockwise direction. Adjust the nut on the eyebolt until it allows the eyebolt to seat securely in the locator. The nut should act as a stop to prevent the eyebolt from applying excessive force on the elbow. Once the nut is in its final position, it will not need to be readjusted when removing and replacing the elbow.
- Perform Voltage Test (Optional but Recommended)
If performing a voltage test, remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the suitable sensing device used with capacitive test points to determine if the cable is energized. Contamination or incorrect equipment can provide a false “no voltage” indication; treat the elbow as energized until confirmed by other means. After testing, clean the inside surface of the cap, lubricate with silicone lubricant, and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.