ABB Installation Products 35PCJ1H1210 35kV Power Cable Joint Style 1, Cable Insulation Diameter 0.850 inch to 1.050 inch.…
UPC: 075114355865
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV rated power cable joint
- Accommodates 0.850" to 1.050" cable insulation diameter
- Aluminum compression lug
- Suitable for AWG #3 compressed stranded or #2 compacted solid conductors
- ABB Installation Products quality
Specifications
Connection Type | Compression Lug |
Material | Aluminum |
Series | 35PCJ1H |
Size | 0.850 inch to 1.050 inch |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

35PCJ1K1260-S
35kV Power Cable Joint Style 1, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95. Cold Shrinkable Jacket Seal included.
25PCJ2H1240
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
25PCJ2H2250
25 kV Power Cable Joint, Style 2 Universal Housing and Separate Cable Adapters. Cable Insulation Diameter H - .850 - 1.050 inch, Copper Conductor, Cable Size 250 - 2/0 Stranded, Compressed or 3/0 Compact. Solid
25PCJ2H2280
25 kV Power Cable Joint, Style 2 Universal Housing and Separate Cable Adapters. Cable Insulation Diameter H - .850 - 1.050 inch, Copper Conductor, Cable Size 280 - 250 kcmil Stranded/Compressed.
15PCJ1K2330-SG3
15kV, Power Cable Joint with SG3 - Cold-Shrinkable Jacket Seal with Copper Braid and Constant Force Spring. Cable Insulation Diameter K - 1.090 to 1.310 inch. Copper Compression Lug, Conductor Size 330 - 500 kcmil Stranded/Compressed or 600 kcmil Solid/Compact.
25PCJ1L1230
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded #1 or Solid 1/0. Overall Length 14-3/8 inch, Diameter 2-25/32 inch.
69TCJS1R140PVAGNB
69kV Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style - 1, Insulation Diameter Range R - 2.20 to 2.58 inch, Aluminum Connector, Connector Code 40P - 1.036 to 1.100 inch, Bore Size 1.125, Type Shield - Copper Tape, Metallic Screen Continuity Kit - 4/0 Welding cable, 6 Foot Quantity 4 but 1 without Split Bolts, Outer Jacket Restoration Kit - Heat Sink.
RC6-HT
High Temperature Insulated Nylon Wire Joints for Minimum Wire Range (3) #16 to Maximum Wire Range (3) #14, WhiteFrequently Asked Questions
What conductor materials are compatible with PCJ joints?
PCJ power cable joints can be used with both copper and aluminum conductors.
What voltage classes are available for PCJ joints?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
What are the two styles of PCJ power cable joints?
Style 1 has a single-piece housing for straight splicing. Style 2 has a universal housing with separate cable adapters for transition splicing.
Where can Elastimold PCJ joints be installed?
They can be installed in direct-burial, underground vault, and even overhead applications. They provide a permanent, fully shielded, fully submersible splice.
What is the maximum cable size supported?
These joints can be used with cable sizes up to 1250 kcmil.
What types of cable splicing do PCJ joints support?
PCJ power cable joints support straight splicing of two similar cables or transition splicing of different cable sizes.
What are Elastimold PCJ power cable joints?
They are power cable joints with permanently crimped connectors inside EPDM rubber housings, offering proven reliability.
What type of connector is needed for copper-to-copper splices?
An all-copper compression connector is required for copper-to-copper connections. Copper connectors should not be used on aluminum conductors.
What are the continuous and short-time current ratings?
The continuous current rating is equal to the cable rating. The short-time current rating is equal to the cable rating up to 35 kA.
What safety standards do PCJ joints meet?
The shield design meets IEEE 592 standard, and connectors meet ANSI 119.4 Class A and Class 3 ratings.
How to Install the 15/25/35PCJ1 Series Cable Straight Joint
This guide provides step-by-step instructions for the permanent, fully shielded, and fully submersible installation of the 15/25/35PCJ1 series straight joint for aluminum and/or copper conductor, wire shielded cables.
Estimated time: 1h 30m
Tools needed:
Cable cutter, Cable stripping tool, Tapering tool, Wire brush, Crimping tool, Deburring tool
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Appropriate grounding connector, No. 14 AWG copper wire (if needed), Jacket sealing or restoration kit (if applicable)
- Ensure Safety and Prepare Materials
DANGER: All apparatus must be de-energized during installation or removal of parts. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Inspect all parts for damage, rating, and compatibility. Read these instructions completely before starting. Have all required tools at hand and maintain cleanliness throughout the procedure.
- Prepare Cables for Joint Centerline
Overlap both cables and cut them to 12 inches (305mm) from the intended centerline of the joint. This ensures sufficient length of shield wires to rejoin over the joint. If applicable, remove the cable jacket of Cable 1 to 34 inches (865mm) and Cable 2 to 20 inches (510mm). Fold back the shield wires. Finally, cut both cables at the joint centerline.
- Taper Cable 1 and Position Housing
Taper the edge of Cable 1's insulation from 1/2 inch to 1-1/2 inches (13mm to 38mm). Clean and then lubricate the insulation shield of Cable 1. Lubricate the inside bore of the joint housing on both ends. Carefully slide the joint housing onto Cable 1 up to the shield wires. This procedure will not contaminate electrical interfaces.
- Strip Cable Insulation and Shield
Using the stripping guide provided, carefully remove 2 inches (51mm) of cable insulation from both cables. Then, carefully remove 6 inches (150mm) of the insulation shield from both cables. WARNING: DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR, as this could result in assembly failure.
- Install and Crimp Conductor Splice
If using aluminum conductors, wirebrush them thoroughly and immediately insert them into the splice. Ensure the 'Check' dimension does not exceed 5 inches (127mm); if it does, redo the assembly. Crimp the splice following the manufacturer's recommendations. Wipe off any excess inhibitor (if applicable). Verify the distance between cable insulations does not exceed 5-1/4 inches (133mm); if it does, redo the assembly. Remove any sharp protrusions or burrs generated during crimping and clean all metal chips/filings from the splice and joint assembly area.
- Lubricate Cables for Housing Installation
Clean the cables where indicated. Lubricate the cables in the direction of the arrows to provide a build-up or ramp of lubricant at the edge of the insulation shield. This prepares the cables for the final housing installation.
- Position Housing and Connect Grounding
Slide the joint housing into its final position. Proper positioning is ensured by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield. Reshape the shield wires and secure them to the ends of the joint as shown in the diagram. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use a separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and any remaining shield wires using an appropriate connector.
- Restore Cable Jacket (If Applicable)
If applicable, reconstruct the cable jacket over both cables and also over the joint housing. WARNING: If one or both of the cables being joined are jacketed, it is critical to seal the ends of the jacket or completely restore the jacket across the joint. Follow standard operating procedures or instructions provided with compatible jacket sealing or restoration kits to provide the appropriate seals or restoration.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.