ABB Installation Products 252LR-B2035 12/20 24kV, 250 Amp, Deadbreak, Elbow Connector with Test Point, No Sealing Kit, Cable…
UPC: 075114373555
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 24kV rated, 250 Amp deadbreak elbow connector with integrated test point
- Accommodates 35mm² copper conductors with 16.13-22.90mm insulation diameter
- IEC standard compliant for international medium-voltage systems
- Includes compression lug, probe, wrench, bail assembly, and installation accessories
- Deadbreak design enables safe connection/disconnection under load
Specifications
Amperage Rating | 250 A |
Application | 12/20 (24) kV |
Color | Black |
Conductor Range | 35 mm |
Connection | Compression |
Environmental Conditions | Harsh Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | Robust Stainless Steel Pulling Eye. Dual Grounding Eye Positions. Designed to Remain Fully Operational in Harsh Conditions |
Standard | IEC 60502-4, CEN 629.1 S2 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 15 to 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

252LRJS-B2035
12/20 24kV, 250 Amp, Deadbreak, Elbow Connector with Test Point, with Jacket Seal, Cable Insulation Diameter - 16.13 mm - 22.90 mm, Copper Compression Lug, Conductor Size 35mm. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide.
252LR-B2050-S
12/20 24kV, 250 Amp, Deadbreak, Elbow Connector with Test Point, with Sealing Kit, Cable Insulation Diameter - 16.13 mm - 22.90 mm, Copper Compression Lug, Conductor Size 50mm. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide. IEC Standard.
252LR-C2095-S
12/20 24kV, 250 Amp, Deadbreak, Elbow Connector with Test Point, with Sealing Kit, Cable Insulation Diameter - 20.45 mm - 26.92 mm, Copper Compression Lug, Conductor Size 95mm. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide. IEC Standard.
252LRJS-B2025
12/20 24kV, 250 Amp, Deadbreak, Elbow Connector with Test Point, with Jacket Seal, Cable Insulation Diameter - 16.13 mm - 22.90 mm, Copper Compression Lug, Conductor Size 25mm. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide.
252LR-C2070-S
12/20 24kV, 250 Amp, Deadbreak, Elbow Connector with Test Point, with Sealing Kit, Cable Insulation Diameter - 20.45 mm - 26.92 mm, Copper Compression Lug, Conductor Size 70mm. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide. IEC Standard.
252LRJS-B2050
12/20 24kV, 250 Amp, Deadbreak, Elbow Connector with Test Point, with Jacket Seal, Cable Insulation Diameter - .16.13 mm - 22.90 mm, Copper Compression Lug, Conductor Size 50mm. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide.
252LRJS-C2070
12/20 24kV, 250 Amp, Deadbreak, Elbow Connector with Test Point, with Jacket Seal, Cable Insulation Diameter - 20.45 mm - 26.92 mm, Copper Compression Lug, Conductor Size 70mm. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide.
K656CCPG0240S
15/25kV, 600 Amp Combo-T Elbow/Connecting Pluf with Stud, Cable Adapter and Lug Kit with Test Point and with 200ECS Cold Scrinkable Jacket Seal. Cable Insulation Diameter G - 0.760 to 0.950 inch. Aluminum Compression Lug, Conductor Size 240 - 1/0 Stranded/Compressed or 2/0 Solid/Compact.Frequently Asked Questions
What items are included in the connector kit?
Each kit contains the elbow connector housing, copper lug, probe, probe wrench, standard bail assembly, lubricant, installation instructions, crimp chart, and V.D. cap-peroxide.
What items are included in the connector kit?
Each kit contains the elbow connector housing, copper lug, probe, probe wrench, standard bail assembly, lubricant, installation instructions, crimp chart, and V.D. cap-peroxide.
What is the current rating of the elbow connector?
The Elastimold IEC deadbreak elbow connector has a current rating of 250 amps.
Are installation instructions provided with the kit?
Yes, installation instructions (IS-1626/IS-1627) are included in each connector kit.
What if my cable insulation OD is under 14.61 mm?
For insulation ODs lower than 14.61 mm, use cable adapter 160CA-W, selecting 'W' based on the insulation OD range.
What conductor types are compatible with the copper lug?
The copper lug included with the connector is suitable for all copper conductors only.
How do I choose the correct compression lug?
Select the proper compression lug 'X' code from the conductor code table based on your conductor size.
How do I select the correct cable adapter?
Determine your cable's insulation diameter and choose the 'W' letter code from Table W that best straddles this range.
Which industry standards does the connector meet?
The connector meets IEC 60502-4 and CEN 629.1 S2 standards, and is KEMA certified.
What is the voltage rating of the elbow connector?
The Elastimold IEC 250 amp deadbreak elbow connector is rated for 12/20 (24) kV.
How to Install the 252LR Deadbreak Elbow Connector
This guide provides step-by-step instructions for the safe installation and connection of the 252LR Deadbreak Elbow Connector. It covers initial cable training, precise cable preparation, elbow assembly, neutral connection, and final connection to a deadbreak bushing. Always ensure all apparatus are de-energized before installation or removal.
Estimated time: 1h 30m
Tools needed:
Wrench, Wire brush, Hot stick, Crimp tool, Wire strippers, Cable cutting tool
Supplies needed:
Elbow Connector Housing, Compression Lug, Probe, Probe Contact, Lubricant, Hold-down Bail, No. 14 AWG / 2.5mm copper wire, Appropriate connector (for neutrals), Vinyl tape (optional), Cold shrink tube (if using sealing kit), Conductive copper tape (if using 200ECS-G2 kit)
- De-energize Apparatus and Inspect Parts
Ensure all apparatus are de-energized before beginning installation. Inspect all parts for damage, correct rating, and compatibility with mating components. Read the entire installation instruction before starting, and check package contents for completeness and damage.
- Train and Prepare Cable for Termination
Train the cable to ensure adequate slack for operation. Connect neutral wires to the tank ground with a jumper or braid, ensuring extra length for hotstick operation. Cut the cable squarely at the centerline of the bushing. Remove the outer jacket 9-5/8 inches (240mm) back from the bushing centerline (refer to the document for specific cable types and measurements). If applicable, unwrap and bind neutral or drain wires, or wrap conductive copper tape over the shield end. Slide any cold shrink tube onto the cable.
- Prepare Conductor and Crimp Lug
Remove the insulation shield and insulation 2-1/8 inches (55mm) from the cable end, cutting squarely without nicking the conductor. Wire brush bare aluminum conductors and immediately place the compression lug over the bushing, rotating to spread inhibitor. Align the lug's threaded hole with the bushing bore. Crimp the lug starting at the crimp line mark, rotating 180 degrees for each successive crimp. Carefully wipe excess inhibitor from the lug and cable. Remove the remaining insulation shield as shown in the document, and bevel the insulation end 1/8 inch (5mm) maximum. Thoroughly clean the insulation.
- Assemble the Elbow Connector
Clean the cable insulation and the inside of the elbow housing, then lubricate with the supplied lubricant. DO NOT SUBSTITUTE other lubricants. Slide the elbow connector onto the cable using a back and forth twisting motion, then wipe off all excess lubricant. Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, taking care not to cross-thread, then tighten with a wrench until the wrench bends.
- Assemble the Hold-down Bail
Place the hold-down bail into the hold-down bracket.
- Connect Concentric Neutrals to Ground
Using a separate No. 14 AWG (2.5mm) copper wire or equivalent, insert one end through the grounding eye on the elbow and twist tightly. Twist all neutral wires together and connect them to ground using an appropriate connector, providing adequate slack for elbow operation.
- Connect Elbow to Bushing Plug
Clean the receptacle portion of the elbow connector and the mating bushing, then lubricate with the supplied lubricant ONLY if the transformer and elbow are known to be de-energized. Use a fully insulated hot stick to place the elbow onto the bushing. DO NOT operate by hand or separate if energized.
- Secure the Elbow with the Bail
Pull the hold-down bail up over the crown or top of the elbow so the eyebolt on the bail is directly over the operating eye. Tighten the eyebolt by turning it in a clockwise direction. Adjust the nut on the eyebolt to allow it to seat securely in the locator, acting as a stop to prevent excessive force on the elbow.
- Perform Voltage Test (Optional)
Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. Use a suitable sensing device designed for capacitive test points to determine if the cable is energized. Do not use conventional voltage measuring equipment. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means to prevent serious or fatal injury. After testing, clean and lubricate the inside of the cap and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.