ABB Installation Products 15PCJ2F2240 15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable…
UPC: 075114151467
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV Voltage Class, IEEE Standard 404 Rated
- Accommodates 0.640" to 0.820" Cable Insulation Diameter
- For AWG Stranded 1/0 or Solid 2/0 Copper Conductors
- Fully Shielded, Fully Submersible Molded Rubber Housing
- Universal Housing with Separate Cable Adapters for Installation Flexibility
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 1/0 STR AWG , 2/0 SOL AWG |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 16-3/8 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

15PCJ1F2240
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.640 inch to 0.820 inch. Copper Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
25PCJ2H1250-H1240
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
25PCJ2K2300-J2270
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Stranded 350. Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
15PCJ2F1210
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded #3/Solid #2.
25PCJ1-K1280
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size kcmil Stranded-Compressed 250, Solid-Compact 300.
69TCJS1R246PVDHNN
69kV, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 1, Housing Size R - Bore Diameter 1.930 inch, Insulation Range 2.200-2.580 inch, Connector Type - Copper, Conductor Code 46P - 1.328-1.377 inch Diameter
15PCJ2F1240
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
15PCJ2J1330
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size Stranded 500.Frequently Asked Questions
What voltage rating does this cable joint support?
This cable joint is rated for 15kV medium-voltage applications.
Does this joint include a universal housing?
Yes, the joint features a universal housing with separate cable adapters for installation flexibility.
What conductor sizes are compatible with this joint?
The joint supports stranded 1/0 AWG and solid 2/0 AWG copper conductors.
What is the insulation diameter range for this joint?
The joint accommodates cable insulation diameters from 0.640 inch to 0.820 inch.
Is this joint suitable for underground installations?
Yes, the joint is designed for both underground and aerial medium-voltage power distribution.
How to Install the 15/25/35PCJ2W Cable Joint
This guide provides detailed instructions for the permanent, fully shielded, and submersible installation of the 15/25/35PCJ2W series straight joint for aluminum and/or copper conductor, wire shielded cables. Ensure all apparatus is de-energized before beginning.
Estimated time: 2h
Tools needed:
Wire strippers, Circular cutting tool, Glass scraper, Wirebrush, Hex wrench, Crimping tool
Supplies needed:
Joint Housing, Splice (Conductor Contact), Cable Adapters, Lubricant, Retaining Collars, Hose Clamp, Electrical tape, #14 AWG copper wire (or equivalent), Appropriate connector (user supplied), Heat/cold shrink jacket (user supplied)
- Perform Safety Checks and Initial Preparation
DANGER: Ensure all apparatus is de-energized before installation or removal. Inspect all components for damage, rating, and compatibility. Examine mating cable ends for moisture and contaminants. Remove graphite coatings 12 inches (30.5cm) beyond the cable jacket cut using a circular cutting tool or glass scraper; avoid sanding. If conductors contain strand filled or water-blocking material, contact the cable manufacturer for welding/crimping procedures.
- Prepare Cable Jackets and Position Housing
Using a stripping guide, carefully remove the cable jacket of both cables for a distance of 11-1/4 inches (285.7mm). Fold back the shield wires and tape the end of the wires on Cable 1, allowing enough extra length to rejoin later. Clean the surface of the insulation shield, shield wires, and jacket for a distance of 30 inches (760mm). Slide the joint housing onto Cable 1 to a distance of 30 inches (760mm).
- Prepare Cable Insulation
Using the stripping guide, carefully remove the insulation shield and cable insulation. CAUTION: DO NOT CUT OR NICK THE INSULATION, as this could lead to assembly failure. Wrap two turns of tape 1 inch (25mm) from the edge of the insulation shield on both cables to serve as a marker. Clean the cable insulation thoroughly, then lubricate it to create a build-up or ramp of lubricant at the edge of the insulation shield.
- Install Cable Adapters and Retaining Collars
Lubricate the inside of both ends of one cable adapter. Install this cable adapter onto Cable 1 until it meets the tape marker. Repeat this process for the other cable adapter on Cable 2. Select the retaining collars and partially thread the proper size setscrews. Position each retaining collar over the insulation, flush against its respective cable adapter. Using the supplied hex wrench, tighten each set screw one or two turns at a time to keep the collar centered, then continue tightening until the screws are below the collar surface.
- Splice Conductors
Thoroughly clean the ends of the cable adapters and the cable where shown. Install a hose clamp around the adapter on the opposite side of the splice from where the housing is stored to hold the adapter in place. Tape over the hose clamp to form a smooth surface. Wirebrush the exposed conductors of both cables and immediately insert them into the splice. Verify the 'Check' dimension does not exceed 8-1/2 inches (215mm); redo assembly if it does. Crimp the splice according to its recommendations. Wipe off all excess inhibitor. Check the distance between cable adapters; redo assembly if it exceeds 8-3/4 inches (222mm). Clean and lubricate the outside surface of the cable adapters.
- Complete Joint Assembly and Grounding
Slide the joint housing into its final position, centering it over the cable adapters. Remove all tape, ensuring that no cable or adapter insulation is exposed after positioning the joint. Reshape the shield wires and secure them to the ends of the joint. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and remaining shield wires using an appropriate connector. Reconstruct the cable jacket (where applicable) over both cables and over the joint housing using heat/cold shrink materials (not included).
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.