ABB Installation Products 162A4-B5250 15kV, 200 Amp, Loadbreak Elbow-Bushing Insert, Cable Insulation Diameter 0.635 inch to…
UPC: 075114319744
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV, 200 Amp rated for medium-voltage applications
- Bi-metal compression lug for 2/0-3/0 AWG conductors (compressed stranded or solid)
- Cable insulation diameter compatibility: 0.635" to 0.905"
- Loadbreak design enables safe energized disconnection under load
- Includes elbow connector housing, probe, wrench, bushing insert, and accessories
Specifications
Amperage Rating | 200 A |
Application | 15kV 200 Amp |
Color | Black |
Conductor Range | 2/0 STR/COMPR AWG , 3/0 SOL/COMPT AWG |
Connection | Compression |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 2.9 in |
Length | 73.66 mm |
Material | Housing - EPDM-Rubber |
Special Features | Non-corrosive capacitive test point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow with Test Point and Bushing |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

162LR-B5250-SG3
200 Amp, 15kV, Loadbreak Elbow Connector, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. 200ECS-G3 Jacket Seal and Grounding Kit Included.
167ELR-7495-5240
15kV, 200 Amps, Loadbreak Repair Elbow Connector without Test Point. Cable Insulation Diameter .740-.950 inches (18.80-24.13mm). Bi-Metal Compression Lug. Conductor Sizse 240 - 1/0 Stranded/Compressed or 2/0 Solid/Compact or 53.49 mmsq. No Sealing Kit. Includes Elbow Housing, Compression Lug, Probe, Probe Wrench, Tube of Lubricant, Crimp Chart, and Installation Instructions.
168ELR-7495-5200
15kV 200 Amp Loadbreak Repair Elbow with Test Point. Cable Insulation Diameter 0.740-0.950 inches (18.80-24.13mm). BiMetal Compression Lug, Conductor Size #4 Stranded #3 Solid/Compressed. Includes Elbow Connector Housing, Compression Lug, Probe Wrench, Probe, Tube Lubricant, Installation Instructions and Crimp Chart. ANSI/IEEE Standard 386.
K655L3-J0330
15-25kV, 600 Amp, Deadbreak, 3-Way L-Kit without Test Point, without Seal. 29.49 inch (749.0mm). Cable Insulation Diameter 0.980 - 1.180 inches (24.9-30.0mm). Aluminum Compression Lug. Conductor Size 330 - 500 kcmil Stranded/Compressed or 600 kcmil Solid/Compact.
168FLR3-B5230
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Bi-Metal Connector, Conductor size 1 AWG Stranded/Compressed, 1/0 AWG Solid/Compact.
656ETP-N-AC04-DRG
15kV, 600 Amp, Elbow Tap Plug, Test and Ground Connector Kit with Test Point. Includes Insulated Cap, Test and Ground Reducing Tap Plug, 600 Series Elbow Housing, Cable Adapter and Tin-Plated Aluminum ShearBolt Lug. Cable Insulation Diameter N - 1.515 to 1.780 inch. Conductor Size AC04 - 750 to 1250 kcmil Stranded/Compressed/Solid/Compact.
168AFLR1-B5220
8.3kV, 200 Amp, Loadbreak Fused Elbow Connector with Two Direct Test Points. No Sealing Kit. Small Housing - 8-7/8 inches wide x 16-7/6 inches long. Cable Insulation Diameter - 0.635-0.905 inches. Bi-Metal Connector. #2 Stranded/Compressed or #1 Solid/Compact conductor size.
168FLR1C5200-S
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Bi-Metal Crimp Connector, Conductor size #4 Stranded/Compressed or #3 Solid/Compact. S - Cold-Shrinkable Jacket Seal.Frequently Asked Questions
What is the voltage rating of the 162A4 elbow?
The 162A4 elbow is rated for 15kV voltage class, with an 8.3kV max phase-to-ground operating voltage and 14.4kV max phase-to-phase.
What is the impulse withstand rating (BIL)?
The impulse withstand (BIL) rating is 95kV (1.2 x 50 microsecond wave).
What sealing kit is for copper tape shield cables?
For copper tape shield cables, the 200ECSG3 sealing and grounding kit is used, or add suffix "-SG3" to the part number for cables with nominal O.D. 0.80-1.50 in.
What sealing kit is for jacketed concentric neutral cables?
For jacketed concentric neutral cables, the 200ECS sealing kit is used, or add suffix "-S" to the part number for cables with nominal O.D. 0.80-1.50 in.
Is a sealing and grounding kit recommended?
Yes, for safety purposes, a sealing and grounding kit with the loadbreak elbow is highly recommended.
What types of conductors are compatible with the lugs?
Bi-metal compression lugs are suitable for copper or aluminum conductors, while copper compression lugs are for copper conductors only.
Is the 162A4 elbow submersible?
Yes, the 162A4 features a fully shielded, fully submersible molded rubber housing.
What standards does this product meet?
The product meets ANSI/IEEE Standard 386, Latest Revision.
Can the 162A4 be operated while energized?
Yes, it includes provisions for energized operation using standard hotstick tools, allowing loadmake/loadbreak operation and a visible disconnect.
What cable insulation diameters are compatible?
The 162A4 allows connection of cables with insulation diameters from .575 in (14,6mm) to 1.220 in (31,0mm).
How to Install the 162LR Loadbreak Elbow Connector
This guide provides step-by-step instructions for the safe and proper installation of the 162LR Loadbreak Elbow Connector, including cable preparation, assembly, and grounding.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Wire brush, Crimp tool, Probe wrench, Hotstick, Suitable sensing device (for capacitive test points)
Supplies needed:
Elbow Connector Housing, Compression Lug, Probe, Lubricant (Do Not Substitute), Copper wire (No. 14 AWG / 2.5mm), Appropriate connector for neutral wires, Vinyl tape (if applicable), Conductive copper tape (if applicable), Cold shrink tube (if using sealing kit), Insulated cap(s) or connector(s)
- Prepare for Installation and Inspect Components
DANGER: Ensure all apparatus is de-energized before beginning installation. This product must be installed by competent personnel trained in high voltage safety practices. Inspect all package contents for completeness and damage. Verify all components fit properly with the cable and mating products. Check the probe threads by hand-threading into the compression lug; replace if resistance is encountered.
- Prepare the Cable for Termination
Train the cable to ensure adequate slack for operation. Based on your cable type (non-jacketed, jacketed concentric neutral, jacketed with drain wires, or jacketed copper tape shield), prepare the cable by cutting it squarely at the bushing centerline and removing the outer jacket, shield, or tape as specified in the product documentation (e.g., 9-5/8" (240mm) for jacketed cables). Unwrap and manage neutral or drain wires, or wrap conductive copper tape as required. If using a cold shrink sealing kit, slide the cold shrink tube onto the cable now.
- Prepare Cable Insulation and Install Compression Lug
Remove 2-1/8" (55mm) of the shield and insulation from the cable end, cutting squarely without nicking the conductor. Wire brush bare aluminum conductors immediately. Install the compression lug, rotating it to spread inhibitor, and align its threaded hole with the bushing bore. Crimp the lug according to the crimp chart provided with the lug, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe off any excess inhibitor. Remove 6-7/8" (175mm) of the insulation shield and bevel the insulation end by a maximum of 1/8" (5mm). Thoroughly clean the insulation to remove all dirt or inhibitor traces.
- Assemble the Elbow Connector
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant; do not substitute. Slide the elbow connector onto the cable using a back-and-forth twisting motion, then wipe off any excess lubricant. Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, ensuring it turns freely for approximately four turns before becoming snug. Tighten the probe with the supplied probe wrench until the wrench bends.
- Ground the Elbow and Connect Neutrals
Insert one end of a separate No. 14 AWG (2.5mm) copper wire or equivalent through the grounding eye on the elbow and twist it tightly, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector, ensuring adequate slack for elbow operation. If using a cold shrink grounding kit, follow its specific instructions.
- Connect the Elbow to the Bushing Plug
DANGER: Re-confirm that both the transformer and the elbow are de-energized before proceeding. Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. Securely fasten a hotstick to the loadbreak connector pulling eye. Insert the probe tip approximately 2" (50mm) into the bushing, then immediately push the elbow home with a fast, firm, straight motion, using sufficient force to engage the internal lock. DO NOT OPERATE BY HAND.
- Perform Voltage Test (Optional)
If the connector is equipped with a capacitance test point, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device; do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points and follow its manufacturer's directions to determine if the cable is energized. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means. After testing, clean the inside of the cap, lubricate with silicone lubricant, and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.