ABB Installation Products 15PCJ2N2440 15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable…
UPC: 075114423762
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV voltage rating for high-power applications.
- Universal housing for versatile cable compatibility.
- Accommodates cable insulation diameters from 1.515" to 1.780".
- Designed for 1250 kcmil stranded/compressed copper conductors.
- Style 2 joint with separate cable adapters for secure termination.
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 1250 kcmil |
Connection | Compression |
Connection Type | Joint Style |
Insulation | Yes |
Material | Copper |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | Length 21 in |
Size | Cable Insulation Diameter: 1.515 inch to 1.780 inch, Conductor Size: 1250 kcmil |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other severe service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Power Cable Joint |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

35PCJ1Q1440-S
35kV Power Cable Joint Style 1, Cable Insulation Diameter 1.900 inch to 2.120 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1250. Cold Shrinkable Jacket Seal included.
25PCJ1L2310
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Solid 500.
25PCJ1N1410
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Conductor. Conductor Size AWG Stranded 1000. Length 15-3/4 inch, Diameter 3-3/16 inch.
35PCJ1H1210
35kV Power Cable Joint Style 1, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #3/ Compacted Solid #2.
25PCJ2H1240
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
25PCJ2H2250
25 kV Power Cable Joint, Style 2 Universal Housing and Separate Cable Adapters. Cable Insulation Diameter H - .850 - 1.050 inch, Copper Conductor, Cable Size 250 - 2/0 Stranded, Compressed or 3/0 Compact. Solid
25PCJ2H2280
25 kV Power Cable Joint, Style 2 Universal Housing and Separate Cable Adapters. Cable Insulation Diameter H - .850 - 1.050 inch, Copper Conductor, Cable Size 280 - 250 kcmil Stranded/Compressed.
15PCJ1K2330-SG3
15kV, Power Cable Joint with SG3 - Cold-Shrinkable Jacket Seal with Copper Braid and Constant Force Spring. Cable Insulation Diameter K - 1.090 to 1.310 inch. Copper Compression Lug, Conductor Size 330 - 500 kcmil Stranded/Compressed or 600 kcmil Solid/Compact.Frequently Asked Questions
What is the maximum cable insulation diameter supported?
The ABB 15kV Power Cable Joint Style 2 supports cable insulation diameters ranging from 1.515 inches to 1.780 inches.
What conductor size is compatible with this joint?
This joint is designed for copper conductors sized at 1250 kcmil, specifically for stranded or compressed configurations.
What type of conductor material is this joint for?
The ABB 15kV Power Cable Joint Style 2 is designed for copper conductors.
What is the voltage rating of this cable joint?
This ABB cable joint has a voltage rating of 15kV.
How to Install the 15/25/35PCJ2WXXXX-RC Straight Joint
This guide provides step-by-step instructions for the permanent, fully shielded, and submersible installation of the 15/25/35PCJ2WXXXX-RC straight joint for aluminum and/or copper conductor, wire shielded cables.
Estimated time: 2h
Tools needed:
Wire strippers, Circular cutting tool or glass scraper, Wire brush, Hex wrench (supplied with collars), Crimping tool, Measuring tape or ruler
Supplies needed:
Joint Housing, Splice (Conductor Contact), Cable Adapters, Lubricant, Retaining Collars, Hose Clamp, Electrical tape, Appropriate grounding connector, #14 AWG copper wire (if needed), Heat/cold shrink kit (user-supplied), Materials for bonding lead sheath/neutral wires (user-supplied)
- Prepare for Installation
Ensure all apparatus is de-energized and follow all local and national work rules. Inspect all kit components for damage and compatibility. Read the entire instructions. Gather all required tools and maintain cleanliness. Examine cable ends for moisture and contaminants. Remove graphite coatings 12 inches (30.5cm) beyond the cable jacket cut; avoid sanding. If conductors are strand-filled, consult the cable manufacturer for welding/crimping procedures.
- Prepare Cable Jackets and Position Joint Housing
Carefully remove the cable jacket from both cables for a distance of 11-1/4 inches (285.7mm). Fold back shield wires and tape the ends of wires on Cable 1 to the jacket, allowing sufficient extra length for later rejoining. Clean the surface of the insulation shield, shield wires, and jacket for a distance of 30 inches (760mm). Slide the joint housing onto Cable 1 to a distance of 30 inches (760mm).
- Prepare Cable Insulation
Using the stripping guide, carefully remove the insulation shield and cable insulation. DO NOT CUT OR NICK THE INSULATION, as this can lead to assembly failure. Wrap two turns of electrical tape 1 inch (25mm) from the edge of the insulation shield on both cables to serve as markers. Clean the cable insulation thoroughly, then lubricate it to create a build-up or ramp of lubricant at the edge of the insulation shield.
- Install Cable Adapters
Take one cable adapter and lubricate the inside of both ends. Install this cable adapter onto Cable 1 until it meets the tape marker. Repeat this process for the second cable adapter on Cable 2, ensuring it also meets its respective tape marker. The insulation should extend approximately 5/16 inch beyond the cable adapter.
- Install Retaining Collars
Select the appropriate retaining collar and partially thread the setscrews (refer to instructions packaged with collars). Position the retaining collar over the insulation, ensuring it is flush against the cable adapter. Using the supplied hex wrench, tighten each set screw one or two turns at a time to keep the collar centered over the insulation. Continue tightening until all setscrews are below the surface of the collar. Repeat for Cable 2.
- Splice Conductors and Verify Dimensions
Thoroughly clean the ends of the cable adapters and the exposed cable areas. Install a hose clamp around the adapter on the opposite side of the splice from where the housing is stored to secure the adapter during assembly. Tape over the hose clamp to create a smooth surface. Wirebrush the exposed conductors of both cables and immediately insert them into the splice. Crimp the splice according to its recommendations. Wipe off any excess inhibitor. Verify the distance between cable adapters does not exceed 8-1/2 inches (215mm) after crimping, and 8-3/4 inches (222mm) before final housing slide. If dimensions are exceeded, redo assembly. Clean and lubricate the outside surface of the cable adapters.
- Complete Joint Assembly and Grounding
Slide the joint housing into its final position, centering it over the cable adapters. Remove all temporary tape; ensure no cable or adapter insulation is exposed after positioning the joint. Reshape the shield wires and secure them to the ends of the joint. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use a separate #14 AWG copper wire or equivalent. Connect all joint grounding wires and remaining shield wires using an appropriate connector.
- Reconstruct Cable Jacket
Reconstruct the cable jacket (where applicable) over both cables and also over the joint housing. This typically requires a heat or cold shrink kit, which is not included in this package and must be supplied by the installer. Ensure the reconstructed jacket provides a complete seal and protection for the joint.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.